Transition Plan
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
2-Stairway Handrails:<br />
West Entrance to <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
4-Doors: West Entrance<br />
to <strong>Pierce</strong> <strong>Annex</strong>. [One<br />
set of double doors.]<br />
Rails are 34" - 38" above stair nosing. 12"<br />
minimum level extension beyond top nosing<br />
(parallel with the ground or floor surface) before<br />
being returned. 12" plus one tread width level<br />
extension beyond bottom nosing (parallel with<br />
the ground or floor surface) before being<br />
returned.<br />
5 lb. maximum pressure to operate exterior<br />
doors.<br />
Raise existing handrail height.<br />
Install top and bottom<br />
extensions to existing handrail.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $6,392.39<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
6-Signage: <strong>Pierce</strong> <strong>Annex</strong><br />
1st Floor.<br />
7-Tactile Exit Signage:<br />
<strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
8-Floors and Levels:<br />
<strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
[Four carpets / mats.]<br />
9-Doors: Unisex<br />
Restroom to the Left on<br />
the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each exit door that leads directly to a gradelevel<br />
exterior exit by means of a stairway or<br />
ramp is identified by a tactile exit sign that states<br />
"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />
"EXIT STAIR UP", or "EXIT RAMP UP", as<br />
appropriate.<br />
Carpets or carpet tiles are securely attached<br />
and do not exceed 1/2" in height. Carpet's<br />
exposed edges are fastened to floor surfaces<br />
and have trim along entire length.<br />
5 lb. maximum pressure to operate interior<br />
doors. 3 seconds minimum for door closer to<br />
close from 70 degree position to within 3" of the<br />
latch [ADAAG 404.2.8.1 Door & gate closers<br />
require a 5 second minimum closing time from<br />
open position of 90 degree to 12 degree<br />
position].<br />
Install permanent ID sign to<br />
latch side of door.<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
Secure loose doormat. 1 $980.02<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
6/1/2012 Page 1 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
11-Identification<br />
Symbols, Restrooms:<br />
Unisex Restroom to the<br />
Left on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Unisex - 12" diameter circle 1/4" thick with 1/4"<br />
thick triangle superimposed in the circle. The<br />
circle and triangle symbols contrasts with the<br />
door, light on dark background or dark on light<br />
background [CBC 1115B.6 The triangle shall<br />
contrast w the circle and the circle shall contrast<br />
with the door]. Wall mounted signage: Symbol of<br />
accessibility is mounted on wall sign adjacent to<br />
latch side of door [ADAAG 703.6.1 & CBC<br />
1117B.5.5 Item 4 Pictograms shall have a field<br />
height of 6" ADAAG 703.6.1 Characters and<br />
Braille shall not be located in the pictogram<br />
field]. Verbal description as to restroom usage is<br />
placed directly below the pictogram, if utilized in<br />
conjunction with verbal identification and the<br />
border dimensions of this pictogram is a<br />
minimum of 6" in height.<br />
Install door-mounted sign on<br />
single door. Install wallmounted<br />
sign at single<br />
entrance.<br />
3 $367.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
12-Single<br />
Accommodation Toilet:<br />
Unisex Restroom to the<br />
Left on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
60" minimum diameter turning circle, or a T-<br />
shaped clear space, is provided in room with 12"<br />
maximum door encroachment into the required<br />
clear space. A minimum 60" wide and 48" deep<br />
clear floor space is provided in front of water<br />
closet. Front of toilet paper dispenser is within<br />
36" of the back wall. The toilet paper dispenser<br />
is located on the side wall below the grab bar<br />
and within 7" - 9" of the front of the toilet seat as<br />
measured to the centerline of the dispenser.<br />
Requires<br />
engineering/architectural<br />
evaluation. Relocate the toilet<br />
paper dispenser away from the<br />
top of the grab bar.<br />
3 $7,238.13<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
13-Toilet Grab Bars:<br />
Unisex Restroom to the<br />
Left on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #12 for<br />
additional actions.]<br />
14-Lavatories: Unisex<br />
Restroom to the Left on<br />
the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
The front of the side grab bar extends 54" from<br />
back wall in single accommodation stall. Area<br />
directly above grab bars or proposed grab bars<br />
is free of protruding obstructions to a height of<br />
18" (recessed items are allowed).<br />
18" minimum from center of fixture to side wall<br />
or partition.<br />
Relocate side grab bar.<br />
Relocate the seat cover<br />
dispenser away from the top of<br />
the grab bar.<br />
Replace with accessible<br />
lavatory.<br />
3 $367.51<br />
3 $3,185.07<br />
6/1/2012 Page 2 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
15-Accessories: Unisex<br />
Restroom to the Left on<br />
the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>. [See Sequence<br />
#12 and #13 for<br />
additional actions. Soap<br />
dispenser - 44" high /<br />
seat cover dispenser -<br />
48" high / paper towel<br />
dispenser - 45" high /<br />
toilet paper dispenser -<br />
42-1/2" high.]<br />
40" max. height to all other fixtures (i.e., soap<br />
dispensers, towels, toilet seat covers, auto<br />
dryers, sanitary napkins, waste recepatacles,<br />
etc.). Coat hooks and shelving are located within<br />
appropriate reach ranges (48" max. height<br />
above floor surface is recommended). A<br />
minimum 30" x 48" minimum clear floor or<br />
ground space is provided to allow forward or<br />
parallel approach to accessories.<br />
Install accessible coat hook.<br />
Lower the soap dispenser.<br />
Lower the paper towel<br />
dispenser.<br />
3 $367.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
16-Visual/Audible<br />
Alarms: Unisex<br />
Restroom to the Left on<br />
the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
18-Doors: Unisex<br />
Restroom to the Right<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong> .<br />
20-Identification<br />
Symbols, Restrooms:<br />
Unisex Restroom to the<br />
Right on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
The appliance is placed 80" above the highest<br />
floor level within the space or 6" below the<br />
ceiling, whichever is lower.<br />
5 lb. maximum pressure to operate interior<br />
doors. 3 seconds minimum for door closer to<br />
close from 70 degree position to within 3" of the<br />
latch [ADAAG 404.2.8.1 Door & gate closers<br />
require a 5 second minimum closing time from<br />
open position of 90 degree to 12 degree<br />
position].<br />
Unisex - 12" diameter circle 1/4" thick with 1/4"<br />
thick triangle superimposed in the circle. The<br />
circle and triangle symbols contrasts with the<br />
door, light on dark background or dark on light<br />
background [CBC 1115B.6 The triangle shall<br />
contrast w the circle and the circle shall contrast<br />
with the door]. Wall mounted signage: Symbol of<br />
accessibility is mounted on wall sign adjacent to<br />
latch side of door [ADAAG 703.6.1 & CBC<br />
1117B.5.5 Item 4 Pictograms shall have a field<br />
height of 6" ADAAG 703.6.1 Characters and<br />
Braille shall not be located in the pictogram<br />
field]. Verbal description as to restroom usage is<br />
placed directly below the pictogram, if utilized in<br />
conjunction with verbal identification and the<br />
border dimensions of this pictogram is a<br />
minimum of 6" in height.<br />
Review entire alarm system. 1 $7,115.62<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
Install door-mounted sign on<br />
single door. Install wallmounted<br />
sign at single<br />
entrance.<br />
2 $306.26<br />
3 $367.51<br />
6/1/2012 Page 3 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
21-Single<br />
Accommodation Toilet:<br />
Unisex Restroom to the<br />
Right on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
A minimum 60" wide and 48" deep clear floor<br />
space is provided in front of water closet. Front<br />
of toilet paper dispenser is within 36" of the back<br />
wall. The toilet paper dispenser is located on the<br />
side wall below the grab bar and within 7" - 9" of<br />
the front of the toilet seat as measured to the<br />
centerline of the dispenser.<br />
Requires<br />
engineering/architectural<br />
evaluation. Relocate the toilet<br />
paper dispenser away from the<br />
top of the grab bar.<br />
3 $7,238.13<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
22-Toilet Grab Bars:<br />
Unisex Restroom to the<br />
Right on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #21 for<br />
additional actions.]<br />
23-Lavatories: Unisex<br />
Restroom to the Right<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
24-Accessories: Unisex<br />
Restroom to the Right<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #21 and #22<br />
for additional actions.<br />
Soap dispenser - 43" /<br />
seat cover dispenser -<br />
48" / paper towel<br />
dispenser - 45" / toilet<br />
paper dispenser - 42-<br />
1/4".]<br />
28-Water Fountains<br />
(Drinking): 1st Floor<br />
Corridor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
33-Clear Space at<br />
Doors: 1st Floor Rooms<br />
#124, #123, #103 and<br />
#102 at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Four office doors.]<br />
The front of the side grab bar extends 54" from<br />
back wall in single accommodation stall. Area<br />
directly above grab bars or proposed grab bars<br />
is free of protruding obstructions to a height of<br />
18" (recessed items are allowed).<br />
18" minimum from center of fixture to side wall<br />
or partition.<br />
40" max. height to all other fixtures (i.e., soap<br />
dispensers, towels, toilet seat covers, auto<br />
dryers, sanitary napkins, waste recepatacles,<br />
etc.). Coat hooks and shelving are located within<br />
