APPROVED COMPONENTS<br />

'A'<br />

(Rod Size)<br />

Hanger Rod<br />

Not Included<br />

C<br />

C<br />

U L<br />

LISTED<br />

U<br />

® L<br />

US<br />

US<br />

Pipe<br />

Pipe Size Clevis Hanger Sleeve<br />

in. (mm) Part No. Part No.*<br />

1 /2" (15) B3100- 1 /2 B3100PS- 1 /2<br />

3/4" (20) B3100- 3 /4 B3100PS- 3 /4<br />

1" (25) B3100-1 B3100PS-1<br />

1 1 /4" (32) B3100-1 1 /4 B3100PS-1 1 /4<br />

1 1 /2" (40) B3100-1 1 /2 B3100PS-1 1 /2<br />

2" (50) B3100-2 B3100PS-2<br />

2 1 /2" (65) B3100-2 1 /2 B3100PS-2 1 /2<br />

3" (80) B3100-3 B3100PS-3<br />

3 1 /2" (90) B3100-3 1 /2 B3100PS-3 1 /2<br />

4" (100) B3100-4 B3100PS-4<br />

5" (125) B3100-5 B3100PS-5<br />

6" (150) B3100-6 B3100PS-6<br />

8" (200) B3100-8 B3100PS-8<br />

10" (250) B3100-10 B3100PS-10<br />

12" (300) B3100-12 B3100PS-12<br />

®<br />

COOPER B-<strong>Line</strong><br />

B3100<br />

Standard Clevis Hanger<br />

Nominal Rod Size Design Load<br />

Part No. Pipe Size 'A'<br />

in. (mm) lbs. (kN)<br />

*Not included when ordering standard<br />

B3100 Series Clevis Hanger.<br />

SEISMIC APPROVAL:<br />

Transverse Brace Attachment<br />

B3100- 1 /2 1/2" (15) 3/8"-16 610 (2.71)<br />

B3100- 3 /4 3 /4" (20) 3 /8"-16 610 (2.71)<br />

B3100-1 1" (25) 3/8"-16 610 (2.71)<br />

B3100-1 1 /4 1 1 /4" (32) 3/8"-16 610 (2.71)<br />

B3100-1 1 /2 1 1 /2" (40) 3 /8"-16 610 (2.71)<br />

B3100-2 2" (50) 3/8"-16 610 (2.71)<br />

B3100-2 1 /2 2 1 /2" (65) 1 /2"-13 1130 (5.02)<br />

B3100-3 3" (80) 1/2"-13 1130 (5.02)<br />

B3100-3 1 /2 3 1 /2" (90) 1/2"-13 1130 (5.02)<br />

B3100-4 4" (100) 5/8"-11 1430 (6.36)<br />

B3100-5 5" (125) 5/8"-11 1430 (6.36)<br />

Underwriter's Laboratories Listed for 3 /4" (20) thru<br />

12" (300). Complies with Federal Specification<br />

WW-H-171E Type 1 and Manufacturers'<br />

Standardization Society SP-69 Type 1.<br />

Note: When attaching seismic bracing to clevis<br />

hanger, install a B3100 Pipe Sleeve over the cross<br />

bolt (See Figure 1 on page 13).<br />

Order B3100PS (Pipe Sleeve) separately.<br />

B3100PS<br />

Pipe Sleeve<br />

B3100-6 6" (150) 3/4"-10 1940 (8.63)<br />

B3100-8 8" (200) 3/4"-10 2000 (8.89)<br />

B3100-10 10" (250) 7/8"-9 3600 (16.01)<br />

B3100-12 12" (300) 7/8"-9 3770 (16.77)<br />

509 West Monroe Street<br />

Highland, Illinois 62249<br />

Phone: 800-851-7415<br />

Fax: 618-654-1917<br />

Date:<br />

Page No.<br />

Sheet Number:<br />

6 - 2 - 06<br />

63<br />

of<br />

Raafat S. Aboulhosn<br />

Structural Engineer S 3913