Cooper B-Line Seismic Restraints - Dixie Construction Products
Cooper B-Line Seismic Restraints - Dixie Construction Products Cooper B-Line Seismic Restraints - Dixie Construction Products
SUPPORT SPACING FOR SINGLE ROD HANGER PIPING Table 2 - Maximum Hanger Spacing for Copper Tubing Seismic Force Level (g’s) 0.45g (ASD) Field Maximum Transverse Maximum Longitudinal Braced Minimum Hanger Transverse Structure Longitudinal Structure Hanger & Braced Water Nominal Spacing Support Connection Support Connection Rod Loads Rod Filled Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m) 1/2" (15) 5 (1.52) 15 (4.57) I 30 (9.14) I 8.3 (0.037) 3/8"-16 0.43 (0.64) 1/2" (15) 6 (1.83) 12 (3.66) I 24 (7.32) I 7.6 (0.034) 3/8"-16 0.43 (0.64) 1/2" (15) 7 (2.13) 14 (4.27) I 28 (8.54) I 8.9 (0.039) 3/8"-16 0.43 (0.64) 1/2" (15) 8 (2.44) 8 (2.44) I 16 (4.88) I 7.1 (0.031) 3/8"-16 0.43 (0.64) 1/2" (15) 10 (3.05) 0 (0.00) I 0 (0.00) I 4.9 (0.022) 3/8"-16 0.43 (0.64) 3/4" (20) 5 (1.52) 15 (4.57) I 30 (9.14) I 16.0 (0.071) 3/8"-16 0.83 (1.23) 3/4" (20) 6 (1.83) 12 (3.66) I 24 (7.32) I 14.7 (0.065) 3/8"-16 0.83 (1.23) 3/4" (20) 7 (2.13) 14 (4.27) I 28 (8.54) I 17.1 (0.076) 3/8"-16 0.83 (1.23) 3/4" (20) 8 (2.44) 8 (2.44) I 16 (4.88) I 13.6 (0.060) 3/8"-16 0.83 (1.23) 3/4" (20) 10 (3.05) 10 (3.05) I 20 (6.10) I 17.0 (0.075) 3/8"-16 0.83 (1.23) 1" (25) 5 (1.52) 20 (6.10) I 40 (12.19) I 28.0 (0.124) 3/8"-16 1.18 (1.75) 1" (25) 6 (1.83) 18 (5.48) I 36 (10.97) I 27.3 (0.121) 3/8"-16 1.18 (1.75) 1" (25) 7 (2.13) 14 (4.27) I 28 (8.54) I 24.4 (0.108) 3/8"-16 1.18 (1.75) 1" (25) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 27.8 (0.123) 3/8"-16 1.18 (1.75) 1" (25) 10 (3.05) 10 (3.05) I 20 (6.10) I 24.2 (0.107) 3/8"-16 1.18 (1.75) 1 1 /4" (32) 5 (1.52) 20 (6.10) I 40 (12.19) I 37.3 (0.166) 3/8"-16 1.57 (2.33) 1 1 /4" (32) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 44.7 (0.199) 3/8"-16 1.57 (2.33) 1 1 /4" (32) 7 (2.13) 21 (6.40) I 42 (12.80) I 42.3 (0.188) 3/8"-16 1.57 (2.33) 1 1 /4" (32) 8 (2.44) 16 (4.88) I 32 ( 9.75) I 37.1 (0.165) 3/8"-16 1.57 (2.33) 1 1 /4" (32) 10 (3.05) 20 (6.10) I 40 (12.19) I 46.3 (0.206) 3/8"-16 1.57 (2.33) 1 1 /2" (40) 5 (1.52) 25 (7.62) I 50 (15.24) I 59.3 (0.264) 3/8"-16 2.10 (3.17) 1 1 /2" (40) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 59.8 (0.266) 3/8"-16 2.10 (3.17) 1 1 /2" (40) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 64.7 (0.288) 3/8"-16 2.10 (3.17) 1 1 /2" (40) 10 (3.05) 20 (6.10) I 40 (12.19) I 61.9 (0.275) 3/8"-16 2.10 (3.17) 1 1 /2" (40) 12 (3.66) 12 (3.66) I 24 (7.32) I 51.7 (0.230) 3/8"-16 2.10 (3.17) 2" (50) 5 (1.52) 30 (9.15) I 60 (18.30) I 110.4 (0.491) 3/8"-16 3.37 (5.01) 2" (50) 6 (1.83) 24 (7.32) I 48 ( 14.64) I 96.0 (0.427) 3/8"-16 3.37 (5.01) 2" (50) 8 (2.44) 24 (7.32) I 48 ( 14.64) I 103.8 (0.462) 3/8"-16 3.37 (5.01) 2" (50) 10 (3.05) 20 (6.10) I 40 (12.19) I 99.4 (0.442) 3/8"-16 3.37 (5.01) 2" (50) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 119.3 (0.530) 3/8"-16 3.37 (5.01) 2 1 /2" (65) 5 (1.52) 30 (9.15) I 55 (16.76) I 150.1 (0.667) 1/2"-13 4.92 (7.32) 2 1 /2" (65) 6 (1.83) 30 (9.15) I 54 (16.46) I 153.5 (0.683) 1/2"-13 4.92 (7.32) 2 1 /2" (65) 9 (2.74) 27 (8.23) I 54 (16.46) I 170.5 (0.758) 1/2"-13 4.92 (7.32) 2 1 /2" (65) 10 (3.05) 30 (9.15) I 50 (15.24) I 167.3 (0.744) 1/2"-13 4.92 (7.32) 2 1 /2" (65) 12 (3.66) 24 (7.32) I 48 ( 14.64) I 174.2 (0.775) 1/2"-13 4.92 (7.32) Continued on following page. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 93 of Raafat S. Aboulhosn Structural Engineer S 3913