appropriate reach ranges (48" max. height<br />
above floor surface is recommended). A<br />
minimum 30" x 48" minimum clear floor or<br />
ground space is provided to allow forward or<br />
parallel approach to accessories.<br />
Stream of bubbler is parallel to front edge. The<br />
force required to activate controls does not<br />
exceed 5lbf.<br />
60" min. clear space in direction of door swing.<br />
Minimum strike side clearance on PULL side of<br />
door: 18" wide x 60" depth at interior doors, front<br />
approach.<br />
Relocate side grab bar.<br />
Relocate the seat cover<br />
dispenser away from the top of<br />
the grab bar.<br />
Replace with accessible<br />
lavatory.<br />
Install accessible coat hook.<br />
Lower the soap dispenser.<br />
Adjust angle of stream.<br />
Reduce force needed to<br />
operate fountain controls ( 5 lb.<br />
maximum).<br />
Relocate furniture to provide<br />
clear space. University staff<br />
shall be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
Relocate restricting objects.<br />
3 $367.51<br />
3 $3,185.07<br />
3 $245.01<br />
2 $551.26<br />
1M $428.77<br />
6/1/2012 Page 4 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
34-Signage: 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $980.02<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
35-Doors: Room #107<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
36-Clear Space at<br />
Doors: Room #107 on<br />
the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
37-Signage: Room #107<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Interior<br />
door inside of Room<br />
#107.]<br />
39-Clear Space at<br />
Doors: Behind Room<br />
#107 Toward Lab on the<br />
1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
40-Sales and Service<br />
Counters: Room #106<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Minimum strike side clearance on PUSH side of<br />
door: 12" front approach with latch and closer.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate furniture to provide<br />
clear space. University staff shall<br />
be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
1M $61.25<br />
Relocate existing signage. 3 $490.00<br />
Minimum strike side clearance on PULL side of Relocate furniture to provide 1M $61.25<br />
door: 18" wide x 60" depth at interior doors, front clear space. University staff shall<br />
approach.<br />
be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
Knee space at table(s) is at least 27" high, 30" Install accessible counter. 2 $1,592.53<br />
wide and extends 19" under the table(s) and;<br />
6/1/2012 Page 5 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
41-Sinks: Room #106 on<br />
the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Minimum 30" x 48" clear space is provided in<br />
front of sink that allows forward approach. 34"<br />
maximum height of rim or counter above floor<br />
surfaces. Sink is a maximum of 6-1/2" deep.<br />
Knee clearance under sink is a minimum of 27"<br />
high and 30" wide, and provides an absolute<br />
depth of 19" underneath the sink [ADAAG 606.2<br />
Exception 6 The dip of the overflow shall not be<br />
considered in determining knee and toe<br />
clearance]. Drain and hot water piping is<br />
insulated or configured to prevent contact.<br />
Replace with accessible sink.<br />
Insulate pipes under lavatory<br />
sink. Cut the paneling under<br />
the sink counter to comply with<br />
knee clearance.<br />
3 $3,920.09<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
44-Controls, Operating<br />
Mechanisms & Vending<br />
Machines.: Room #106<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />
hood.]<br />
Forward Reach to Objects: Highest operable<br />
part of object is a maximum of 48" above the<br />
floor surface.<br />
Replace the fume hood with an<br />
accessible fume hood<br />
workstation.<br />
3 $18,216.00 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
46-Protruding Objects:<br />
Room #106 on the 1st<br />
Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Fume hood.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
47-Protruding Objects:<br />
Room #106 on the 1st<br />
Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Power control boxes.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $980.02<br />
6/1/2012 Page 6 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
48-Protruding Objects:<br />
Room #106 on the 1st<br />
Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Emergency eyewash.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $122.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
50-Doors: Room #111<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>. [One set<br />
of double doors.]<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
52-Signage: Room #111<br />
on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
54-Doors: Door to<br />
Courtyard from Room<br />
#111 on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
32" minimum clear width of doorway. 5 lb.<br />
maximum pressure to operate exterior doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted<br />
by DSA Fire / Life Safety.<br />
Consider issues connected<br />
with building pressure / climate<br />
control. Replace door and<br />
frame (concrete or block wall).<br />
2 $5,573.87<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
56-Signage: Door to<br />
Courtyard from Room<br />
#111 on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
57-Elevators: Southeast<br />
Side at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
68" min. width of the car platform with off-center<br />
door panels. Elevator doors have an automatic<br />
reopening device. The device opens the doors<br />
when objects pass through the opening at<br />
heights of 5" and 29" from the floor without<br />
requiring contact. Doors remain open for 20<br />
seconds minimum. At the grade level, a raised<br />
five-pointed star with an outside diameter of 2" is<br />
placed to the left of the raised character.<br />
Install permanent ID sign to<br />
latch side of door.<br />
Requires<br />
engineering/architectural<br />
evaluation. Repair door<br />
operation. Provide a raised five<br />
pointed star at the ground<br />
level.<br />
1 $183.75<br />
1 $9,606.09<br />
6/1/2012 Page 7 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
60-Doors: Southeast<br />
Entrance on the 1st<br />
Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
[One set of double<br />
doors.]<br />
32" minimum clear width of doorway. 5 lb.<br />
maximum pressure to operate exterior doors.<br />
The international symbol of accessibility is<br />
posted at all primary entrances.<br />
Replace door(s) and frame<br />
(stud wall). Adjust door<br />
opening pressure / closing time<br />
unless accepted by DSA Fire /<br />
Life Safety. Consider issues<br />
connected with building<br />
pressure / climate control. Post<br />
a sign/decal displaying the<br />
"International Symbol of<br />
Accessibility" at the primary<br />
entrance.<br />
2 $3,466.84<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
62-Stairways: Southeast<br />
Entrance on the 1st<br />
Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Two staircases.]<br />
All steps have uniform riser height and tread<br />
width.<br />
Replace existing steps. 2 $30,135.81<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
63-Stairway Handrails:<br />
Southeast Entrance on<br />
the 1st Floor to <strong>Pierce</strong><br />
<strong>Annex</strong>. [Two stair<br />
cases.]<br />
64-Doors: Room #109<br />
on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Rails are 34" - 38" above stair nosing. 12"<br />
minimum level extension beyond top nosing<br />
(parallel with the ground or floor surface) before<br />
being returned. 12" plus one tread width level<br />
extension beyond bottom nosing (parallel with<br />
the ground or floor surface) before being<br />
returned.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Raise existing handrail height. 2 $16,280.55<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
66-Signage: Room #109<br />
on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
68-Sinks: Room #109 on<br />
the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Knee clearance under sink is a minimum of 27"<br />
high and 30" wide, and provides an absolute<br />
depth of 19" underneath the sink [ADAAG 606.2<br />
Exception 6 The dip of the overflow shall not be<br />
considered in determining knee and toe<br />
clearance].<br />
Insulate pipes under sink. Cut<br />
the paneling under the sink<br />
counter to comply with knee<br />
clearance.<br />
3 $735.02<br />
6/1/2012 Page 8 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
69-Controls, Operating<br />
Mechanisms & Vending<br />
Machines.: Room #109<br />
on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Paper<br />
towel dispenser.]<br />
Forward Reach to Objects: Highest operable<br />
part of object is a maximum of 48" above the<br />
floor surface.<br />
Relocate existing paper towel<br />
dispenser.<br />
3 $122.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
73-Doors: Room #104<br />
on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
74-Clear Space at<br />
Doors: Room #104 on<br />
the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Minimum strike side clearance on PULL side of<br />
door: 18" wide x 60" depth at interior doors, front<br />
approach. Minimum strike side clearance on<br />
PUSH side of door: 12" front approach with latch<br />
and closer.<br />
Relocate furniture to provide<br />
clear space. University staff<br />
shall be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces. Modify<br />
door to swing opposite hand.<br />
2 $551.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
75-Signage: Room #104<br />
on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
77-Sinks: Room #105 on<br />
the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Minimum 30" x 48" clear space is provided in<br />
front of sink that allows forward approach. Sink<br />
is a maximum of 6-1/2" deep. Knee clearance<br />
under sink is a minimum of 27" high and 30"<br />
wide, and provides an absolute depth of 19"<br />
underneath the sink [ADAAG 606.2 Exception 6<br />
The dip of the overflow shall not be considered<br />
