Cooper B-Line Seismic Restraints - Dixie Construction Products
Cooper B-Line Seismic Restraints - Dixie Construction Products
Cooper B-Line Seismic Restraints - Dixie Construction Products
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
STRUCTURAL ATTACHMENTS<br />
Wood Beam Attachments<br />
Detail 15<br />
Used where brace runs parallel to wood beam or where double bolts are required.<br />
Minimum beam thickness of 3 1 /2” (88.9mm) required.<br />
Lag bolts of diameter ‘D’ with<br />
3” (76.2mm) embedment (min.)<br />
B3060SW Series<br />
(See Page 73)<br />
1 /2" x 1 1 /4" (32mm)<br />
Hex Head Cap Screw<br />
with Lock Washer<br />
& Hex Nut<br />
(See Page 62)<br />
Angle must be attached to<br />
wood beam above the neutral<br />
axis at a minimum of (4 x ‘D’)<br />
from the top and bottom of<br />
the beam.<br />
Adjustable Hinge<br />
(See Page 59)<br />
1<br />
1 /2" x 1 1 /4" Hex Head<br />
Cap Screws &<br />
N225WO Nuts<br />
(See Pages 61 & 62)<br />
1 min.<br />
B-<strong>Line</strong> Channel<br />
Longitudinal or Transverse Brace<br />
Load<br />
Structure Allowable Lag Bolt<br />
Connection Load * Dia ‘D’<br />
Type<br />
lbs. (kN) in. (mm)<br />
I 175 (0.78) 1/2" (12)<br />
* Based on douglas fir with .51 specific gravity or greater.<br />
COOPER B-<strong>Line</strong><br />
509 West Monroe Street<br />
Highland, Illinois 62249<br />
Phone: 800-851-7415<br />
Fax: 618-654-1917<br />
Date:<br />
Page No.<br />
Sheet Number:<br />
6 - 2 - 06<br />
37<br />
of<br />
Raafat S. Aboulhosn<br />
Structural Engineer S 3913