SUPPORT SPACING FOR SINGLE ROD HANGER PIPING Table 2 - Maximum Hanger Spacing for Copper Tubing Seismic Force Level (g’s) 0.45g (ASD) Field Maximum Transverse Maximum Longitudinal Braced Minimum Hanger Transverse Structure Longitudinal Structure Hanger & Braced Water Nominal Spacing Support Connection Support Connection Rod Loads Rod Filled Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m) 3" (80) 5 (1.52) 35 (10.67) II 70 (21.33) III 259.3 (1.153) 1/2"-13 6.96 (10.35) 3" (80) 6 (1.83) 30 (9.15) I 60 (18.29) II 235.9 (1.049) 1/2"-13 6.96 (10.35) 3" (80) 8 (2.44) 32 (9.75) II 64 (19.61) II 264.5 (1.176) 1/2"-13 6.96 (10.35) 3" (80) 10 (3.05) 30 (9.15) II 60 (18.29) II 267.9 (1.191) 1/2"-13 6.96 (10.35) 3" (80) 12 (3.66) 24 (7.32) I 48 ( 14.64) II 246.4 (1.096) 1/2"-13 6.96 (10.35) 3 1 /2" (90) 5 (1.52) 35 (10.67) II 70 (21.33) III 336.0 (1.494) 1/2"-13 9.02 (13.42) 3 1 /2" (90) 8 (2.44) 32 (9.75) II 64 (19.61) III 342.7 (1.524) 1/2"-13 9.02 (13.42) 3 1 /2" (90) 10 (3.05) 30 (9.15) II 60 (18.29) III 347.3 (1.545) 1/2"-13 9.02 (13.42) 3 1 /2" (90) 12 (3.66) 24 (7.32) II 48 ( 14.64) II 319.3 (1.420) 1/2"-13 9.02 (13.42) 4" (100) 5 (1.52) 36 (10.98) II 72 (21.94) IV 454.7 (2.022) 1/2"-13 11.57 (17.21) 4" ( 100) 6 (1.83) 32 (9.75) II 64 (19.61) IV 439.6 (1.955) 1/2"-13 11.57 (17.21) 4" ( 100) 8 (2.44) 30 (9.15) II 60 (18.29) III 445.4 (1.981) 1/2"-13 11.57 (17.21) 4" ( 100) 9 (2.74) 36 (10.98) II 72 (21.94) IV 534.5 (2.377) 1/2"-13 11.57 (17.21) 4" ( 100) 11 (3.35) 30 (9.15) II 60 (18.29) III 511.9 (2.277) 1/2"-13 11.57 (17.21) Notes: 1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer hanger spacing may be required when additional valves and fittings increase the load. For electrical conduit support spacing and weight of conduit filled with conductors information, see B-Line Strut Systems Catalog. 2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for brace attachment details. 3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity and the additional seismic forces at the braced location. Select a pipe hanger from pages 63 thru 71 that meets the hanger load requirements. Select a rod attachment detail from pages 39 thru 56 that meets the rod load requirements. Be sure to follow the guidelines on page 57 & 58 to see if a rod stiffener is required, due to the length of the rod. Rod stiffeners, if necessary, are only required at braced locations. Unbraced hangers do not require rod stiffeners. 4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8. 5). Table 1 is for steel pipe. Spacing limitations may exist for other types of pipe. See Note E) on page 9. 6). Seismic forces include 1 /3 of horizontal seismic force applied in vertical direction. 7). Consult appropriate plumbing code for non-braced hanger rod sizes. 8). Charts on pages 91 - 94 are for 0.45g (ASD) applications. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 94 of
