1999 BOCA (Building Officials and Code Administrators) As defined in the 1999 BOCA, Chapter 16, Section 1610.6.4, the seismic horizontal force, F p , may be calculated using the following formula: Where, F p = Seismic Force Level F p = A v C c Pa c W c A v = Peak velocity-related acceleration (Section 1610.1.3) C c = Seismic coefficient for mechanical, electrical components and systems (Table 1610.6.4(1)) P = Performance criteria factor (Table 1610.6.4(1)) a c = Attachment amplification factor (Table 1610.6.4(2)) W c = Operating weight of the mechanical, electrical component of system Example This example is for a primary cable tray system suspended in a surgical center in St. Louis, MO. F p = A v C c Pa c W c A v = (0.15) for the St. Louis, MO area (Figure 1610.1.3(1)) C c = (2.0) for a primary cable tray system (Table 1610.6.4(1)) P = (1.5) for a primary cable tray system (Table 1610.6.4(1)) - Group III for an essential Surgery or Emergency Treatment Facility (Table 1610.1.6) a c = Always (1.0) when using a fixed connection type (Table 1610.6.4(2)) F p = 0.15(2.0)(1.5)(1.0)W c = .45W c = .45g To convert F p from a strength design, as just determined from the building code, to an Allowable Stress Design (ASD) as used in the Cooper B-Line Seismic Restraints Manual divide by 1.4. F p = 0.45g = 0.32g (ASD) 1.4 0.32g is the Allowable Stress Design Seismic Load Factor determined from the 1999 BOCA. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 155 of Raafat S. Aboulhosn Structural Engineer S 3913

Appendix 5 This page has been reserved for future professional engineering approvals. These additional stamps are beyond the scope of OSHPD pre-approval and are not intended for use on hospital projects in the State of California. A current version of this page with all available engineering approvals is available on our website at http://www.cooperbline.com/pdf/catalogs/SRS02/appendix5.pdf COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 156 of

1999 BOCA (Building Officials and Code Administrators)<br />

As defined in the 1999 BOCA, Chapter 16, Section 1610.6.4, the seismic horizontal force, F p , may be calculated<br />

using the following formula:<br />

Where,<br />

F p = <strong>Seismic</strong> Force Level<br />

F p = A v C c Pa c W c<br />

A v = Peak velocity-related acceleration (Section 1610.1.3)<br />

C c = <strong>Seismic</strong> coefficient for mechanical, electrical components and systems<br />

(Table 1610.6.4(1))<br />

P = Performance criteria factor (Table 1610.6.4(1))<br />

a c = Attachment amplification factor (Table 1610.6.4(2))<br />

W c = Operating weight of the mechanical, electrical component of system<br />

Example<br />

This example is for a primary cable tray system suspended in a surgical center in St. Louis, MO.<br />

F p = A v C c Pa c W c<br />

A v = (0.15) for the St. Louis, MO area (Figure 1610.1.3(1))<br />

C c = (2.0) for a primary cable tray system (Table 1610.6.4(1))<br />

P = (1.5) for a primary cable tray system (Table 1610.6.4(1))<br />

- Group III for an essential Surgery or Emergency Treatment<br />

Facility (Table 1610.1.6)<br />

a c = Always (1.0) when using a fixed connection type (Table 1610.6.4(2))<br />

F p = 0.15(2.0)(1.5)(1.0)W c = .45W c = .45g<br />

To convert F p from a strength design, as just determined from the building code, to an Allowable<br />

Stress Design (ASD) as used in the <strong>Cooper</strong> B-<strong>Line</strong> <strong>Seismic</strong> <strong>Restraints</strong> Manual divide by 1.4.<br />

F p = 0.45g = 0.32g (ASD)<br />

1.4<br />

0.32g is the Allowable Stress Design <strong>Seismic</strong> Load Factor determined from the 1999 BOCA.<br />

COOPER B-<strong>Line</strong><br />

509 West Monroe Street<br />

Highland, Illinois 62249<br />

Phone: 800-851-7415<br />

Fax: 618-654-1917<br />

Date:<br />

Page No.<br />

Sheet Number:<br />

6 - 2 - 06<br />

155<br />

of<br />

Raafat S. Aboulhosn<br />

Structural Engineer S 3913