HANGER ROD ATTACHMENTS & APPROVED COMPONENTS SEISMIC APPROVAL: To be used as a vertical ATR support. Not usable as a structural attachment for seismic brace. 'B' Setscrew Included Part Rod Setscrew 'C' 'T' Design Load No. Size 'B' in. (mm) in. (mm) lbs. (kN) B303 1/4"-20 3/8"-16 2 5 /16" (59) 11 Ga. (3) 400 (1.78) B304 5 /16"-18 3 /8"-16 2 5 /16" (59) 11 Ga. (3) 600 (2.67) B305 3/8"-16 3/8"-16 2 5 /16" (59) 11 Ga. (3) 600 (2.67) B306 3/8"-16 1/2"-13 2 7 /16" (62) 7 Ga. (4) 1100 (4.89) B307 1 /2"-13 1 /2"-13 2 7 /16" (62) 7 Ga. (4) 1100 (4.89) B308 1/2"-13 1/2"-13 2 9 /16" (65) 1 /4" (6) 1500 (6.67) B309 5/8"-11 1/2"-13 2 9 /16" (65) 1 /4" (6) 1500 (6.67) Recommended Setscrew Torque: 3 /8"-16 150 in.-lbs. (16.9 N•m) 1 /2"-13 350 in.-lbs. (39.5 N•m) Retaining Strap is required, order B312 separately. 'C' 'T' 7/8" (22mm) 'A' 2 1 /2" (63mm) B303 Thru B309 BEAM CLAMP 1 1 /8" (28mm) SEISMIC APPROVAL: To be used as a vertical ATR support. Not usable as a structural attachment for seismic brace. Part Rod Setscrew 'C' 'T' Design Load No. Size 'B' in. (mm) in. (mm) lbs. (kN) B321-1 3/8"-16 1/2"-13 3 9 /16" (92) 1/4" (6) 1300 (5.78) B321-2 1/2"-13 1/2"-13 3 9 /16" (92) 1/4" (6) 1400 (6.23) B321-3 5/8"-11 1/2"-13 3 9 /16" (92) 1/4" (6) 1600 (7.12) B321-4 5/8"-11 5/8"-11 3 23 /32" (94) 5/16" (8) 1800 (8.00) B321-5 3/4"-13 5/8"-11 3 23 /32" (94) 5/16" (8) 2000 (8.89) Recommended Setscrew Torque: 3 /8"-16 150 in.-lbs. (16.9 N•m) 1 /2"-13 350 in.-lbs. (39.5 N•m) SEISMIC APPROVAL: To be used as a vertical ATR support. Not usable as a structural attachment for seismic brace. Minimum Flange Thickness: B321-1 thru B321-3 3 /8" (9mm) B321-4 and B321-5 5 /8" (16mm) Retaining Strap is required, order B312 separately. 'C' 1 11 /16" (43mm) 3 1 /4" (82mm) 'A' 'T' 'A' B321 SERIES BEAM CLAMP 'B' Setscrew Included 1 5 /8" (41mm) For Flange Part No. Width 'A' in. (mm) in. (mm) B312S-6 6" (152) 9 5 /8" (244) B312S-9 9" (228) 12 5 /8" (320) B312S-12 12" (305) 15 5 /8" (397) B312S-15 15" (381) 18 5 /8" (473) For maximum beam thickness of 3 /4" (19mm). For thicker beams step up one flange width size. Material: 12 Gauge (2.7mm) 1 1 /4" (32mm) 1/4" (6mm) 1 3 /4" (44mm) B312S SERIES ANCHOR STRAP FOR USE WITH B303 thru B309 and B321 SERIES 1/2" (13mm) COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 53 of Raafat S. Aboulhosn Structural Engineer S 3913
HANGER ROD ATTACHMENTS & APPROVED COMPONENTS SEISMIC APPROVAL: To be used as a vertical ATR support. Not usable as a structural attachment for seismic brace. Rod Size Throat Design Part No. 'A' Opening Load in. (mm) lbs. (kN) B3033- 3 /8 3/8"-16 1 1 /4" (32) 500 (2.22) B3033- 1 /2 1 /2"-13 1 1 /4" (32) 810 (3.60) B3033- 5 /8 5/8"-11 1 5 /16" (33) 1000 (4.45) B3033- 3 /4 3/4"-10 1 5 /16" (33) 1400 (6.23) Setscrew Torque: 1 /4” = 4 ft•lbs 3 /8” = 5 ft•lbs 1 /2” = 11 ft•lbs Retaining Strap is required, order B3367 separately. C C U ® L LISTED U ® L US US B3033 REVERSABLE BEAM CLAMP SEISMIC APPROVAL: To be used as a vertical ATR support. Not usable as a structural attachment for seismic brace. Rod Size Throat Design Part No. 