- Page 45 and 46: Concrete Attachments To Slab HANGER
- Page 47 and 48: Concrete Attachments To Slab HANGER
- Page 49 and 50: Concrete Attachments To Slab HANGER
- Page 51 and 52: Strut Attachments Typical All Threa
- Page 53 and 54: HANGER ROD ATTACHMENTS & APPROVED C
- Page 55 and 56: HANGER ROD ATTACHMENTS & APPROVED C
- Page 57 and 58: HANGER ROD ATTACHMENTS & APPROVED C
- Page 59 and 60: HANGER ROD SWIVEL ATTACHMENTS A 2 3
- Page 61 and 62: APPROVED COMPONENTS SC228 HANGER RO
- Page 63 and 64: APPROVED COMPONENTS NOTE: B633 can
- Page 65 and 66: APPROVED COMPONENTS Hardware SEISMI
- Page 67 and 68: APPROVED COMPONENTS 'A' (Rod Size)
- Page 69 and 70: APPROVED COMPONENTS 'A' (Rod Size)
- Page 71 and 72: APPROVED COMPONENTS Copper Adjustab
- Page 73 and 74: APPROVED COMPONENTS Vertical Load S
- Page 75 and 76: APPROVED COMPONENTS Seismic Approva
- Page 77 and 78: APPROVED COMPONENTS 'A 'T' 2 'A 'T'
- Page 79 and 80: APPROVED COMPONENTS 2” (50.8mm) 3
- Page 81 and 82: APPROVED COMPONENTS 2 9 /16" (65mm)
- Page 83 and 84: APPENDIX - SEISMIC MAP SEISMIC MAP
- Page 85 and 86: Appendix 1 Support Spacing for Sing
- Page 87 and 88: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 89 and 90: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 91 and 92: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 93 and 94: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 95: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 99 and 100: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 101 and 102: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 103 and 104: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 105 and 106: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 107 and 108: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 109 and 110: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 111 and 112: Appendix 2 Seismic Bracing Charts f
- Page 113 and 114: TRAPEZE BRACING Seismic Bracing Cha
- Page 115 and 116: TRAPEZE BRACING Seismic Bracing Cha
- Page 117 and 118: Seismic Bracing Charts for Trapeze
- Page 119 and 120: TRAPEZE BRACING Seismic Bracing Cha
- Page 121 and 122: TRAPEZE BRACING Seismic Bracing Cha
- Page 123 and 124: Seismic Bracing Charts for Trapeze
- Page 125 and 126: TRAPEZE BRACING Seismic Bracing Cha
- Page 127 and 128: TRAPEZE BRACING Seismic Bracing Cha
- Page 129 and 130: Seismic Bracing Charts for Trapeze
- Page 131 and 132: TRAPEZE BRACING Seismic Bracing Cha
- Page 133 and 134: TRAPEZE BRACING Seismic Bracing Cha
- Page 135 and 136: Seismic Bracing Charts for Trapeze
- Page 137 and 138: TRAPEZE BRACING Seismic Bracing Cha
- Page 139 and 140: TRAPEZE BRACING Seismic Bracing Cha
- Page 141 and 142: Seismic Bracing Charts for Trapeze
- Page 143 and 144: TRAPEZE BRACING Seismic Bracing Cha
- Page 145 and 146: TRAPEZE BRACING Seismic Bracing Cha
SUPPORT SPACING FOR SINGLE ROD HANGER PIPING<br />
Table 2 - Maximum Hanger Spacing for Copper Tubing<br />
<strong>Seismic</strong> Force Level (g’s) 0.45g (ASD)<br />
Field Maximum Transverse Maximum Longitudinal Braced Minimum<br />
Hanger Transverse Structure Longitudinal Structure Hanger & Braced Water<br />
