Cooper B-Line Seismic Restraints - Dixie Construction Products
Cooper B-Line Seismic Restraints - Dixie Construction Products
Cooper B-Line Seismic Restraints - Dixie Construction Products
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
STRUCTURAL ATTACHMENTS<br />
Concrete Attachments<br />
Minimum distance from<br />
edge of concrete to center<br />
of bolt is (10 x 'D').<br />
B2500 Spot Insert with<br />
N2500 Square Nut of thread<br />
size 'D'.<br />
(See Page 76)<br />
Detail 10<br />
Metal Deck<br />
1”<br />
(25mm)<br />
min.<br />
E<br />
B200 Series Square Washer<br />
(See Page 62)<br />
B-<strong>Line</strong> Adjustable Hinge<br />
Longitudinal or Transverse<br />
Brace<br />
(See Page 59)<br />
1<br />
1 min.<br />
1 /2" x 1 1 /4" Hex Head<br />
Cap Screws & N225WO Nuts<br />
(See Pages 61 & 62)<br />
B-<strong>Line</strong> Channel<br />
Longitudinal or<br />
Transverse Brace<br />
Load<br />
Normal Weight Concrete<br />
Minimum<br />
Structure Thread Minimum Distance<br />
Connection Load Size Embedment Between<br />
Type 'D' 'E' Anchors<br />
lbs. (kN) in. (mm) in. (mm)<br />
I 175 (0.78) 1/2"-13, 5 /8"-11, 3 /4"-10, 7 /8"-9 1 9 /16" (40) 6" (152)<br />
* B-<strong>Line</strong> Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete.<br />
COOPER B-<strong>Line</strong><br />
509 West Monroe Street<br />
Highland, Illinois 62249<br />
Phone: 800-851-7415<br />
Fax: 618-654-1917<br />
Date:<br />
Page No.<br />
Sheet Number:<br />
Raafat S. Aboulhosn<br />
Structural Engineer S 3913<br />
6 - 2 - 06<br />
32<br />
of