'A' Opening Load in. (mm) lbs. (kN) B3034- 3 /8 3/8"-16 3/4" (19) 560 (2.49) B3034- 1 /2 1 /2"-13 3 /4" (19) 810 (360) Setscrew Torque: 1 /4” = 4 ft•lbs 3 /8” = 5 ft•lbs Retaining Strap is required, order U C ® B3367 separately. L C LISTED U ® L US US B3034 REVERSABLE BEAM CLAMP SEISMIC APPROVAL: To be used as a vertical ATR support. Not usable as a structural attachment for seismic brace. ’B’ ‘A’ ‘B’ Part No. Width Diameter in. (mm) in. (mm) B3367- 3 /8 1 1 /4" (32) 7/16" (11) B3367- 1 /2 1 1 /4" (32) 9/16" (14) B3367- 5 /8 1 1 /4" (32) 11/16" (17) B3367- 3 /4 1 1 /4" (32) 13 /16" (20) ’L’ ’A’ Material Thickness: 11 Ga. (3.0mm) Specify ‘L’ Length (add 2” (51mm) to flange width) B3367 SERIES ANCHOR STRAP FOR USE WITH B3033 and B3034 SERIES COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 54 of
- Page 5 and 6: GENERAL INFORMATION I p = Importanc
- Page 7 and 8: GENERAL INFORMATION Cable tray syst
- Page 9 and 10: GENERAL INFORMATION c) Check the re
- Page 11 and 12: GENERAL INFORMATION f) When a flexi
- Page 13 and 14: GENERAL NOTES FOR SEISMIC BRACING G
- Page 15 and 16: SINGLE PIPE/CONDUIT BRACING Single
- Page 17 and 18: SINGLE PIPE BRACING PIPE CLAMP TRAN
- Page 19 and 20: CLEVIS HANGER TRANSVERSE BRACING (F
- Page 21 and 22: TRAPEZE BRACING TRAPEZE TRANSVERSE
- Page 23 and 24: TRAPEZE BRACING TRAPEZE TRANSVERSE
- Page 25 and 26: TRAPEZE BRACING Typical Trapeze ATR
- Page 27 and 28: STRUCTURAL ATTACHMENTS ‘T’ Conc
- Page 29 and 30: Concrete Attachments Detail 4 Metal
- Page 31 and 32: Concrete Attachments STRUCTURAL ATT
- Page 33 and 34: STRUCTURAL ATTACHMENTS Minimum dist
- Page 35 and 36: STRUCTURAL ATTACHMENTS Concrete Att
- Page 37 and 38: STRUCTURAL ATTACHMENTS Wood Beam At
- Page 39 and 40: STRUCTURAL ATTACHMENTS Wood Beam At
- Page 41 and 42: Structural Steel Detail 16 Case 1 C
- Page 43 and 44: Concrete Attachments To Slab HANGER
- Page 45 and 46: Concrete Attachments To Slab HANGER
- Page 47 and 48: Concrete Attachments To Slab HANGER
- Page 49 and 50: Concrete Attachments To Slab HANGER
- Page 51 and 52: Strut Attachments Typical All Threa
- Page 53 and 54: HANGER ROD ATTACHMENTS & APPROVED C
- Page 55: HANGER ROD ATTACHMENTS & APPROVED C
- Page 59 and 60: HANGER ROD SWIVEL ATTACHMENTS A 2 3
- Page 61 and 62: APPROVED COMPONENTS SC228 HANGER RO
- Page 63 and 64: APPROVED COMPONENTS NOTE: B633 can
- Page 65 and 66: APPROVED COMPONENTS Hardware SEISMI
- Page 67 and 68: APPROVED COMPONENTS 'A' (Rod Size)
- Page 69 and 70: APPROVED COMPONENTS 'A' (Rod Size)
- Page 71 and 72: APPROVED COMPONENTS Copper Adjustab
- Page 73 and 74: APPROVED COMPONENTS Vertical Load S
- Page 75 and 76: APPROVED COMPONENTS Seismic Approva
- Page 77 and 78: APPROVED COMPONENTS 'A 'T' 2 'A 'T'
- Page 79 and 80: APPROVED COMPONENTS 2” (50.8mm) 3
- Page 81 and 82: APPROVED COMPONENTS 2 9 /16" (65mm)
- Page 83 and 84: APPENDIX - SEISMIC MAP SEISMIC MAP
- Page 85 and 86: Appendix 1 Support Spacing for Sing
- Page 87 and 88: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 89 and 90: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 91 and 92: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 93 and 94: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 95 and 96: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 97 and 98: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 99 and 100: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 101 and 102: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 103 and 104: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 105 and 106: SUPPORT SPACING FOR SINGLE ROD HANG
