1999 BOCA (Building Officials and Code Administrators) As defined in the 1999 BOCA, Chapter 16, Section 1610.6.4, the seismic horizontal force, F p , may be calculated using the following formula: Where, F p = Seismic Force Level F p = A v C c Pa c W c A v = Peak velocity-related acceleration (Section 1610.1.3) C c = Seismic coefficient for mechanical, electrical components and systems (Table 1610.6.4(1)) P = Performance criteria factor (Table 1610.6.4(1)) a c = Attachment amplification factor (Table 1610.6.4(2)) W c = Operating weight of the mechanical, electrical component of system Example This example is for a primary cable tray system suspended in a surgical center in St. Louis, MO. F p = A v C c Pa c W c A v = (0.15) for the St. Louis, MO area (Figure 1610.1.3(1)) C c = (2.0) for a primary cable tray system (Table 1610.6.4(1)) P = (1.5) for a primary cable tray system (Table 1610.6.4(1)) - Group III for an essential Surgery or Emergency Treatment Facility (Table 1610.1.6) a c = Always (1.0) when using a fixed connection type (Table 1610.6.4(2)) F p = 0.15(2.0)(1.5)(1.0)W c = .45W c = .45g To convert F p from a strength design, as just determined from the building code, to an Allowable Stress Design (ASD) as used in the Cooper B-Line Seismic Restraints Manual divide by 1.4. F p = 0.45g = 0.32g (ASD) 1.4 0.32g is the Allowable Stress Design Seismic Load Factor determined from the 1999 BOCA. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 155 of Raafat S. Aboulhosn Structural Engineer S 3913
Appendix 5 This page has been reserved for future professional engineering approvals. These additional stamps are beyond the scope of OSHPD pre-approval and are not intended for use on hospital projects in the State of California. A current version of this page with all available engineering approvals is available on our website at http://www.cooperbline.com/pdf/catalogs/SRS02/appendix5.pdf COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 156 of
- Page 107 and 108: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 109 and 110: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 111 and 112: Appendix 2 Seismic Bracing Charts f
- Page 113 and 114: TRAPEZE BRACING Seismic Bracing Cha
- Page 115 and 116: TRAPEZE BRACING Seismic Bracing Cha
- Page 117 and 118: Seismic Bracing Charts for Trapeze
- Page 119 and 120: TRAPEZE BRACING Seismic Bracing Cha
- Page 121 and 122: TRAPEZE BRACING Seismic Bracing Cha
- Page 123 and 124: Seismic Bracing Charts for Trapeze
- Page 125 and 126: TRAPEZE BRACING Seismic Bracing Cha
- Page 127 and 128: TRAPEZE BRACING Seismic Bracing Cha
- Page 129 and 130: Seismic Bracing Charts for Trapeze
- Page 131 and 132: TRAPEZE BRACING Seismic Bracing Cha
- Page 133 and 134: TRAPEZE BRACING Seismic Bracing Cha
- Page 135 and 136: Seismic Bracing Charts for Trapeze
- Page 137 and 138: TRAPEZE BRACING Seismic Bracing Cha
- Page 139 and 140: TRAPEZE BRACING Seismic Bracing Cha
- Page 141 and 142: Seismic Bracing Charts for Trapeze
- Page 143 and 144: TRAPEZE BRACING Seismic Bracing Cha
- Page 145 and 146: TRAPEZE BRACING Seismic Bracing Cha
- Page 147 and 148: TRAPEZE BRACING Seismic Bracing Cha
- Page 149 and 150: Appendix 3 Proof Test Instructions
- Page 151 and 152: Example: Deeply Embedded Anchors In
- Page 153 and 154: Check if value falls within the all
- Page 155 and 156: 1997 Uniform Building Code As defin
- Page 157: Example Two, Shallow Embedded Ancho
1999 BOCA (Building Officials and Code Administrators)<br />
As defined in the 1999 BOCA, Chapter 16, Section 1610.6.4, the seismic horizontal force, F p , may be calculated<br />
using the following formula:<br />
Where,<br />
F p = <strong>Seismic</strong> Force Level<br />
F p = A v C c Pa c W c<br />
A v = Peak velocity-related acceleration (Section 1610.1.3)<br />
C c = <strong>Seismic</strong> coefficient for mechanical, electrical components and systems<br />
(Table 1610.6.4(1))<br />
P = Performance criteria factor (Table 1610.6.4(1))<br />
a c = Attachment amplification factor (Table 1610.6.4(2))<br />
W c = Operating weight of the mechanical, electrical component of system<br />
Example<br />
This example is for a primary cable tray system suspended in a surgical center in St. Louis, MO.<br />
F p = A v C c Pa c W c<br />
A v = (0.15) for the St. Louis, MO area (Figure 1610.1.3(1))<br />
C c = (2.0) for a primary cable tray system (Table 1610.6.4(1))<br />
P = (1.5) for a primary cable tray system (Table 1610.6.4(1))<br />
- Group III for an essential Surgery or Emergency Treatment<br />
Facility (Table 1610.1.6)<br />
a c = Always (1.0) when using a fixed connection type (Table 1610.6.4(2))<br />
F p = 0.15(2.0)(1.5)(1.0)W c = .45W c = .45g<br />
To convert F p from a strength design, as just determined from the building code, to an Allowable<br />
Stress Design (ASD) as used in the <strong>Cooper</strong> B-<strong>Line</strong> <strong>Seismic</strong> <strong>Restraints</strong> Manual divide by 1.4.<br />
F p = 0.45g = 0.32g (ASD)<br />
1.4<br />
0.32g is the Allowable Stress Design <strong>Seismic</strong> Load Factor determined from the 1999 BOCA.<br />
COOPER B-<strong>Line</strong><br />
509 West Monroe Street<br />
Highland, Illinois 62249<br />
Phone: 800-851-7415<br />
Fax: 618-654-1917<br />
Date:<br />
Page No.<br />
Sheet Number:<br />
6 - 2 - 06<br />
155<br />
of<br />
Raafat S. Aboulhosn<br />
Structural Engineer S 3913