in determining knee and toe clearance]. Drain<br />
and hot water piping is insulated or configured to<br />
prevent contact.<br />
Replace with accessible sink.<br />
Insulate pipes under sink. Cut<br />
the paneling under the sink<br />
counter to comply with knee<br />
clearance.<br />
3 $3,920.09<br />
6/1/2012 Page 9 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
79-Controls, Operating<br />
Mechanisms & Vending<br />
Machines.: Room #105<br />
on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
[Thermogravimetric<br />
analyzer.]<br />
81-Seating, Tables and<br />
Work Surfaces: Room<br />
#105 on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />
hood.]<br />
Forward Reach to Objects: Highest operable<br />
part of object is a maximum of 48" above the<br />
floor surface.<br />
27" high, 30" wide and 19" deep knee clearance<br />
provided. 28" - 34" height of table or work<br />
surface that is 36" wide.<br />
Lower the machine. 1M $61.25<br />
Replace the fume hood with an<br />
accessible fume hood<br />
workstation.<br />
3 $18,216.00 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
82-Protruding Objects:<br />
Room #105 on the 1st<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Fume hood.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
83-Aisles: Room #105<br />
on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
36" minimum width of aisles. Requires<br />
engineering/architectural<br />
evaluation.<br />
2 $7,115.62<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
84-Protruding Objects:<br />
Room #105 on the 1st<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Emergency eye wash.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $122.51<br />
6/1/2012 Page 10 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
85-Doors: Room #105<br />
and Room #106 on the<br />
1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. [Three doors.]<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $612.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
87-Signage: Room #105<br />
and Room #106 on the<br />
1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
88-Doors: North<br />
Stairwell on the 1st Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
32" minimum clear width of doorway. 5 lb.<br />
maximum pressure to operate interior doors.<br />
Relocate existing signage. 3 $490.00<br />
Adjust door opening pressure /<br />
closing time unless accepted<br />
by DSA Fire / Life Safety.<br />
Consider issues connected<br />
with building pressure / climate<br />
control. Replace door and<br />
frame (concrete or block wall).<br />
2 $5,573.87<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
90-Signage: North<br />
Stairwell on the 1st Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>.<br />
91-Tactile Exit Signage:<br />
North Stairwell on the<br />
1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
92-Doors: Stairwell to<br />
Outside on the 1st Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>. [Exit<br />
only door.]<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each exit door that leads directly to a gradelevel<br />
exterior exit by means of a stairway or<br />
ramp is identified by a tactile exit sign that states<br />
"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />
"EXIT STAIR UP", or "EXIT RAMP UP", as<br />
appropriate.<br />
5 lb. maximum pressure to operate exterior<br />
doors.<br />
Install permanent ID sign to<br />
latch side of door.<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
95-Stairway Handrails:<br />
North Stairwell on the<br />
1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Rails are 34" - 38" above stair nosing. 12"<br />
minimum level extension beyond top nosing<br />
(parallel with the ground or floor surface) before<br />
being returned. 12" plus one tread width level<br />
extension beyond bottom nosing (parallel with<br />
the ground or floor surface) before being<br />
returned.<br />
Raise existing handrail height. 2 $5,879.79<br />
6/1/2012 Page 11 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
97-Hazards: North<br />
Stairwell on the 1st Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>.<br />
98-Doors: North<br />
Entrance on the 1st<br />
Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
[One set of double<br />
doors.]<br />
Any obstrution that overhangs a pedestrian way<br />
is a minimum 80" above the walking surface<br />
(measured from the bottom of the obstruction).<br />
Sidewalks are clear of hazards. If vertical<br />
clearance of an area adjoining an accessible<br />
route is reduced to less than 80", a barrier to<br />
warn blind or visually impaired persons is<br />
provided.<br />
5 lb. maximum pressure to operate exterior<br />
doors.<br />
Install cane detectable barrier<br />
below stairwell.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
1 $980.02<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
100-Signage: North<br />
Entrance on the 1st<br />
Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
101-Tactile Exit<br />
Signage: North Entrance<br />
on the 1st Floor to<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
102-Doors: West<br />
Entrance on the 2nd<br />
Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
[One set of double<br />
doors.]<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each grade-level exterior exit door shall be<br />
identified by a tactile sign with the word "EXIT".<br />
5 lb. maximum pressure to operate exterior<br />
doors.<br />
Install permanent ID sign to<br />
latch side of door.<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
104-Signage: West<br />
Entrance on the 2nd<br />
Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
105-Tactile Exit<br />
Signage: West Entrance<br />
on the 2nd Floor to<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each exit door that leads directly to a gradelevel<br />
exterior exit by means of a stairway or<br />
ramp is identified by a tactile exit sign that states<br />
"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />
"EXIT STAIR UP", or "EXIT RAMP UP", as<br />
appropriate.<br />
Install permanent ID sign to<br />
latch side of door.<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
6/1/2012 Page 12 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
106-Doors: Unisex<br />
Restroom to the Left on<br />
the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
108-Identification<br />
Symbols, Restrooms:<br />
Unisex Restroom to the<br />
Left on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Unisex - 12" diameter circle 1/4" thick with 1/4"<br />
thick triangle superimposed in the circle. The<br />
circle and triangle symbols contrasts with the<br />
door, light on dark background or dark on light<br />
background [CBC 1115B.6 The triangle shall<br />
contrast w the circle and the circle shall contrast<br />
with the door]. Wall mounted signage: Symbol of<br />
accessibility is mounted on wall sign adjacent to<br />
latch side of door [ADAAG 703.6.1 & CBC<br />
1117B.5.5 Item 4 Pictograms shall have a field<br />
height of 6" ADAAG 703.6.1 Characters and<br />
Braille shall not be located in the pictogram<br />
field]. Verbal description as to restroom usage is<br />
placed directly below the pictogram, if utilized in<br />
conjunction with verbal identification and the<br />
border dimensions of this pictogram is a<br />
minimum of 6" in height.<br />
Install door-mounted sign on<br />
single door. Install wallmounted<br />
sign at single<br />
entrance.<br />
3 $367.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
109-Single<br />
Accommodation Toilet:<br />
Unisex Restroom to the<br />
Left on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
110-Toilet Grab Bars:<br />
Unisex Restroom to the<br />
Left on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #109 for<br />
additional actions.]<br />
111-Lavatories: Unisex<br />
Restroom to the Left on<br />
the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
60" minimum diameter turning circle, or a T-<br />
shaped clear space, is provided in room with 12"<br />
maximum door encroachment into the required<br />
clear space. A minimum 60" wide and 48" deep<br />
clear floor space is provided in front of water<br />
closet. Front of toilet paper dispenser is within<br />
36" of the back wall.<br />
The front of the side grab bar extends 54" from<br />
back wall in single accommodation stall. Area<br />
directly above grab bars or proposed grab bars<br />
is free of protruding obstructions to a height of<br />
18" (recessed items are allowed).<br />
18" minimum from center of fixture to side wall<br />
or partition. 34" max. height to rim or counter<br />
above floor surface.<br />
Requires<br />
engineering/architectural<br />
evaluation. Relocate the toilet<br />
paper dispenser away from the<br />
top of the grab bar.<br />
Relocate side grab bar.<br />
Relocate the seat cover<br />
dispenser away from the top of<br />
the grab bar.<br />
Replace with accessible<br />
lavatory.<br />
3 $7,238.13<br />
3 $367.51<br />
3 $3,185.07<br />
6/1/2012 Page 13 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
112-Accessories: Unisex<br />
Restroom to the Left on<br />
the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. [See Sequence<br />
#109 and #110 for<br />
additional actions.]<br />
40" max. height to all other fixtures (i.e., soap<br />
dispensers, towels, toilet seat covers, auto<br />
dryers, sanitary napkins, waste recepatacles,<br />
etc.). Coat hooks and shelving are located within<br />
appropriate reach ranges (48" max. height<br />
above floor surface is recommended).<br />
Install accessible coat hook.<br />
Lower the soap dispenser.<br />
Lower the paper towel<br />
dispenser.<br />
3 $367.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
113-Doors: Unisex<br />
Restroom to the Right<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
115-Identification<br />
Symbols, Restrooms:<br />
Unisex Restroom to the<br />
Right on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Unisex - 12" diameter circle 1/4" thick with 1/4"<br />
thick triangle superimposed in the circle. The<br />
circle and triangle symbols contrasts with the<br />
door, light on dark background or dark on light<br />
background [CBC 1115B.6 The triangle shall<br />
contrast w the circle and the circle shall contrast<br />