Nominal Spacing Support Connection Support Connection Rod Loads Rod Filled<br />
Tubing Size See Note 1 Spacing Type Spacing Type See Note 3 Size Weight<br />
in. (mm) ft. (m) ft. (m) See Note 2 ft. (m) See Note 2 lbs. (kN) lbs./ft. (kg/m)<br />
3" (80) 5 (1.52) 35 (10.67) II 70 (21.33) III 259.3 (1.153) 1/2"-13 6.96 (10.35)<br />
3" (80) 6 (1.83) 30 (9.15) I 60 (18.29) II 235.9 (1.049) 1/2"-13 6.96 (10.35)<br />
3" (80) 8 (2.44) 32 (9.75) II 64 (19.61) II 264.5 (1.176) 1/2"-13 6.96 (10.35)<br />
3" (80) 10 (3.05) 30 (9.15) II 60 (18.29) II 267.9 (1.191) 1/2"-13 6.96 (10.35)<br />
3" (80) 12 (3.66) 24 (7.32) I 48 ( 14.64) II 246.4 (1.096) 1/2"-13 6.96 (10.35)<br />
3 1 /2" (90) 5 (1.52) 35 (10.67) II 70 (21.33) III 336.0 (1.494) 1/2"-13 9.02 (13.42)<br />
3 1 /2" (90) 8 (2.44) 32 (9.75) II 64 (19.61) III 342.7 (1.524) 1/2"-13 9.02 (13.42)<br />
3 1 /2" (90) 10 (3.05) 30 (9.15) II 60 (18.29) III 347.3 (1.545) 1/2"-13 9.02 (13.42)<br />
3 1 /2" (90) 12 (3.66) 24 (7.32) II 48 ( 14.64) II 319.3 (1.420) 1/2"-13 9.02 (13.42)<br />
4" (100) 5 (1.52) 36 (10.98) II 72 (21.94) IV 454.7 (2.022) 1/2"-13 11.57 (17.21)<br />
4" ( 100) 6 (1.83) 32 (9.75) II 64 (19.61) IV 439.6 (1.955) 1/2"-13 11.57 (17.21)<br />
4" ( 100) 8 (2.44) 30 (9.15) II 60 (18.29) III 445.4 (1.981) 1/2"-13 11.57 (17.21)<br />
4" ( 100) 9 (2.74) 36 (10.98) II 72 (21.94) IV 534.5 (2.377) 1/2"-13 11.57 (17.21)<br />
4" ( 100) 11 (3.35) 30 (9.15) II 60 (18.29) III 511.9 (2.277) 1/2"-13 11.57 (17.21)<br />
Notes:<br />
1). Many codes require pipe hangers to be spaced every 10’-0” (3.05m) regardless of size. Check<br />
your local codes. Spacing and capacities are based on water filled standard weight pipe. Closer<br />
hanger spacing may be required when additional valves and fittings increase the load. For<br />
electrical conduit support spacing and weight of conduit filled with conductors information,<br />
see B-<strong>Line</strong> Strut Systems Catalog.<br />
2). The “structure connection type” is the brace anchorage requirement. See pages 23 thru 38 for<br />
brace attachment details.<br />
3). The hanger and rod loads indicates the maximum tension in the rod (and hanger) due to gravity<br />
and the additional seismic forces at the braced location. Select a pipe hanger from pages<br />
63 thru 71 that meets the hanger load requirements. Select a rod attachment detail from pages<br />
39 thru 56 that meets the rod load requirements. Be sure to follow the guidelines on page 57 &<br />
58 to see if a rod stiffener is required, due to the length of the rod. Rod stiffeners, if necessary,<br />
are only required at braced locations. Unbraced hangers do not require rod stiffeners.<br />
4). Braces must be attached within 4 inches (101mm) of hanger, see Figure 5, 6 and 8.<br />
5). Table 1 is for steel pipe. Spacing limitations may exist for other types of pipe. See<br />
Note E) on page 9.<br />
6). <strong>Seismic</strong> forces include 1 /3 of horizontal seismic force applied in vertical direction.<br />
7). Consult appropriate plumbing code for non-braced hanger rod sizes.<br />
8). Charts on pages 91 - 94 are for 0.45g (ASD) applications.<br />