THREADED ROD (ATR) Rod Size TABLE 5 Allowable Loads lbs. (kN) 3/8"-16 610 (2.71) 1/2"-13 1130 (5.02) 5 /8"-11 1810 (8.05) 3 /4"-10 2710 (12.05) 7/8"-9 3770 (16.77) * Anchor capacity may be lower than all threaded rod. ALL THREADED ROD - ATR THREADED ROD - MAXIMUM LENGTH WITHOUT STIFFENER ATR All Threaded Rod Table 5 B22 Channel Longitudinal or Transverse Brace (9’-4” (2.8 m) Maximum Length) ATR Size TABLE 6 Max. Rod Length Without Rod Stiffener in. (mm) 3/8"-16 19" (482.6) 1/2"-13 25" (635.0) B-Line Channel Size as Required (See Page 22) 5 /8"-11 31" (787.4) 3/4"-10 37" (939.8) 7 /8"-9 43" (1092.2) Note: If rod stiffener is required see Table 7 - page 58 B335-2- 1 /2 Adjustable Hinges Longitudinal & Transverse Braces (See Page 59) COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 57 of Raafat S. Aboulhosn Structural Engineer S 3913
APPROVED COMPONENTS SC228 HANGER ROD STIFFENER ASSEMBLY For 3 /8" thru 5 /8" ATR (Order B22 Channel Separately) SC-UB HANGER ROD STIFFENER ASSEMBLY For 3 /4" & 7 /8" ATR (Order B22 Channel Separately) SC228 Hanger Rod Stiffener Assembly B22 Channel Rod Stiffener ATR All Threaded Rod (See Page 57) B3188-1 1 /4” WO U-Bolt 2-Hole Plate 1 /4” x 1 5 /8” x 3 1 /2” (6mm x 41mm x 89mm) ATR All Threaded Rod (See Page 57) B22 Channel 3 /8” Hex Nuts Note: SC-UB assembly includes U-Bolt, 2-Hole Plate & 3 / 8 "-16 Hex Nuts. APPROVED COMPONENTS Maximum distance from top of hanger rod to first bolt of the channel rod stiffener is 6” (152.4mm). ‘X’ Maximum distance from top of channel where the hanger rod is attached to the first bolt of the channel rod stiffener is 6” (152.4mm). B-Line channel size as required. (See Page 22) ATR All Threaded Rod (See Page 57) B22 Channel Longitudinal or Transverse Brace (9’-4” (2.8 m) Maximum Length) B22 Channel Rod Stiffener with SC228 or SC-UB Assemblies B335-2- 1 /2 Adjustable Hinges Longitudinal & Transverse Braces (See Page 59) ATR Size TABLE 7 ROD STIFFENER CHART X Max. Spacing Between SC-228 or SC-UB in. (mm) 3/8"-16 13" (330.2) 1/2"-13 18" (457.2) 5/8"-11 23" (584.2) 3/4"-10 28" (711.2) 7 /8"-9 33" (838.2) Note: Minimum of (2) - SC228 or SC-UB are required per rod. Rod Stiffeners required only on hanger rods that have seismic bracing attached to the hanger or trapeze. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 58 of
- Page 9 and 10: GENERAL INFORMATION c) Check the re
- Page 11 and 12: GENERAL INFORMATION f) When a flexi
- Page 13 and 14: GENERAL NOTES FOR SEISMIC BRACING G
- Page 15 and 16: SINGLE PIPE/CONDUIT BRACING Single
- Page 17 and 18: SINGLE PIPE BRACING PIPE CLAMP TRAN
- Page 19 and 20: CLEVIS HANGER TRANSVERSE BRACING (F
- Page 21 and 22: TRAPEZE BRACING TRAPEZE TRANSVERSE
- Page 23 and 24: TRAPEZE BRACING TRAPEZE TRANSVERSE
- Page 25 and 26: TRAPEZE BRACING Typical Trapeze ATR
- Page 27 and 28: STRUCTURAL ATTACHMENTS ‘T’ Conc
- Page 29 and 30: Concrete Attachments Detail 4 Metal
- Page 31 and 32: Concrete Attachments STRUCTURAL ATT
- Page 33 and 34: STRUCTURAL ATTACHMENTS Minimum dist
- Page 35 and 36: STRUCTURAL ATTACHMENTS Concrete Att
- Page 37 and 38: STRUCTURAL ATTACHMENTS Wood Beam At
- Page 39 and 40: STRUCTURAL ATTACHMENTS Wood Beam At
- Page 41 and 42: Structural Steel Detail 16 Case 1 C