with the door]. Wall mounted signage: Symbol of<br />
accessibility is mounted on wall sign adjacent to<br />
latch side of door [ADAAG 703.6.1 & CBC<br />
1117B.5.5 Item 4 Pictograms shall have a field<br />
height of 6" ADAAG 703.6.1 Characters and<br />
Braille shall not be located in the pictogram<br />
field]. Verbal description as to restroom usage is<br />
placed directly below the pictogram, if utilized in<br />
conjunction with verbal identification and the<br />
border dimensions of this pictogram is a<br />
minimum of 6" in height.<br />
Install door-mounted sign on<br />
single door. Install wallmounted<br />
sign at single<br />
entrance.<br />
3 $367.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
116-Single<br />
Accommodation Toilet:<br />
Unisex Restroom to the<br />
Right on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
60" minimum diameter turning circle, or a T-<br />
shaped clear space, is provided in room with 12"<br />
maximum door encroachment into the required<br />
clear space. A minimum 60" wide and 48" deep<br />
clear floor space is provided in front of water<br />
closet. Front of toilet paper dispenser is within<br />
36" of the back wall. The toilet paper dispenser<br />
is located on the side wall below the grab bar<br />
and within 7" - 9" of the front of the toilet seat as<br />
measured to the centerline of the dispenser.<br />
Requires<br />
engineering/architectural<br />
evaluation. Relocate the toilet<br />
paper dispenser away from the<br />
top of the grab bar.<br />
3 $7,238.13<br />
6/1/2012 Page 14 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
117-Toilet Grab Bars:<br />
Unisex Restroom to the<br />
Right on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #116 for<br />
additional actions.]<br />
118-Lavatories: Unisex<br />
Restroom to the Right<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
119-Accessories: Unisex<br />
Restroom to the Right<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #116 and<br />
#117 for additional<br />
actions. Soap dispenser -<br />
44-12" / paper towel<br />
dispenser - 45" / seat<br />
cover dispenser - 48" /<br />
toilet paper dispenser -<br />
43".]<br />
120-Water Fountains<br />
(Drinking): 2nd Floor<br />
Corridor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
128-Signage: Fire Door<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
129-Doors: Room #204<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
The front of the side grab bar extends 54" from<br />
back wall in single accommodation stall. Area<br />
directly above grab bars or proposed grab bars<br />
is free of protruding obstructions to a height of<br />
18" (recessed items are allowed).<br />
18" minimum from center of fixture to side wall<br />
or partition.<br />
40" max. height to all other fixtures (i.e., soap<br />
dispensers, towels, toilet seat covers, auto<br />
dryers, sanitary napkins, waste recepatacles,<br />
etc.). Coat hooks and shelving are located within<br />
appropriate reach ranges (48" max. height<br />
above floor surface is recommended).<br />
Stream of bubbler is parallel to front edge. The<br />
force required to activate controls does not<br />
exceed 5lbf.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Relocate side grab bar. 3 $245.01<br />
Replace with accessible<br />
lavatory.<br />
Install accessible coat hook.<br />
Lower the soap dispenser.<br />
Lower the paper towel<br />
dispenser.<br />
Adjust water pressure of<br />
existing fountain. Adjust angle<br />
of stream.<br />
Install permanent ID sign to<br />
latch side of door.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
3 $3,185.07<br />
3 $367.51<br />
2 $673.76<br />
1 $183.75<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
131-Signage: Room<br />
#204 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $245.01<br />
6/1/2012 Page 15 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
134-Clear Space at<br />
Doors: Behind Room<br />
#204 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
135-Signage: Behind<br />
Room #204 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
136-Sales and Service<br />
Counters: Room #205<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
137-Sinks: Room #205<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Minimum strike side clearance on PULL side of Relocate furniture to provide<br />
door: 18" wide x 60" depth at interior doors, front clear space. University staff shall<br />
approach. Minimum strike side clearance on be instructed to place and<br />
PUSH side of door: 12" front approach with latch maintain the placement of<br />
and closer.<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Knee space at table(s) is at least 27" high, 30"<br />
wide and extends 19" under the table(s) and;<br />
Minimum 30" x 48" clear space is provided in<br />
front of sink that allows forward approach. 34"<br />
maximum height of rim or counter above floor<br />
surfaces. Knee clearance under sink is a<br />
minimum of 27" high and 30" wide, and provides<br />
an absolute depth of 19" underneath the sink<br />
[ADAAG 606.2 Exception 6 The dip of the<br />
overflow shall not be considered in determining<br />
knee and toe clearance]. Drain and hot water<br />
piping is insulated or configured to prevent<br />
contact.<br />
Install permanent ID sign to<br />
latch side of door.<br />
Cut skirt on the counter to<br />
comply with knee clearance.<br />
Replace with accessible sink.<br />
Insulate pipes under sink. Cut<br />
the paneling under the sink<br />
counter to comply with knee<br />
clearance.<br />
1M $122.51<br />
1 $183.75<br />
2 $490.00<br />
3 $3,920.09<br />
6/1/2012 Page 16 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
140-Seating, Tables and<br />
Work Surfaces: Room<br />
#205 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />
hood. Relocate the<br />
flammable box.]<br />
27" high, 30" wide and 19" deep knee clearance<br />
provided.<br />
Replace the fume hood with an<br />
accessible fume hood<br />
workstation.Relocate furniture<br />
to provide clear space.<br />
University staff shall be<br />
instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
3 $18,277.25 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
141-Protruding Objects:<br />
Room #205 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Fume hood.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
142-Protruding Objects:<br />
Room #205 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Emergency eyewash.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $122.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
143-Aisles: Room #205<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
36" minimum width of aisles. Requires<br />
engineering/architectural<br />
evaluation.<br />
2 $7,115.62<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
144-Doors: Rooms #205<br />
and #206 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Three doors.]<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $612.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
146-Signage: Rooms<br />
#205 and #206 on the<br />
2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $490.00<br />
6/1/2012 Page 17 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
147-Doors: Room #207<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
148-Clear Space at<br />
Doors: Room #207 on<br />
the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
149-Signage: Room<br />
#207 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Minimum strike side clearance on PUSH side of<br />
door: 12" front approach with latch and closer.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate furniture to provide<br />
clear space. University staff shall<br />
be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
1M $61.25<br />
Relocate existing signage. 3 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
151-Sinks: Room #206<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Minimum 30" x 48" clear space is provided in<br />
front of sink that allows forward approach. Sink<br />
is a maximum of 6-1/2" deep. Knee clearance<br />
under sink is a minimum of 27" high and 30"<br />
wide, and provides an absolute depth of 19"<br />
underneath the sink [ADAAG 606.2 Exception 6<br />
The dip of the overflow shall not be considered<br />
in determining knee and toe clearance]. Drain<br />
and hot water piping is insulated or configured to<br />
prevent contact.<br />
Replace with accessible sink.<br />
Insulate pipes under sink. Cut<br />
the paneling under the sink<br />
counter to comply with knee<br />
clearance.<br />
3 $3,920.09<br />
6/1/2012 Page 18 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
155-Seating, Tables and<br />
Work Surfaces: Room<br />
#206 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />
hood.]<br />
28" - 34" height of table or work surface that is<br />
36" wide.<br />
Replace the fume hood with an<br />
accessible fume hood<br />
workstation.<br />
3 $18,216.00 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
156-Protruding Objects:<br />
Room #206 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Fume hood.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $245.01<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
157-Aisles: Room #206<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
36" minimum width of aisles. Requires<br />
engineering/architectural<br />
evaluation.<br />
2 $7,115.62<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
158-Protruding Objects:<br />
Room #206 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Emergency eye wash.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $122.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
160-Doors: Rooms #222<br />
and #219 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Two doors.]<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $612.51<br />
6/1/2012 Page 19 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
161-Clear Space at<br />
Doors: Rooms #222 and<br />
#219 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
162-Signage: Rooms<br />
#222 and #219 on the<br />
2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
164-Sinks: Rooms #222<br />
and #219 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Minimum strike side clearance on PUSH side of<br />
