TRAPEZE BRACING Seismic Bracing Charts for Trapeze Supports - Figure 11 Table 2 for Seismic Force Level 0.15g (ASD) 26 - 50 (W t ) continued on next page. Hanger Rod Size Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze Total Support Brace Structure Brace Structure Weight Span Interval 3,4 Connection Interval 3,4 Rod Minimum Rod Minimum Connection W t L t * Type 2 Type 2 Load 5 Rod Size 6 Load 5 Rod Size 6 lbs./ft. ft. ft. ft. lbs. in. lbs. in. 0 - 10 6 36 I 78 I 32 3 /8 90 3 /8 0 - 10 8 40 I 80 I 42 3 /8 102 3 /8 0 - 10 10 40 I 80 I 53 3 /8 112 3 /8 0 - 10 12 36 I 72 I 63 3/8 117 3/8 0 - 10 16 32 I 80 I 84 3/8 144 3/8 0 - 10 20 40 I 80 I 105 3/8 165 3/8 0 - 10 24 24 I 72 I 126 3/8 180 3/8 11 - 25 6 30 I 66 I 79 3/8 202 3/8 11 - 25 6 36 II 78 II 79 3 /8 225 3 /8 11 - 25 8 32 I 64 I 105 3 /8 225 3 /8 11 - 25 8 40 II 80 II 105 3/8 255 3/8 11 - 25 10 30 I 60 I 132 3/8 244 3/8 11 - 25 10 40 II 80 II 132 3 /8 281 3 /8 11 - 25 12 24 I 60 I 158 3 /8 270 3 /8 11 - 25 12 36 II 72 II 158 3/8 292 3/8 11 - 25 16 32 I 64 I 210 3 /8 330 3 /8 11 - 25 16 --- --- 80 II 210 3/8 360 3/8 11 - 25 20 20 I 60 I 263 3/8 375 3/8 11 - 25 20 40 II 80 II 263 3 /8 412 3 /8 11 - 25 24 24 I 48 I 315 3 /8 405 3 /8 11 - 25 24 --- --- 72 II 315 3/8 450 3/8 26 - 50 6 12 I 30 I 158 3/8 270 3/8 26 - 50 6 24 II 54 II 158 3 /8 360 3 /8 26 - 50 6 36 III 78 III 158 3/8 450 3/8 26 - 50 8 16 I 32 I 210 3/8 330 3/8 26 - 50 8 24 II 56 II 210 3 /8 420 3 /8 26 - 50 8 40 III 80 III 210 3/8 510 3/8 26 - 50 10 10 I 30 I 263 3 /8 375 3 /8 26 - 50 10 20 II 50 II 263 3 /8 450 3 /8 26 - 50 10 40 III 80 III 263 3 /8 562 3 /8 26 - 50 12 12 I 24 I 315 3/8 405 3/8 26 - 50 12 24 II 48 II 315 3 /8 495 3 /8 26 - 50 12 36 III 72 III 315 3/8 585 3/8 * See note 2 on page 17. See page 145 for footnotes. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: 6 - 2 - 06 113 of Raafat S. Aboulhosn Structural Engineer S 3913
Seismic Bracing Charts for Trapeze Supports - Figure 11 Table 2 cont. for Seismic Force Level 0.15g (ASD) TRAPEZE BRACING Hanger Rod Size Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze Total Support Brace Structure Brace Structure Weight Span Interval 3,4 Connection Interval 3,4 Rod Minimum Rod Minimum Connection W t L t * Type 2 Type 2 Load 5 Rod Size 6 Load 5 Rod Size 6 lbs./ft. ft. ft. ft. lbs. in. lbs. in. 26 - 50 16 16 I 32 I 420 3/8 540 3/8 26 - 50 16 --- --- 48 II 420 3 /8 600 3 /8 26 - 50 16 32 III 80 III 420 3/8 720 1/2 26 - 50 20 --- --- 20 I 525 3/8 600 3/8 26 - 50 20 20 II 40 II 525 3 /8 675 1 /2 26 - 50 20 40 III 80 III 525 3/8 825 1/2 26 - 50 24 --- --- 24 I 630 1 /2 720 1 /2 26 - 50 24 24 II 48 II 630 1 /2 810 1 /2 26 - 50 24 --- --- 72 III 630 1 /2 900 1 /2 51 - 75 6 6 I 18 I 237 3/8 337 3/8 51 - 75 6 18 II 36 II 237 3 /8 439 3 /8 51 - 75 6 24 III 54 III 237 3/8 540 3/8 51 - 75 6 36 IV 78 IV 237 3 /8 675 1 /2 51 - 75 8 8 I 16 I 315 3/8 405 3/8 51 - 75 8 16 II 32 II 315 3 /8 495 3 /8 51 - 75 8 24 III 56 III 315 3/8 630 1/2 51 - 75 8 