Specification sheet (English) - Trend
Specification sheet (English) - Trend
Specification sheet (English) - Trend
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
IQ23x<br />
Data Sheet<br />
Field Maintenance<br />
The IQ23x Series Controller requires virtually no routine maintenance,<br />
however it is recommended that the lithium battery be<br />
replaced every 5 years, as explained in the IQ23x Installation<br />
Instructions, TG200539, Sheet 3, Options.<br />
Warning: Contains no serviceable parts.<br />
Opening the unit exposes hazardous voltages<br />
DISPOSAL<br />
COSHH (Control of Substances Hazardous to Health -<br />
UK Government Regulations 2002) ASSESSMENT FOR<br />
DISPOSAL OF IQ CONTROLLER. The only part affected is the<br />
lithium battery which must be disposed of in a controlled way.<br />
RECYCLING. All plastic and metal parts are recyclable.<br />
The printed circuit board may be sent to any PCB recovery<br />
contractor to recover some of the components for any metals<br />
such as gold and silver.<br />
WEEE Directive:<br />
At the end of their useful life the packaging,<br />
product, and battery should be disposed of by a<br />
suitable recycling centre.<br />
Do not dispose of with normal household waste.<br />
Do not burn.<br />
Installation<br />
The IQ23x Controller is installed in a panel, using 4 screws and washers. The procedure involves:<br />
mount the controller in position<br />
connect power, do not power up<br />
connect the network<br />
terminate the I/O, leave unconnected<br />
connect the auxiliary output supply, if used<br />
connect any input or output interfaces<br />
specify network address and baud rate<br />
install any link headers<br />
perform input channel linking<br />
disconnect I/O, network<br />
power up<br />
check network<br />
configure the strategy<br />
check operation<br />
connect outputs<br />
test system<br />
backup configuration<br />
This installation procedure, is covered by the IQ23x Installation Instructions, TG200539. Sheets 1 and 2 cover Fixing and<br />
Configuration respectively. Sheet 3, Options, covers fitting an external 2-line display panel (if KIT/2xx/RDS is already fitted),<br />
connecting an external NDP or local PC, mounting an IQ23x in an enclosure (ENCLS/), Replacing the battery, and the Zero Address<br />
Baud Rate Switch Reset. Replacing IQ111 (+), 131 (+) is covered by Sheets 4 to 7 respectively, and moving an integral node from an<br />
IQ111,(+), 131 (+) to an IQ23x is covered by Sheets 8 and 9.<br />
Other installation instructions that provide useful information are:<br />
Fitting Link Headers: LKE Installation Instructions TG102487<br />
Fitting and integral node: KIT/NODE/IQ23x Installation Instructions TG200570.<br />
12 IQ23x Series Controllers Data Sheet TA200538 Issue 2, 18-Jan-2012