door: 12" front approach with latch and closer.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Minimum 30" x 48" clear space is provided in<br />
front of sink that allows forward approach. Sink<br />
is a maximum of 6-1/2" deep. Knee clearance<br />
under sink is a minimum of 27" high and 30"<br />
wide, and provides an absolute depth of 19"<br />
underneath the sink [ADAAG 606.2 Exception 6<br />
The dip of the overflow shall not be considered<br />
in determining knee and toe clearance]. Drain<br />
and hot water piping is insulated or configured to<br />
prevent contact.<br />
Relocate furniture to provide<br />
clear space. University staff shall<br />
be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
1M $122.51<br />
Relocate existing signage. 3 $490.00<br />
Replace with accessible sink.<br />
Insulate pipes under sink. Cut<br />
the paneling under the sink<br />
counter to comply with knee<br />
clearance.<br />
3 $7,840.16<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
166-Controls, Operating<br />
Mechanisms & Vending<br />
Machines.: Rooms #222<br />
and #219 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Various machines.]<br />
Forward Reach to Objects: Highest operable<br />
part of object is a maximum of 48" above the<br />
floor surface.<br />
Relocate existing paper towel<br />
dispenser. Lower the machine.<br />
3 $183.75<br />
6/1/2012 Page 20 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
168-Seating, Tables and<br />
Work Surfaces: Rooms<br />
#222 and #219 on the<br />
2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. [Fume hood.]<br />
28" - 34" height of table or work surface that is<br />
36" wide.<br />
Replace the fume hood with an<br />
accessible fume hood<br />
workstation.<br />
3 $18,216.00 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
170-Aisles: Rooms #222<br />
and #219 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
36" minimum width of aisles. Requires<br />
engineering/architectural<br />
evaluation.<br />
2 $7,115.62<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
171-Protruding Objects:<br />
Rooms #222 and #219<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
[Emergency eyewash.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
1 $122.51<br />
6/1/2012 Page 21 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
172-Seating, Tables and<br />
Work Surfaces: Rooms<br />
#222 and #219 on the<br />
2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
30" x 48" min. clear floor space is provided. 27"<br />
high, 30" wide and 19" deep knee clearance<br />
provided.<br />
Provide accessible table. 1M $245.01 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
173-Doors: Rooms #218<br />
and #221 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Three doors.]<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $612.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
175-Signage: Rooms<br />
#218 and #221 on the<br />
2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
177-Clear Space at<br />
Doors: Rooms #202,<br />
#203, #225 and #224 on<br />
the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. [Four office<br />
doors.]<br />
178-Signage: Rooms<br />
#202, #203, #225 and<br />
#224 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Four<br />
office doors.]<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
60" min. clear space in direction of door swing.<br />
Minimum strike side clearance on PULL side of<br />
door: 18" wide x 60" depth at interior doors, front<br />
approach.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $490.00<br />
Relocate furniture to provide<br />
clear space. University staff shall<br />
be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
1M $245.01<br />
Relocate existing signage. 3 $980.02<br />
6/1/2012 Page 22 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
179-Doors: North<br />
Stairwell on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
32" minimum clear width of doorway. 5 lb.<br />
maximum pressure to operate interior doors.<br />
Adjust door opening pressure<br />
/ closing time unless accepted<br />
by DSA Fire / Life Safety.<br />
Consider issues connected<br />
with building pressure / climate<br />
control. Replace door and<br />
frame (concrete or block wall).<br />
2 $5,573.87<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
181-Signage: North<br />
Stairwell on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
182-Tactile Exit<br />
Signage: North Stairwell<br />
on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
183-Doors: North<br />
Entrance to <strong>Pierce</strong><br />
<strong>Annex</strong> on the 2nd Floor.<br />
[One set of double<br />
doors.]<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each exit door that leads directly to a gradelevel<br />
exterior exit by means of a stairway or<br />
ramp is identified by a tactile exit sign that states<br />
"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />
"EXIT STAIR UP", or "EXIT RAMP UP", as<br />
appropriate.<br />
5 lb. maximum pressure to operate exterior<br />
doors.<br />
Install permanent ID sign to<br />
latch side of door.<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
185-Signage: North<br />
Entrance to <strong>Pierce</strong><br />
<strong>Annex</strong> on the 2nd Floor.<br />
186-Tactile Exit<br />
Signage: North Entrance<br />
to <strong>Pierce</strong> <strong>Annex</strong> on the<br />
2nd Floor.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each grade-level exterior exit door shall be<br />
identified by a tactile sign with the word "EXIT".<br />
Install permanent ID sign to<br />
latch side of door.<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
6/1/2012 Page 23 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
187-Doors: West<br />
Entrance to <strong>Pierce</strong><br />
<strong>Annex</strong> on the 3rd Floor.<br />
[One set of double<br />
doors.]<br />
189-Signage: West<br />
Entrance to <strong>Pierce</strong><br />
<strong>Annex</strong> on the 3rd Floor.<br />
190-Tactile Exit<br />
Signage: West Entrance<br />
to <strong>Pierce</strong> <strong>Annex</strong> on the<br />
3rd Floor.<br />
191-Doors: Unisex<br />
Restroom on the Left on<br />
the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
193-Identification<br />
Symbols, Restrooms:<br />
Unisex Restroom on the<br />
Left on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
5 lb. maximum pressure to operate exterior<br />
doors. 3 seconds minimum for door closer to<br />
close from 70 degree position to within 3" of the<br />
latch [ADAAG 404.2.8.1 Door & gate closers<br />
require a 5 second minimum closing time from<br />
open position of 90 degree to 12 degree<br />
position].<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each exit door that leads directly to a gradelevel<br />
exterior exit by means of a stairway or<br />
ramp is identified by a tactile exit sign that states<br />
"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />
"EXIT STAIR UP", or "EXIT RAMP UP", as<br />
appropriate.<br />
5 lb. maximum pressure to operate interior<br />
doors. 3 seconds minimum for door closer to<br />
close from 70 degree position to within 3" of the<br />
latch [ADAAG 404.2.8.1 Door & gate closers<br />
require a 5 second minimum closing time from<br />
open position of 90 degree to 12 degree<br />
position].<br />
Unisex - 12" diameter circle 1/4" thick with 1/4"<br />
thick triangle superimposed in the circle. The<br />
circle and triangle symbols contrasts with the<br />
door, light on dark background or dark on light<br />
background [CBC 1115B.6 The triangle shall<br />
contrast w the circle and the circle shall contrast<br />
with the door]. Wall mounted signage: Symbol of<br />
accessibility is mounted on wall sign adjacent to<br />
latch side of door [ADAAG 703.6.1 & CBC<br />
1117B.5.5 Item 4 Pictograms shall have a field<br />
height of 6" ADAAG 703.6.1 Characters and<br />
Braille shall not be located in the pictogram<br />
field]. Verbal description as to restroom usage is<br />
placed directly below the pictogram, if utilized in<br />
conjunction with verbal identification and the<br />
border dimensions of this pictogram is a<br />
minimum of 6" in height.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
Install permanent ID sign to<br />
latch side of door.<br />
2 $306.26<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
Install door-mounted sign on<br />
single door. Install wallmounted<br />
sign at single<br />
entrance.<br />
2 $306.26<br />
3 $367.51<br />
6/1/2012 Page 24 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
194-Single<br />
Accommodation Toilet:<br />
Unisex Restroom on the<br />
Left on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
195-Toilet Grab Bars:<br />
Unisex Restroom on the<br />
Left on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #194 for<br />
additional actions.]<br />
196-Lavatories: Unisex<br />
Restroom on the Left on<br />
the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
197-Accessories: Unisex<br />
Restroom on the Left on<br />
the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. [See Sequence<br />
#194 and #195 for<br />
additional actions. Soap<br />
dispenser - 43" / paper<br />
towel dispenser - 45" /<br />
seat cover dispenser -<br />
48" / toilet paper<br />
dispenser - 42-1/4". ]<br />
60" minimum diameter turning circle, or a T-<br />
shaped clear space, is provided in room with 12"<br />
maximum door encroachment into the required<br />
clear space. Front of toilet paper dispenser is<br />
within 36" of the back wall. The toilet paper<br />
dispenser is located on the side wall below the<br />
grab bar and within 7" - 9" of the front of the<br />
toilet seat as measured to the centerline of the<br />
dispenser.<br />
The front of the side grab bar extends 54" from<br />
back wall in single accommodation stall. Area<br />
directly above grab bars or proposed grab bars<br />
is free of protruding obstructions to a height of<br />
18" (recessed items are allowed).<br />
18" minimum from center of fixture to side wall<br />
or partition. 34" max. height to rim or counter<br />
above floor surface.<br />
40" max. height to all other fixtures (i.e., soap<br />
dispensers, towels, toilet seat covers, auto<br />
