IQ23x<br />
Data Sheet<br />
Integral nodes (continued)<br />
CNC2, PNC2, INC2, TMN (TMN board - circa 1999)<br />
24 Vdc Power<br />
CNC2, PNC2 local network<br />
INC2 local network or internetwork segment A<br />
TMN local network or internetwork<br />
= * = )<br />
%<br />
- 6<br />
'<br />
&<br />
CNC2, PNC2, TMN not used<br />
INC2 internetwork or internetwork segment B<br />
, AL )<br />
RS232<br />
CNC2 to device<br />
PNC2 to printer<br />
INC2 not normally used<br />
TMNE to modem<br />
, AL *<br />
@ A<br />
#<br />
$<br />
Integral<br />
modem<br />
(TMNH only)<br />
earth tag<br />
PSTN (TMNH only)<br />
XNC220: This node replaces the XNC but is only available in a<br />
boxed form (NBOX/XNC220) and cannot be mounted in an IQ.<br />
ENC2: This node is used with the EMMPO2, but is only available<br />
in boxed form (NBOX/ENC2) and cannot be mounted in an IQ.<br />
Baud Rates: All the nodes are capable of being linked for 1k2,<br />
4k8, 9k6, or 19k2 baud for both of the network connections (Lan<br />
A, Lan B); except for the LINC which can only be linked for 1k2,<br />
9k6 or 19k2. The IQ23x is capable of all 4 baud rates. The INC2<br />
is also capable of being linked for 38k4 baud on its internetwork<br />
or internetwork segment B port (Lan B).<br />
Display Panel<br />
The IQ23x can have an integral 2 line display panel either<br />
pre‐fitted, or post-fitted (by replacing the cover with COVER/<br />
DP2/IQ23x). The display panel looks different to that of the<br />
IQ111 or 131, as the membrane has been through a layout<br />
change. However, although the arrow and letter keys are in<br />
different places, they have the same functionality.<br />
Note that an integral display panel fitted in an IQ111(+) or<br />
IQ131(+) may not be used with an IQ23x.<br />
An external 2 line display panel (e.g. HDP, FPK) could be<br />
directly fitted to an IQ111 (+),131 (+). The same display panel<br />
can be connected to an IQ23x, but it requires the internal fitting<br />
of KIT/2xx/RDS, the remote display panel support kit.<br />
Controller Baud Rates<br />
The controllers have different local supervisor port, and<br />
network baud rates. The network baud rate is set by a link; the<br />
supervisor baud rate is now fixed at 9k6 but was configurable by<br />
link on the earlier controllers. The IQ131 is unique in not having<br />
CNC functionality built in to its firmware so it needed a CNC to<br />
be fitted, and the network baud rate is set by a link on the CNC<br />
board.<br />
Controller Address<br />
The IQ111 controller address was set in configuration mode so<br />
it should be checked in configuration mode before replacement.<br />
The IQ131 address is set by DIL switches on its CNC. The<br />
Address is set by DIL switches on the controller board for<br />
IQ111+, 131+, and IQ23x.<br />
Firmware<br />
File compatibility: The IQ23x module suite has either the same<br />
or greater numbers of modules than the IQ111 (+), 131 (+). The<br />
IQ111 (+), 131 (+) strategy can be uploaded into a strategy file<br />
(.IQF) using Power Tool or WupDn. It can then be downloaded<br />
into the IQ23x.<br />
Special cables are required to connect to a PC for uploading from<br />
IQ111 (+), IQ131 (+). The IQ111, 131 requires CABLE/58-0750<br />
(9 Way Female D type to 25 Way Male D type), and the IQ111+,<br />
131+ require the additional adaptor CABLE/78-1172 (25 Way<br />
Female D type to 5 in line Stocko).<br />
Certain modifications are required for it to run correctly, and this<br />
can either be done in the controller using configuration mode<br />
(via PowerTool or WupDn), or the strategy file can be uploaded<br />
(as an .IQ2 file) into SET and the changes made there before<br />
downloading to the IQ23x.<br />
If strategy diagrams are required they can be loaded into SET<br />
from an earlier ACE or SET file, or can be laid out in SET<br />
from the strategy file (uploaded from the IQ23x after an .IQF<br />
download as either an .IQ2 or .SCN file).<br />
The standard IQ1xx to IQ2xx modifications are described in the<br />
IQ configuration Manual Addendum (TD200118).<br />
Bit 506,1: This bit is used to set Emulation for IQ1xx Universal<br />
Inputs. It applies in the case where an internal sensor module is<br />
used in internal digital mode.<br />
INTERNAL DIGITAL NODE<br />
Controller Supervisor Network<br />
IQ111 1k2 or 9k6 1k2, 4k8, 9k6, or 19k2<br />
IQ131 1k2 or 9k6 via integral CNC board<br />
1k2, 4k8, 9k6, or 19k2<br />
IQ111+, IQ131+ 9k6 1k2, 9k6, 19k2<br />
IQ23x 9k6 1k2, 4k8, 9k6, 19k2<br />
INTERNAL<br />
DIGITAL MODE<br />
5 <br />
1,<br />
<br />
digital node corresponding to input n<br />
<br />
In IQ1xx controllers, if a sensor (whose number is greater than<br />
the number of real input channels) is set to internal digital mode,<br />
it will take the value from an internal digital node and write it to<br />
its analogue node and digital input node.<br />
10 IQ23x Series Controllers Data Sheet TA200538 Issue 2, 18-Jan-2012