CLEVIS HANGER TRANSVERSE BRACING (Figure 7)<br />

SINGLE PIPE BRACING - COPPER TUBING<br />

ATR<br />

All Threaded Rod<br />

(See Page 57 for<br />

minimum diameter)<br />

Rod Stiffener<br />

(See Pages 57 & 58)<br />

1<br />

1 (Min.)<br />

B-<strong>Line</strong> Channel<br />

Transverse Brace<br />

(See page 11)<br />

B335-2-Bolt Size Adjustable Hinge<br />

(See Page 59)<br />

B3104CTPS Pipe Sleeve<br />

B3104CT Series Clevis Hanger<br />

(See Page 68)<br />

Copper Adjustable Pipe<br />

Tubing Size Clevis Hanger Hinge Sleeve<br />

in. (mm) Part No. Part No. Part No.*<br />

1/2" (15) B3104CT- 1 /2 N/A N/A<br />

3/4" (20) B3104CT- 3 /4 N/A N/A<br />

1" (25) B3104CT-1 B335-2- 3 /8 B3104CTPS-1<br />

1 1 /4" (32) B3104CT-1 1 /4 B335-2- 3 /8 B3104CTPS-1 1 /4<br />

1 1 /2" (40) B3104CT-1 1 /2 B335-2- 3 /8 B3104CTPS-1 1 /2<br />

2" (50) B3104CT-2 B335-2- 3 /8 B3104CTPS-2<br />

2 1 /2" (65) B3104CT-2 1 /2 B335-2- 3 /8 B3104CTPS-2 1 /2<br />

3" (80) B3104CT-3 B335-2- 3 /8 B3104CTPS-3<br />

3 1 /2" (90) B3104CT-3 1 /2 B335-2- 3 /8 B3104CTPS-3 1 /2<br />

4" (100) B3104CT-4 B335-2- 3 /8 B3104CTPS-4<br />

* Not included when ordering standard B3104CT Series Clevis Hanger.<br />

Notes:<br />

Pipe sleeve required over cross bolt of Clevis Hanger when using the brace connection shown above (Figure 7).<br />

Refer to Note Q) on page 10 for installations requiring insulated pipe.<br />

LONGITUDINAL BRACING (Figure 8)<br />

Rod Stiffener May Be Required<br />

(See Pages 57 & 58)<br />

B335V-Bolt Size<br />

Adjustable Half Hinge<br />

(See Page 59)<br />

Copper Riser Adjustable<br />

Tubing Size Clamp * Half Hinge<br />

in. (mm) Part No. Part No.<br />

B-<strong>Line</strong> Channel<br />

Longitudinal Brace<br />

(See page 11)<br />

1" (25) B3373CT-1 B335V- 1 /2<br />

1 1 /4" (32) B3373CT-1 1 /4 B335V- 1 /2<br />

1 1 /2" (40) B3373CT-1 1 /2 B335V- 1 /2<br />

2" (50) B3373CT-2 B335V- 1 /2<br />

2 1 /2" (65) B3373CT-2 1 /2 B335V- 1 /2<br />

3" (80) B3373CT-3 B335V- 1 /2<br />

3 1 /2" (90) B3373CT-3 1 /2 B335V- 1 /2<br />

4" (100) B3373CT-4 B335V- 1 /2<br />

Pipe Hanger<br />

or Support<br />

4” max.<br />

(101mm)<br />

B3373CT<br />

Riser Clamp Series<br />

(See Page 69)<br />

* See note D) on page 9 for clamp torque values.<br />

Note: Install brace within 4" (101mm) of hanger.<br />

Refer to Note Q) on page 10 for installations requiring insulated pipe.<br />

COOPER B-<strong>Line</strong><br />

509 West Monroe Street<br />

Highland, Illinois 62249<br />

Phone: 800-851-7415<br />

Fax: 618-654-1917<br />

Date:<br />

Page No.<br />

Sheet Number:<br />

Raafat S. Aboulhosn<br />

Structural Engineer S 3913<br />

6 - 2 - 06<br />