dryers, sanitary napkins, waste recepatacles,<br />
etc.). Coat hooks and shelving are located within<br />
appropriate reach ranges (48" max. height<br />
above floor surface is recommended).<br />
Requires<br />
engineering/architectural<br />
evaluation. Relocate the toilet<br />
paper dispenser away from the<br />
top of the grab bar.<br />
Relocate side grab bar.<br />
Relocate the seat cover<br />
dispenser away from the top of<br />
the grab bar.<br />
Replace with accessible<br />
lavatory.<br />
Install accessible coat hook.<br />
Lower the soap dispenser.<br />
Lower the paper towel<br />
dispenser.<br />
3 $7,238.13<br />
3 $367.51<br />
3 $3,185.07<br />
3 $367.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
198-Doors: Unisex<br />
Restroom on the Right<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
6/1/2012 Page 25 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
200-Identification<br />
Symbols, Restrooms:<br />
Unisex Restroom on the<br />
Right on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Unisex - 12" diameter circle 1/4" thick with 1/4"<br />
thick triangle superimposed in the circle. The<br />
circle and triangle symbols contrasts with the<br />
door, light on dark background or dark on light<br />
background [CBC 1115B.6 The triangle shall<br />
contrast w the circle and the circle shall contrast<br />
with the door]. Wall mounted signage: Symbol of<br />
accessibility is mounted on wall sign adjacent to<br />
latch side of door [ADAAG 703.6.1 & CBC<br />
1117B.5.5 Item 4 Pictograms shall have a field<br />
height of 6" ADAAG 703.6.1 Characters and<br />
Braille shall not be located in the pictogram<br />
field]. Verbal description as to restroom usage is<br />
placed directly below the pictogram, if utilized in<br />
conjunction with verbal identification and the<br />
border dimensions of this pictogram is a<br />
minimum of 6" in height.<br />
Install door-mounted sign on<br />
single door. Install wallmounted<br />
sign at single<br />
entrance.<br />
3 $367.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
201-Single<br />
Accommodation Toilet:<br />
Unisex Restroom on the<br />
Right on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
60" minimum diameter turning circle, or a T-<br />
shaped clear space, is provided in room with 12"<br />
maximum door encroachment into the required<br />
clear space. A minimum 60" wide and 48" deep<br />
clear floor space is provided in front of water<br />
closet. Front of toilet paper dispenser is within<br />
36" of the back wall. The toilet paper dispenser<br />
is located on the side wall below the grab bar<br />
and within 7" - 9" of the front of the toilet seat as<br />
measured to the centerline of the dispenser.<br />
Requires<br />
engineering/architectural<br />
evaluation. Relocate the toilet<br />
paper dispenser away from the<br />
top of the grab bar.<br />
3 $7,238.13<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
202-Toilet Grab Bars:<br />
Unisex Restroom on the<br />
Right on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #201 for<br />
additional actions.]<br />
203-Lavatories: Unisex<br />
Restroom on the Right<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
The front of the side grab bar extends 54" from<br />
back wall in single accommodation stall. Area<br />
directly above grab bars or proposed grab bars<br />
is free of protruding obstructions to a height of<br />
18" (recessed items are allowed).<br />
18" minimum from center of fixture to side wall<br />
or partition.<br />
Relocate side grab bar.<br />
Relocate the seat cover<br />
dispenser away from the top of<br />
the grab bar.<br />
Replace with accessible<br />
lavatory.<br />
3 $367.51<br />
3 $3,185.07<br />
6/1/2012 Page 26 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
204-Accessories: Unisex<br />
Restroom on the Right<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [See<br />
Sequence #201 and<br />
#202 for additional<br />
actions.]<br />
207-Water Fountains<br />
(Drinking): Corridor on<br />
the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
211-Signage: Fire Doors<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
212-Doors: Rooms #321<br />
and #318 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
40" max. height to all other fixtures (i.e., soap<br />
dispensers, towels, toilet seat covers, auto<br />
dryers, sanitary napkins, waste recepatacles,<br />
etc.). Coat hooks and shelving are located within<br />
appropriate reach ranges (48" max. height<br />
above floor surface is recommended).<br />
Stream of bubbler is parallel to front edge. The<br />
force required to activate controls does not<br />
exceed 5lbf.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Install accessible coat hook.<br />
Lower the paper towel<br />
dispenser. Lower the soap<br />
dispenser.<br />
Adjust angle of stream.<br />
Reduce force needed to<br />
operate fountain controls ( 5 lb.<br />
maximum).<br />
Install permanent ID sign to<br />
latch side of door.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
3 $367.51<br />
2 $551.26<br />
1 $183.75<br />
2 $612.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
214-Signage: Rooms<br />
#321 and #318 on the<br />
3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Relocate existing signage. 3 $490.00<br />
6/1/2012 Page 27 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
220-Seating, Tables and<br />
Work Surfaces: Rooms<br />
#321 and #318 on the<br />
3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. [Fume hood.]<br />
28" - 34" height of table or work surface that is<br />
36" wide.<br />
Replace the fume hood with an<br />
accessible fume hood<br />
workstation.<br />
3 $18,216.00 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
221-Protruding Objects:<br />
Rooms #321 and #318<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Eight<br />
fume hoods.]<br />
222-Protruding Objects:<br />
Rooms #321 and #318<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Two<br />
emergency eyewash<br />
controls.]<br />
223-Aisles: Rooms #321<br />
and #318 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
Install cane detectable barrier<br />
below object.<br />
36" minimum width of aisles. Requires<br />
engineering/architectural<br />
evaluation.<br />
1 $980.02<br />
1 $245.01<br />
2 $7,115.62<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
224-Floors and Levels:<br />
Rooms #321 and #318<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Four<br />
carpets / mats.]<br />
225-Protruding Objects:<br />
Rooms #321 and #318<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Shelf on<br />
machine.]<br />
Carpets or carpet tiles are securely attached<br />
and do not exceed 1/2" in height. Carpet's<br />
exposed edges are fastened to floor surfaces<br />
and have trim along entire length.<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Secure loose doormat. 1 $980.02<br />
Install cane detectable barrier<br />
below object.<br />
1 $245.01<br />
6/1/2012 Page 28 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
226-Doors: Rooms #319<br />
and #317 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Three doors.]<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $612.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
228-Signage: Rooms<br />
#319 and #317 on the<br />
3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
229-Doors: Rooms #307<br />
and #304 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Relocate existing signage. 3 $490.00<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $612.51<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
231-Signage: Rooms<br />
#307 and #304 on the<br />
3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
233-Sinks: Rooms #307<br />
and #304 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
Sink is a maximum of 6-1/2" deep. Knee<br />
clearance under sink is a minimum of 27" high<br />
and 30" wide, and provides an absolute depth of<br />
19" underneath the sink [ADAAG 606.2<br />
Exception 6 The dip of the overflow shall not be<br />
considered in determining knee and toe<br />
clearance]. Drain and hot water piping is<br />
insulated or configured to prevent contact.<br />
Relocate existing signage. 3 $490.00<br />
Replace with accessible sink.<br />
Insulate pipes under sink.<br />
3 $3,430.07<br />
6/1/2012 Page 29 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
237-Seating, Tables and<br />
Work Surfaces: Rooms<br />
#307 and #304 on the<br />
3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. [Fume hood.]<br />
27" high, 30" wide and 19" deep knee clearance<br />
provided. 28" - 34" height of table or work<br />
surface that is 36" wide.<br />
Replace the fume hood with an<br />
accessible fume hood<br />
workstation.<br />
3 $18,216.00 Until such time<br />
as accessible<br />
furniture /<br />
stations are<br />
available in this<br />
room staff shall<br />
be informed of<br />
the immediate<br />
availability of<br />
accessible<br />
furniture /<br />
stations that<br />
may be placed<br />
in the room to<br />
meet the needs<br />
of people with<br />
disabilities.<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
238-Protruding Objects:<br />
Rooms #307 and #304<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />
hood.]<br />
239-Protruding Objects:<br />
Rooms #307 and #304<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Two<br />
eyewash controls.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
Install cane detectable barrier<br />
below object.<br />
Install cane detectable barrier<br />
below object.<br />
1 $980.02<br />
1 $490.00<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
240-Aisles: Rooms #307<br />
and #304 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
36" minimum width of aisles. Requires<br />
engineering/architectural<br />
evaluation.<br />
2 $7,115.62<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
241-Protruding Objects:<br />
Rooms #307 and #304<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. [Shelf on<br />
machine.]<br />
242-Doors: Rooms #306<br />
and #305 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[Three doors.]<br />
Objects projecting from walls (i.e. telephones,<br />
etc.) have 4" maximum projection into walks,<br />
