STRUCTURAL ATTACHMENTS Concrete Attachments Detail 9 Slab Minimum distance from edge of concrete to center of bolt is (10 x 'D'). B2500 Spot Insert with N2500 Square Nut of thread size 'D'. (See Page 76) 1” (25mm) min. Minimum embedment in concrete 'E'. B200 Series Square Washer (See Page 62) B-Line Adjustable Hinge Longitudinal or Transverse Brace (See Page 59) 1 1 /2" x 1 1 /4" Hex Head Cap Screws & N225WO Nuts (See Pages 61 & 62) 1 min. B-Line Channel Longitudinal or Transverse Brace Load Minimum Structure Thread Minimum Distance Connection Load Size Embedment Between Type 'D' 'E' Anchors lbs. (kN) in. (mm) in. (mm) I 175 (0.78) 1/2"-13, 5 /8"-11, 3 /4"-10, 7 /8"-9 1 9 /16" (40) 6" (152) * B-Line Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 31 of Raafat S. Aboulhosn Structural Engineer S 3913
STRUCTURAL ATTACHMENTS Concrete Attachments Minimum distance from edge of concrete to center of bolt is (10 x 'D'). B2500 Spot Insert with N2500 Square Nut of thread size 'D'. (See Page 76) Detail 10 Metal Deck 1” (25mm) min. E B200 Series Square Washer (See Page 62) B-Line Adjustable Hinge Longitudinal or Transverse Brace (See Page 59) 1 1 min. 1 /2" x 1 1 /4" Hex Head Cap Screws & N225WO Nuts (See Pages 61 & 62) B-Line Channel Longitudinal or Transverse Brace Load Normal Weight Concrete Minimum Structure Thread Minimum Distance Connection Load Size Embedment Between Type 'D' 'E' Anchors lbs. (kN) in. (mm) in. (mm) I 175 (0.78) 1/2"-13, 5 /8"-11, 3 /4"-10, 7 /8"-9 1 9 /16" (40) 6" (152) * B-Line Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 32 of
- Page 1 and 2: SEISMIC RESTRAINTS Multi-Directiona
- Page 3 and 4: TABLE OF CONTENTS General Informati
- Page 5 and 6: GENERAL INFORMATION I p = Importanc
- Page 7 and 8: GENERAL INFORMATION Cable tray syst
- Page 9 and 10: GENERAL INFORMATION c) Check the re
- Page 11 and 12: GENERAL INFORMATION f) When a flexi
- Page 13 and 14: GENERAL NOTES FOR SEISMIC BRACING G
- Page 15 and 16: SINGLE PIPE/CONDUIT BRACING Single
- Page 17 and 18: SINGLE PIPE BRACING PIPE CLAMP TRAN
- Page 19 and 20: CLEVIS HANGER TRANSVERSE BRACING (F
- Page 21 and 22: TRAPEZE BRACING TRAPEZE TRANSVERSE
- Page 23 and 24: TRAPEZE BRACING TRAPEZE TRANSVERSE
- Page 25 and 26: TRAPEZE BRACING Typical Trapeze ATR
- Page 27 and 28: STRUCTURAL ATTACHMENTS ‘T’ Conc
- Page 29 and 30: Concrete Attachments Detail 4 Metal
- Page 31 and 32: Concrete Attachments STRUCTURAL ATT
- Page 33: STRUCTURAL ATTACHMENTS Minimum dist
- Page 37 and 38: STRUCTURAL ATTACHMENTS Wood Beam At
- Page 39 and 40: STRUCTURAL ATTACHMENTS Wood Beam At
- Page 41 and 42: Structural Steel Detail 16 Case 1 C
- Page 43 and 44: Concrete Attachments To Slab HANGER
- Page 45 and 46: Concrete Attachments To Slab HANGER
- Page 47 and 48: Concrete Attachments To Slab HANGER
- Page 49 and 50: Concrete Attachments To Slab HANGER
- Page 51 and 52: Strut Attachments Typical All Threa
- Page 53 and 54: HANGER ROD ATTACHMENTS & APPROVED C
- Page 55 and 56: HANGER ROD ATTACHMENTS & APPROVED C
- Page 57 and 58: HANGER ROD ATTACHMENTS & APPROVED C
- Page 59 and 60: HANGER ROD SWIVEL ATTACHMENTS A 2 3
- Page 61 and 62: APPROVED COMPONENTS SC228 HANGER RO
- Page 63 and 64: APPROVED COMPONENTS NOTE: B633 can
- Page 65 and 66: APPROVED COMPONENTS Hardware SEISMI
- Page 67 and 68: APPROVED COMPONENTS 'A' (Rod Size)
- Page 69 and 70: APPROVED COMPONENTS 'A' (Rod Size)
- Page 71 and 72: APPROVED COMPONENTS Copper Adjustab
- Page 73 and 74: APPROVED COMPONENTS Vertical Load S
- Page 75 and 76: APPROVED COMPONENTS Seismic Approva
- Page 77 and 78: APPROVED COMPONENTS 'A 'T' 2 'A 'T'
- Page 79 and 80: APPROVED COMPONENTS 2” (50.8mm) 3
- Page 81 and 82: APPROVED COMPONENTS 2 9 /16" (65mm)
- Page 83 and 84: APPENDIX - SEISMIC MAP SEISMIC MAP
STRUCTURAL ATTACHMENTS<br />
Concrete Attachments<br />
Detail 9<br />
Slab<br />
Minimum distance from<br />
edge of concrete to center<br />
of bolt is (10 x 'D').<br />
B2500 Spot Insert with<br />
N2500 Square Nut of<br />
thread size 'D'.<br />
(See Page 76)<br />
1”<br />
(25mm)<br />
min.<br />
Minimum embedment<br />
in concrete 'E'.<br />
B200 Series Square Washer<br />
(See Page 62)<br />
B-<strong>Line</strong> Adjustable Hinge<br />
Longitudinal or Transverse Brace<br />
(See Page 59)<br />
1<br />
1 /2" x 1 1 /4" Hex Head<br />
Cap Screws & N225WO Nuts<br />
(See Pages 61 & 62)<br />
1 min.<br />
B-<strong>Line</strong> Channel<br />
Longitudinal or<br />
Transverse Brace<br />
Load<br />
Minimum<br />
Structure Thread Minimum Distance<br />
Connection Load Size Embedment Between<br />
Type 'D' 'E' Anchors<br />
lbs. (kN) in. (mm) in. (mm)<br />
I 175 (0.78) 1/2"-13, 5 /8"-11, 3 /4"-10, 7 /8"-9 1 9 /16" (40) 6" (152)<br />
* B-<strong>Line</strong> Figure B2500 in 3000 psi (20.7 MPa) minimum normal weight concrete.<br />
COOPER B-<strong>Line</strong><br />
509 West Monroe Street<br />
Highland, Illinois 62249<br />
Phone: 800-851-7415<br />
Fax: 618-654-1917<br />
Date:<br />
Page No.<br />
Sheet Number:<br />
6 - 2 - 06<br />
31<br />
of<br />
Raafat S. Aboulhosn<br />
Structural Engineer S 3913