40 IV 80 IV 315 3 /8 765 1 /2 51 - 75 10 10 I 20 I 394 3/8 506 3/8 51 - 75 10 --- --- 30 II 394 3 /8 562 3 /8 51 - 75 10 20 III 50 III 394 3/8 675 1/2 51 - 75 10 40 IV 80 IV 394 3 /8 844 1 /2 51 - 75 12 --- --- 12 I 472 3 /8 540 3 /8 51 - 75 12 12 II 36 II 472 3 /8 675 1 /2 51 - 75 12 24 III 48 III 472 3 /8 742 1 /2 51 - 75 12 36 IV 72 IV 472 3 /8 877 1 /2 51 - 75 16 --- --- 16 I 630 1 /2 720 1 /2 51 - 75 16 16 II 32 II 630 1/2 810 1/2 51 - 75 16 --- --- 48 III 630 1 /2 900 1 /2 51 - 75 16 32 IV 80 IV 630 1/2 1080 1/2 51 - 75 20 --- --- 20 I 788 1 /2 900 1 /2 51 - 75 20 20 III 40 III 788 1/2 1012 1/2 51 - 75 20 40 IV 80 IV 788 1 /2 1237 5 /8 51 - 75 24 --- --- 24 II 945 1/2 1080 1/2 51 - 75 24 24 III 48 III 945 1 /2 1215 5 /8 51 - 75 24 --- --- 72 IV 945 1/2 1350 5/8 * See note 2 on page 17. See page 145 for footnotes. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 800-851-7415 Fax: 618-654-1917 Date: Page No. Sheet Number: Raafat S. Aboulhosn Structural Engineer S 3913 6 - 2 - 06 114 of
- Page 65 and 66: APPROVED COMPONENTS Hardware SEISMI
- Page 67 and 68: APPROVED COMPONENTS 'A' (Rod Size)
- Page 69 and 70: APPROVED COMPONENTS 'A' (Rod Size)
- Page 71 and 72: APPROVED COMPONENTS Copper Adjustab
- Page 73 and 74: APPROVED COMPONENTS Vertical Load S
- Page 75 and 76: APPROVED COMPONENTS Seismic Approva
- Page 77 and 78: APPROVED COMPONENTS 'A 'T' 2 'A 'T'
- Page 79 and 80: APPROVED COMPONENTS 2” (50.8mm) 3
- Page 81 and 82: APPROVED COMPONENTS 2 9 /16" (65mm)
- Page 83 and 84: APPENDIX - SEISMIC MAP SEISMIC MAP
- Page 85 and 86: Appendix 1 Support Spacing for Sing
- Page 87 and 88: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 89 and 90: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 91 and 92: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 93 and 94: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 95 and 96: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 97 and 98: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 99 and 100: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 101 and 102: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 103 and 104: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 105 and 106: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 107 and 108: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 109 and 110: SUPPORT SPACING FOR SINGLE ROD HANG
- Page 111 and 112: Appendix 2 Seismic Bracing Charts f
- Page 113 and 114: TRAPEZE BRACING Seismic Bracing Cha
- Page 115: TRAPEZE BRACING Seismic Bracing Cha
- Page 119 and 120: TRAPEZE BRACING Seismic Bracing Cha
- Page 121 and 122: TRAPEZE BRACING Seismic Bracing Cha
- Page 123 and 124: Seismic Bracing Charts for Trapeze
- Page 125 and 126: TRAPEZE BRACING Seismic Bracing Cha
- Page 127 and 128: TRAPEZE BRACING Seismic Bracing Cha
- Page 129 and 130: Seismic Bracing Charts for Trapeze
- Page 131 and 132: TRAPEZE BRACING Seismic Bracing Cha
- Page 133 and 134: TRAPEZE BRACING Seismic Bracing Cha