halls, corridors, passageways or aisles if lower<br />
edge of object is above 27" and below 80".<br />
5 lb. maximum pressure to operate interior<br />
doors.<br />
Install cane detectable barrier<br />
below object.<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
1 $245.01<br />
2 $612.51<br />
6/1/2012 Page 30 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
244-Signage: Rooms<br />
#306 and #305 on the<br />
3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
246-Clear Space at<br />
Doors: Rooms #323,<br />
#324, #303 and #302 on<br />
the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
247-Signage: Rooms<br />
#323, #324, #303 and<br />
#302 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
248-Doors: North<br />
Stairwell on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
250-Signage: North<br />
Stairwell on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
251-Tactile Exit<br />
Signage: North Stairwell<br />
on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
252-Doors: North<br />
Entrance on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
60" min. clear space in direction of door swing.<br />
Minimum strike side clearance on PULL side of<br />
door: 18" wide x 60" depth at interior doors, front<br />
approach.<br />
Mounting height is 60" from the finish floor to the<br />
centerline of the sign.<br />
32" minimum clear width of doorway. 5 lb.<br />
maximum pressure to operate interior doors.<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Each exit door that leads directly to a gradelevel<br />
exterior exit by means of a stairway or<br />
ramp is identified by a tactile exit sign that states<br />
"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />
"EXIT STAIR UP", or "EXIT RAMP UP", as<br />
appropriate.<br />
5 lb. maximum pressure to operate exterior<br />
doors.<br />
Relocate existing signage. 3 $490.00<br />
Relocate furniture to provide<br />
clear space. University staff shall<br />
be instructed to place and<br />
maintain the placement of<br />
furniture to provide a clear path<br />
of travel and avoid the<br />
obstruction of accessible<br />
required clear spaces.<br />
1M $245.01<br />
Relocate existing signage. 3 $980.02<br />
Adjust door opening pressure /<br />
closing time unless accepted<br />
by DSA Fire / Life Safety.<br />
Consider issues connected<br />
with building pressure / climate<br />
control. Replace door and<br />
frame (concrete or block wall).<br />
Install permanent ID sign to<br />
latch side of door.<br />
2 $5,573.87<br />
1 $183.75<br />
Provide compliant sign. 1 $183.75<br />
Adjust door opening pressure /<br />
closing time unless accepted by<br />
DSA Fire / Life Safety. Consider<br />
issues connected with building<br />
pressure / climate control.<br />
2 $306.26<br />
6/1/2012 Page 31 of 32
Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />
Report<br />
Name<br />
Item/Location<br />
Barrier<br />
(noted feature, item or area does not meet the<br />
new construction criteria detailed below)<br />
Action Priority Target<br />
Date<br />
Estimated<br />
Cost<br />
Interim<br />
Solution<br />
Action<br />
Completion<br />
Date<br />
UCR P5508<br />
<strong>Pierce</strong><br />
<strong>Annex</strong><br />
254-Signage: North<br />
Entrance on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
[No signage.]<br />
Permanent I.D. signs, when provided, are<br />
installed on the wall adjacent to the latch side of<br />
the door NOTE: At double leaf doors, and when<br />
there is no room on the latch side, signs shall be<br />
placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Install permanent ID sign to<br />
latch side of door.<br />
1 $183.75<br />
Grand Total $406,255.30<br />
6/1/2012 Page 32 of 32
Cost Report
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
2. Stairway Handrails - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Raise/Lower existing handrail height. 44 l.f. $88.00 $3,872.00 $4,259.20 $4,791.60 $5,510.34 $5,510.34<br />
Install top or bottom extensions to existing handrail. 6 ea. $103.30 $619.80 $681.78 $767.00 $882.05 $882.05<br />
TOTAL EST: $6,392.39<br />
4. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
6. Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
7. Tactile Exit Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
8. Floors and Levels - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Secure loose doormat. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
Page 1 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
9. Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $306.26<br />
11. Identification Symbols, Restrooms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $367.50<br />
12. Single Accommodation Toilet - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $7,238.13<br />
13. Toilet Grab Bars - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $367.52<br />
14. Lavatories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
TOTAL EST: $3,185.07<br />
Page 2 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
15. Accessories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $367.53<br />
16. Visual/Audible Alarms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 0<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
18. Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong> .<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $306.26<br />
20. Identification Symbols, Restrooms - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $367.50<br />
21. Single Accommodation Toilet - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $7,238.13<br />
Page 3 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
22. Toilet Grab Bars - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $367.52<br />
23. Lavatories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
TOTAL EST: $3,185.07<br />
24. Accessories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $245.02<br />
28. Water Fountains (Drinking) - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $551.27<br />
30. Visual/Audible Alarms - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 0<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
Page 4 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
33. Clear Space at Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 3 ea. $43.04 $129.12 $142.03 $159.78 $183.75 $183.75<br />
Modify, relocate, replace or remove restricting objects. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $428.76<br />
34. Signage - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate permanent ID sign to latch side of door. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
35. Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
36. Clear Space at Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />
TOTAL EST: $61.25<br />
37. Signage - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
Page 5 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
39. Clear Space at Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />
TOTAL EST: $61.25<br />
40. Sales and Service Counters - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install accessible counter. 1 ea. $1,119.04 $1,119.04 $1,230.94 $1,384.81 $1,592.53 $1,592.53<br />
TOTAL EST: $1,592.53<br />
41. Sinks - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />
knee clearance.<br />
TOTAL EST: $3,920.08<br />
44. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />
TOTAL EST: $18,216.00<br />
46. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
Page 6 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
47. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
48. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $122.51<br />
50. Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
52. Signage - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
54. Doors - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />
TOTAL EST: $5,573.87<br />
Page 7 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
56. Signage - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
57. Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
Repair door operation. 1 ea. $1,500.00 $1,500.00 $1,650.00 $1,856.25 $2,134.69 $2,134.69<br />
Provide a raised five pointed star at the ground level. 1 ea. $250.00 $250.00 $275.00 $309.38 $355.79 $355.79<br />
TOTAL EST: $9,606.10<br />
60. Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace door(s) and frame (stud wall). 1 ea. $2,203.65 $2,203.65 $2,424.02 $2,727.02 $3,136.07 $3,136.07<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
Post a sign/decal displaying the ”International Symbol of Accessibility”<br />
1 ea. $17.22 $17.22 $18.94 $21.31 $24.51 $24.51<br />
at the primary entrance.<br />
TOTAL EST: $3,466.84<br />
62. Stairways - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Remove/Replace existing stairways or steps. 30 riser $705.86 $21,175.80 $23,293.38 $26,205.05 $30,135.81 $30,135.81<br />
TOTAL EST: $30,135.81<br />
63. Stairway Handrails - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Raise/Lower existing handrail height. 130 l.f. $88.00 $11,440.00 $12,584.00 $14,157.00 $16,280.55 $16,280.55<br />
TOTAL EST: $16,280.55<br />
Page 8 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
64. Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
66. Signage - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
68. Sinks - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />
knee clearance.<br />
TOTAL EST: $735.01<br />
69. Controls, Operating Mechanisms & Vending Machines. - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing paper towel dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $122.51<br />
73. Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
Page 9 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
74. Clear Space at Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />
Modify door to swing opposite hand. 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $551.25<br />
75. Signage - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
77. Sinks - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />
knee clearance.<br />
TOTAL EST: $3,920.08<br />
79. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Lower the machine. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />
TOTAL EST: $61.25<br />
81. Seating, Tables and Work Surfaces - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />
