10.11.2014 Views

Cooper B-Line Seismic Restraints - Dixie Construction Products

Cooper B-Line Seismic Restraints - Dixie Construction Products

Cooper B-Line Seismic Restraints - Dixie Construction Products

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

TRAPEZE BRACING<br />

TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING (Figure 11)<br />

B-<strong>Line</strong> Channel<br />

Longitudinal Brace<br />

(See page 11)<br />

ATR<br />

All Threaded Rod<br />

(See Page 57)<br />

Rod Stiffener<br />

(See Pages 57 & 58)<br />

B2400<br />

Series<br />

Pipe Straps<br />

(See Page 71)<br />

1 (Min.)<br />

1<br />

B-<strong>Line</strong> Channel -<br />

Size as Required<br />

(See Page 22 -<br />

Table 4 & 4A For<br />

Channel Load Data)<br />

See Note 3b<br />

on page 17<br />

B2000 Series<br />

Pipe Straps<br />

(See Page 70)<br />

B-<strong>Line</strong> Channel<br />

Transverse Brace<br />

(See page 11)<br />

B335-2- 1 /2 Adjustable Hinge<br />

Longitudinal Brace<br />

Hex Nut &<br />

(See Page 59)<br />

Square Washer<br />

(See Page 62)<br />

Notes:<br />

1). B335-2 adjustable hinges for longitudinal braces may be attached on either side adjacent<br />

to the all thread rod, or attached to the all thread rod itself.<br />

2). B335-2 adjustable hinges for transverse braces may be attached to the all thread rod.<br />

3). Two B335-2 adjustable hinges may be attached to the strut trapeze using the same bolt<br />

or all thread rod.<br />

4). It is not necessary to install both transverse braces and longitudinal braces on the same trapeze<br />

support. Either set of braces may be removed to form a longitudinal brace only or a transverse<br />

brace only if desired.<br />

5). Longitudinal braces, when needed, must be installed at both ends of trapeze.<br />

6). The equipment shown on this trapeze support is generic in nature. Any number of pipes,<br />

conduits, ductwork or cable tray may be supported following the system weight and support<br />

spans listed in Appendix 2 - Table 2.<br />

7). Torque all nuts per Note D, page 9.<br />

8). Refer to note Q, page 10 for installations requiring insulated pipe.<br />

COOPER B-<strong>Line</strong><br />

509 West Monroe Street<br />

Highland, Illinois 62249<br />

Phone: 800-851-7415<br />

Fax: 618-654-1917<br />

Date:<br />

Page No.<br />

Sheet Number:<br />

Raafat S. Aboulhosn<br />

Structural Engineer S 3913<br />

6 - 2 - 06<br />

20<br />

of

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!