- Page 135 and 136: Seismic Bracing Charts for Trapeze
- Page 137 and 138: TRAPEZE BRACING Seismic Bracing Cha
- Page 139 and 140: TRAPEZE BRACING Seismic Bracing Cha
- Page 141 and 142: Seismic Bracing Charts for Trapeze
- Page 143 and 144: TRAPEZE BRACING Seismic Bracing Cha
- Page 145 and 146: TRAPEZE BRACING Seismic Bracing Cha
- Page 147 and 148: TRAPEZE BRACING Seismic Bracing Cha
- Page 149 and 150: Appendix 3 Proof Test Instructions
- Page 151 and 152: Example: Deeply Embedded Anchors In
- Page 153 and 154: Check if value falls within the all
- Page 155 and 156: 1997 Uniform Building Code As defin
- Page 157 and 158: Example Two, Shallow Embedded Ancho
- Page 159 and 160: Appendix 5 This page has been reser
<strong>Seismic</strong> Bracing Charts for Trapeze Supports - Figure 11<br />
Table 2 cont. for <strong>Seismic</strong> Force Level 0.15g (ASD)<br />
TRAPEZE BRACING<br />
Hanger Rod Size<br />
Transverse Bracing 1 Longitudinal Bracing 1 Unbraced Trapeze Braced Trapeze<br />
Total Support Brace Structure Brace Structure<br />
Weight Span Interval 3,4 Connection Interval 3,4 Rod Minimum Rod Minimum<br />
Connection<br />
W t L t * Type 2 Type 2 Load 5 Rod Size 6 Load 5 Rod Size 6<br />
lbs./ft. ft. ft. ft. lbs. in. lbs. in.<br />
26 - 50 16 16 I 32 I 420 3/8 540 3/8<br />
26 - 50 16 --- --- 48 II 420 3 /8 600 3 /8<br />
26 - 50 16 32 III 80 III 420 3/8 720 1/2<br />
26 - 50 20 --- --- 20 I 525 3/8 600 3/8<br />
26 - 50 20 20 II 40 II 525 3 /8 675 1 /2<br />
26 - 50 20 40 III 80 III 525 3/8 825 1/2<br />
26 - 50 24 --- --- 24 I 630 1 /2 720 1 /2<br />
26 - 50 24 24 II 48 II 630 1 /2 810 1 /2<br />
26 - 50 24 --- --- 72 III 630 1 /2 900 1 /2<br />
51 - 75 6 6 I 18 I 237 3/8 337 3/8<br />
51 - 75 6 18 II 36 II 237 3 /8 439 3 /8<br />
51 - 75 6 24 III 54 III 237 3/8 540 3/8<br />
51 - 75 6 36 IV 78 IV 237 3 /8 675 1 /2<br />
51 - 75 8 8 I 16 I 315 3/8 405 3/8<br />
51 - 75 8 16 II 32 II 315 3 /8 495 3 /8<br />
51 - 75 8 24 III 56 III 315 3/8 630 1/2<br />
51 - 75 8 40 IV 80 IV 315 3 /8 765 1 /2<br />
51 - 75 10 10 I 20 I 394 3/8 506 3/8<br />
51 - 75 10 --- --- 30 II 394 3 /8 562 3 /8<br />
51 - 75 10 20 III 50 III 394 3/8 675 1/2<br />
51 - 75 10 40 IV 80 IV 394 3 /8 844 1 /2<br />
51 - 75 12 --- --- 12 I 472 3 /8 540 3 /8<br />
51 - 75 12 12 II 36 II 472 3 /8 675 1 /2<br />
51 - 75 12 24 III 48 III 472 3 /8 742 1 /2<br />
51 - 75 12 36 IV 72 IV 472 3 /8 877 1 /2<br />
51 - 75 16 --- --- 16 I 630 1 /2 720 1 /2<br />
51 - 75 16 16 II 32 II 630 1/2 810 1/2<br />
51 - 75 16 --- --- 48 III 630 1 /2 900 1 /2<br />
51 - 75 16 32 IV 80 IV 630 1/2 1080 1/2<br />
51 - 75 20 --- --- 20 I 788 1 /2 900 1 /2<br />
51 - 75 20 20 III 40 III 788 1/2 1012 1/2<br />
51 - 75 20 40 IV 80 IV 788 1 /2 1237 5 /8<br />
51 - 75 24 --- --- 24 II 945 1/2 1080 1/2<br />
51 - 75 24 24 III 48 III 945 1 /2 1215 5 /8<br />
51 - 75 24 --- --- 72 IV 945 1/2 1350 5/8<br />
* See note 2 on page 17.<br />
See page 145 for footnotes.<br />