APPROVED COMPONENTS<br />

Bolts and Nuts<br />

Included<br />

<strong>Seismic</strong> Approval:<br />

Transverse and Longitudinal<br />

Bracing of Steel Pipe &<br />

Copper Tubing.<br />

Bolt Size<br />

'L'<br />

Approvals: Complies with Federal Specification<br />

WW-H-171E Type 4 and Manufacturers'<br />

Standardization Society SP-69 UType 8.<br />

C ®<br />

Underwriter's Laboratories Listed<br />

L US<br />

for 3 /4" (20mm)<br />

thru 8" (200mm) on Standard Riser Clamp only.<br />

LISTED<br />

B3373 - Standard Riser Clamp<br />

Nominal<br />

Design Load<br />

Part No. Pipe Size 'L' Bolt Size lbs. kN<br />

C<br />

U<br />

® L<br />

US<br />

B3373-1 1" (25) 9 9 /16" (242.9) 3/8"-16 x 1 1 /4" 255 (1.13)<br />

B3373-1 1 /4 1 1 /4" (32) 10" (254.0) 3/8"-16 x 1 1 /4" 255 (1.13)<br />

B3373-1 1 /2 1 1 /2" (40) 10 1 /4" (260.3) 3/8"-16 x 1 1 /2" 255 (1.13)<br />

B3373-2 2" (50) 10 3 /4" (273.0) 3/8"-16 x 1 1 /2" 255 (1.13)<br />

B3373-2 1 /2 2 1 /2" (65) 11 1 /4" (285.7) 3/8"-16 x 1 1 /2" 390 (1.73)<br />

B3373-3 3" (80) 11 15 /16" (303.2) 3/8"-16 x 1 1 /2" 530 (2.35)<br />

B3373-3 1 /2 3 1 /2" (90) 12 3 /8" (314.3) 1/2"-13 x 1 3 /4" 670 (2.98)<br />

B3373-4 4" (100) 12 7 /8" (327.0) 1/2"-13 x 1 3 /4" 810 (3.60)<br />

B3373-5 5" (125) 14" (355.6) 1/2"-13 x 1 3 /4" 1160 (5.16)<br />

B3373-6 6" (150) 15 3 /16" (385.8) 1/2"-13 x 2" 1570 (6.98)<br />

B3373-8 8" (200) 17 3 /4" (450.8) 5/8"-11 x 2 1 /2" 2500 (11.12)<br />

B3373-10 10" (250) 19 7 /16" (493.7) 5/8"-11 x 2 1 /2" 2500 (11.12)<br />

B3373-12 12" (300) 21 11 /16" (550.9) 5/8"-11 x 3" 2700 (12.01)<br />

See note D) on page 9 for required tightening torques.<br />

B3373CT - Riser Clamp for Copper Tubing<br />

Nominal<br />

Design Load<br />

Part No. Tubing Size 'L' Bolt Size lbs. kN<br />

B3373CT- 1 /2 1/2" (15) 8 3 /4" (222.2) 5/16"-18 x 1" 75 (.33)<br />

B3373CT- 3 /4 3/4" (20) 9 1 /16" (234.9) 5/16"-18 x 1" 75 (.33)<br />

B3373CT-1 1" (25) 9 5 /16" (236.5) 3/8"-16 x 1" 120 (.53)<br />

B3373CT-1 1 /4 1 1 /4" (32) 9 5 /8" (244.5) 3/8"-16 x 1" 150 (.67)<br />

B3373CT-1 1 /2 1 1 /2" (40) 9 3 /4" (247.6) 3/8"-16 x 1 1 /4" 150 (.67)<br />

B3373CT-2 2" (50) 10 7 /16" (265.1) 3/8"-16 x 1 1 /4" 150 (.67)<br />

B3373CT-2 1 /2 2 1 /2" (65) 10 15 /16" (277.8) 3/8"-16 x 1 1 /4" 300 (1.33)<br />

B3373CT-3 3" (80) 11 7 /16" (290.5) 3/8"-16 x 1 1 /4" 300 (1.33)<br />

B3373CT-3 1 /2 3 1 /2" (90) 11 15 /16" (303.2) 3/8"-16 x 1 1 /4" 300 (1.33)<br />

B3373CT-4 4" (100) 12 1 /2" (317.5) 1/2"-13 x 1 3 /4" 300 (1.33)<br />

See note D) on page 9 for required tightening torques.<br />

Finish: For B3373CT is<br />

Dura-Copper Epoxy Paint.<br />

This non-metallic coating<br />

eliminates dissimilar metal<br />

contact between the hanger<br />

and the copper tubing.<br />

COOPER B-<strong>Line</strong><br />

509 West Monroe Street<br />

Highland, Illinois 62249<br />

Phone: 800-851-7415<br />

Fax: 618-654-1917<br />

Date:<br />

Page No.<br />

Sheet Number:<br />

6 - 2 - 06<br />

69<br />

of<br />

Raafat S. Aboulhosn<br />

Structural Engineer S 3913

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!