- Page 43 and 44: Concrete Attachments To Slab HANGER
- Page 45 and 46: Concrete Attachments To Slab HANGER
- Page 47 and 48: Concrete Attachments To Slab HANGER
- Page 49 and 50: Concrete Attachments To Slab HANGER
- Page 51 and 52: Strut Attachments Typical All Threa
- Page 53 and 54: HANGER ROD ATTACHMENTS & APPROVED C
- Page 55 and 56: HANGER ROD ATTACHMENTS & APPROVED C
- Page 57 and 58: HANGER ROD ATTACHMENTS & APPROVED C
- Page 59: HANGER ROD SWIVEL ATTACHMENTS A 2 3
- Page 63 and 64: APPROVED COMPONENTS NOTE: B633 can
- Page 65 and 66: APPROVED COMPONENTS Hardware SEISMI
- Page 67 and 68: APPROVED COMPONENTS 'A' (Rod Size)
- Page 69 and 70: APPROVED COMPONENTS 'A' (Rod Size)
- Page 71 and 72: APPROVED COMPONENTS Copper Adjustab
- Page 73 and 74: APPROVED COMPONENTS Vertical Load S
- Page 75 and 76: APPROVED COMPONENTS Seismic Approva
- Page 77 and 78: APPROVED COMPONENTS 'A 'T' 2 'A 'T'
- Page 79 and 80: APPROVED COMPONENTS 2” (50.8mm) 3
- Page 81 and 82: APPROVED COMPONENTS 2 9 /16" (65mm)
- Page 83 and 84: APPENDIX - SEISMIC MAP SEISMIC MAP
- Page 85 and 86: Appendix 1 Support Spacing for Sing
- Page 87 and 88: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 89 and 90: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 91 and 92: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 93 and 94: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 95 and 96: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 97 and 98: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 99 and 100: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 101 and 102: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 103 and 104: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 105 and 106: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 107 and 108: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 109 and 110: SUPPORT SPACING FOR SINGLE ROD HANG
THREADED ROD (ATR)<br />
Rod<br />
Size<br />
TABLE 5<br />
Allowable<br />
Loads<br />
lbs.<br />
(kN)<br />
3/8"-16 610 (2.71)<br />
1/2"-13 1130 (5.02)<br />
5 /8"-11 1810 (8.05)<br />
3 /4"-10 2710 (12.05)<br />
7/8"-9 3770 (16.77)<br />
* Anchor capacity may be lower<br />
than all threaded rod.<br />
ALL THREADED ROD - ATR<br />
THREADED ROD - MAXIMUM LENGTH WITHOUT STIFFENER<br />
ATR<br />
All Threaded Rod<br />
Table 5<br />
B22 Channel<br />
Longitudinal or Transverse Brace<br />
(9’-4” (2.8 m) Maximum Length)<br />
ATR<br />
Size<br />
TABLE 6<br />
Max. Rod Length<br />
Without Rod<br />
Stiffener<br />
in. (mm)<br />
3/8"-16 19" (482.6)<br />
1/2"-13 25" (635.0)<br />
B-<strong>Line</strong> Channel<br />
Size as Required<br />
(See Page 22)<br />
5 /8"-11 31" (787.4)<br />
3/4"-10 37" (939.8)<br />
7 /8"-9 43" (1092.2)<br />
Note: If rod stiffener is required<br />
see Table 7 - page 58<br />
B335-2- 1 /2 Adjustable Hinges<br />
Longitudinal & Transverse Braces<br />
(See Page 59)<br />
COOPER B-<strong>Line</strong><br />
509 West Monroe Street<br />
Highland, Illinois 62249<br />
Phone: 800-851-7415<br />
Fax: 618-654-1917<br />
Date:<br />
Page No.<br />
Sheet Number:<br />
6 - 2 - 06<br />
57<br />
of<br />
Raafat S. Aboulhosn<br />
Structural Engineer S 3913