HANGER ROD ATTACHMENTS & APPROVED COMPONENTS<br />
SEISMIC APPROVAL: To be used as a vertical ATR support.<br />
Not usable as a structural attachment for seismic brace.<br />
'B' Setscrew<br />
Included<br />
Part Rod Setscrew 'C' 'T' Design Load<br />
No. Size 'B' in. (mm) in. (mm) lbs. (kN)<br />
B303 1/4"-20 3/8"-16 2 5 /16" (59) 11 Ga. (3) 400 (1.78)<br />
B304 5 /16"-18 3 /8"-16 2 5 /16" (59) 11 Ga. (3) 600 (2.67)<br />
B305 3/8"-16 3/8"-16 2 5 /16" (59) 11 Ga. (3) 600 (2.67)<br />
B306 3/8"-16 1/2"-13 2 7 /16" (62) 7 Ga. (4) 1100 (4.89)<br />
B307 1 /2"-13 1 /2"-13 2 7 /16" (62) 7 Ga. (4) 1100 (4.89)<br />
B308 1/2"-13 1/2"-13 2 9 /16" (65) 1 /4" (6) 1500 (6.67)<br />
B309 5/8"-11 1/2"-13 2 9 /16" (65) 1 /4" (6) 1500 (6.67)<br />
Recommended Setscrew Torque:<br />
3 /8"-16 150 in.-lbs. (16.9 N•m)<br />
1 /2"-13 350 in.-lbs. (39.5 N•m)<br />
Retaining<br />
Strap is<br />
required,<br />
order B312<br />
separately.<br />
'C'<br />
'T'<br />
7/8"<br />
(22mm)<br />
'A'<br />
2 1 /2"<br />
(63mm)<br />
B303 Thru B309<br />
BEAM CLAMP<br />
1 1 /8"<br />
(28mm)<br />
SEISMIC APPROVAL: To be used as a<br />
vertical ATR support. Not usable as a<br />
structural attachment for seismic brace.<br />
Part Rod Setscrew 'C' 'T' Design Load<br />
No. Size 'B' in. (mm) in. (mm) lbs. (kN)<br />
B321-1 3/8"-16 1/2"-13 3 9 /16" (92) 1/4" (6) 1300 (5.78)<br />
B321-2 1/2"-13 1/2"-13 3 9 /16" (92) 1/4" (6) 1400 (6.23)<br />
B321-3 5/8"-11 1/2"-13 3 9 /16" (92) 1/4" (6) 1600 (7.12)<br />
B321-4 5/8"-11 5/8"-11 3 23 /32" (94) 5/16" (8) 1800 (8.00)<br />
B321-5 3/4"-13 5/8"-11 3 23 /32" (94) 5/16" (8) 2000 (8.89)<br />
Recommended Setscrew Torque:<br />
3 /8"-16 150 in.-lbs. (16.9 N•m)<br />
1 /2"-13 350 in.-lbs. (39.5 N•m)<br />
SEISMIC APPROVAL: To be used as a<br />
vertical ATR support. Not usable as a<br />
structural attachment for seismic brace.<br />
Minimum Flange Thickness:<br />
B321-1 thru B321-3 3 /8" (9mm)<br />
B321-4 and B321-5 5 /8" (16mm)<br />
Retaining<br />
Strap is<br />
required,<br />
order B312<br />
separately.<br />
'C'<br />
1 11 /16"<br />
(43mm)<br />
3 1 /4"<br />
(82mm)<br />
'A'<br />
'T'<br />
'A'<br />
B321 SERIES<br />
BEAM CLAMP<br />
'B' Setscrew<br />
Included<br />
1 5 /8"<br />
(41mm)<br />
For Flange<br />
Part No. Width 'A'<br />
in. (mm) in. (mm)<br />
B312S-6 6" (152) 9 5 /8" (244)<br />
B312S-9 9" (228) 12 5 /8" (320)<br />
B312S-12 12" (305) 15 5 /8" (397)<br />
B312S-15 15" (381) 18 5 /8" (473)<br />
For maximum beam thickness of 3 /4" (19mm).<br />
For thicker beams step up one flange width size.<br />
Material: 12 Gauge (2.7mm)<br />
1 1 /4"<br />
(32mm)<br />
1/4"<br />
(6mm)<br />
1 3 /4"<br />
(44mm)<br />
B312S SERIES<br />
ANCHOR STRAP FOR USE WITH<br />
B303 thru B309 and B321 SERIES<br />
1/2"<br />
(13mm)<br />
COOPER B-<strong>Line</strong><br />
509 West Monroe Street<br />
Highland, Illinois 62249<br />
Phone: 800-851-7415<br />
Fax: 618-654-1917<br />
Date:<br />
Page No.<br />
Sheet Number:<br />
6 - 2 - 06<br />
53<br />
of<br />
Raafat S. Aboulhosn<br />
Structural Engineer S 3913