STRUCTURAL ATTACHMENTS Concrete Attachments Detail 11 “L” B32I-8 or Stronger Concrete Insert Attached to Concrete Structure (See Pages 77 & 78) B633- 1 /2, B634, B335-2- 1 /2 or B650- 1 /2 Adjustable Hinge (See Pages 59 & 60) Reduce loads by 50% when Adjustable Hinge is mounted within 2” (51mm) from the end of the insert. Use 1 /2” diameter bolts and 1 /2” channel nuts B-Line Channel (Longitudinal or Transverse Brace) Load Minimum Structure Allowable Insert Connection Load Length Type “L” lbs. (kN) in. (mm) I,II,III,IV,V 975 (4.33) 8" (203) COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 33 of Raafat S. Aboulhosn Structural Engineer S 3913

STRUCTURAL ATTACHMENTS Wood Beam Attachments (Used for Bracing Perpendicular) Detail 12 B3248-2 x 2 x 1 /4 (min.) Series Square Washer & Hex Nut (See Pages 62 & 74) Wood Beam Thickness Thru bolt of diameter “D”. Must be above the neutral axis of wood beam and a minimum of (4 x ‘D’) from top and bottom of the beam. Adjustable Hinge (See Page 59) 1 /2" x 1 1 /4" Hex Head Cap Screws & N225WO Nuts (See Pages 61 & 62) B-Line Channel Longitudinal or Transverse Brace 1 Load 1 min. 1 1 /2” (38mm) 3 1 /2” (89mm) Structure Allowable Minimum Beam Minimum Beam Connection Load * Thickness Thickness Type Bolt Dia ‘D’ Bolt Dia ‘D’ lbs. (kN) in. (mm) in. (mm) I 175 (0.78) 1/2" (13) 1/2" (13) II 300 (1.33) 1/2" (13) 1/2" (13) III 450 (2.00) 3/4" (19) 1/2" (13) IV 675 (3.00) -- -- 5/8" (16) V 975 (4.33) -- -- 3/4" (19) * Based on douglas fir with .51 specific gravity or greater. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 34 of

STRUCTURAL ATTACHMENTS<br />

Concrete Attachments<br />

Detail 11<br />

“L”<br />

B32I-8 or Stronger Concrete Insert<br />

Attached to Concrete Structure<br />

(See Pages 77 & 78)<br />

B633- 1 /2, B634,<br />

B335-2- 1 /2 or B650- 1 /2<br />

Adjustable Hinge<br />

(See Pages 59 & 60)<br />

Reduce loads by 50% when<br />

Adjustable Hinge is mounted within<br />

2” (51mm) from the end of the insert.<br />

Use 1 /2” diameter bolts and<br />

1 /2” channel nuts<br />

B-<strong>Line</strong> Channel<br />

(Longitudinal or Transverse Brace)<br />

Load<br />

Minimum<br />

Structure Allowable Insert<br />

Connection Load Length<br />

Type<br />

“L”<br />

lbs. (kN) in. (mm)<br />

I,II,III,IV,V 975 (4.33) 8" (203)<br />

COOPER B-<strong>Line</strong><br />

509 West Monroe Street<br />

Highland, Illinois 62249<br />

Phone: 800-851-7415<br />

Fax: 618-654-1917<br />

Date:<br />

Page No.<br />

Sheet Number:<br />

6 - 2 - 06<br />

33<br />

of<br />

Raafat S. Aboulhosn<br />

Structural Engineer S 3913