TOTAL EST: $18,216.00<br />
Page 10 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
82. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
83. Aisles - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
84. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $122.51<br />
85. Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
87. Signage - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
Page 11 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
88. Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />
TOTAL EST: $5,573.87<br />
90. Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
91. Tactile Exit Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
92. Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $306.26<br />
95. Stairway Handrails - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Raise/Lower existing handrail height. 120 l.f. $34.43 $4,131.60 $4,544.76 $5,112.86 $5,879.79 $5,879.79<br />
TOTAL EST: $5,879.79<br />
Page 12 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
97. Hazards - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
98. Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
100. Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
101. Tactile Exit Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
102. Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
Page 13 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
104. Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
105. Tactile Exit Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
106. Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $306.26<br />
108. Identification Symbols, Restrooms - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $367.50<br />
109. Single Accommodation Toilet - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $7,238.13<br />
Page 14 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
110. Toilet Grab Bars - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $367.52<br />
111. Lavatories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
TOTAL EST: $3,185.07<br />
112. Accessories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $367.53<br />
113. Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $306.26<br />
115. Identification Symbols, Restrooms - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $367.50<br />
Page 15 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
116. Single Accommodation Toilet - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $7,238.13<br />
117. Toilet Grab Bars - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
118. Lavatories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
TOTAL EST: $3,185.07<br />
119. Accessories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $367.53<br />
120. Water Fountains (Drinking) - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust water pressure of existing fountain. 1 ea. $301.28 $301.28 $331.41 $372.84 $428.77 $428.77<br />
Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $673.78<br />
Page 16 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
128. Signage - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
129. Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
131. Signage - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
134. Clear Space at Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 2 ea. $43.04 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $122.51<br />
135. Signage - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
136. Sales and Service Counters - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Cut skirt on the counter to comply with knee clearance. 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
Page 17 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
137. Sinks - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />
knee clearance.<br />
TOTAL EST: $3,920.08<br />
140. Seating, Tables and Work Surfaces - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />
Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />
TOTAL EST: $18,277.25<br />
141. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
142. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $122.51<br />
143. Aisles - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
Page 18 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
144. Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
146. Signage - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
147. Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
148. Clear Space at Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />
TOTAL EST: $61.25<br />
149. Signage - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
Page 19 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
151. Sinks - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />
knee clearance.<br />
TOTAL EST: $3,920.08<br />
155. Seating, Tables and Work Surfaces - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />
TOTAL EST: $18,216.00<br />
156. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
157. Aisles - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
158. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $122.51<br />
Page 20 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
160. Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
161. Clear Space at Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 2 ea. $43.04 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $122.51<br />
162. Signage - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
164. Sinks - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible sink. 2 ea. $2,238.08 $4,476.16 $4,923.78 $5,539.25 $6,370.14 $6,370.14<br />
Insulate pipes under lavatory (or sink when applicable). 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
Cut the paneling under the lavatory/sink counter to comply with 2 ea. $344.32 $688.64 $757.50 $852.19 $980.02 $980.02<br />
knee clearance.<br />
TOTAL EST: $7,840.16<br />
166. Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing paper towel dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Lower the machine. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />
TOTAL EST: $183.76<br />
Page 21 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
168. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />
TOTAL EST: $18,216.00<br />
169. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
170. Aisles - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
171. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Modify, relocate, replace or remove restricting objects. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
172. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
173. Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
Page 22 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
175. Signage - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
177. Clear Space at Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 4 ea. $43.04 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
178. Signage - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
179. Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />
TOTAL EST: $5,573.87<br />
181. Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
Page 23 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
182. Tactile Exit Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
183. Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
185. Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
186. Tactile Exit Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
187. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
Page 24 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
189. Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
190. Tactile Exit Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
191. Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $306.26<br />
193. Identification Symbols, Restrooms - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $367.50<br />
194. Single Accommodation Toilet - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $7,238.13<br />
Page 25 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
195. Toilet Grab Bars - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $367.52<br />
196. Lavatories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
TOTAL EST: $3,185.07<br />
197. Accessories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $367.53<br />
198. Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $306.26<br />
200. Identification Symbols, Restrooms - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $367.50<br />
Page 26 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
201. Single Accommodation Toilet - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $7,238.13<br />
202. Toilet Grab Bars - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
bars or proposed grab bars.<br />
TOTAL EST: $367.52<br />
203. Lavatories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
TOTAL EST: $3,185.07<br />
204. Accessories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />
TOTAL EST: $367.53<br />
207. Water Fountains (Drinking) - Corridor on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $551.27<br />
Page 27 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
211. Signage - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
212. Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
214. Signage - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
220. Seating, Tables and Work Surfaces - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />
TOTAL EST: $18,216.00<br />
221. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
222. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
Page 28 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
223. Aisles - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
224. Floors and Levels - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Secure loose doormat. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
225. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
226. Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
228. Signage - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
Page 29 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
229. Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
231. Signage - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
233. Sinks - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />
Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $3,430.08<br />
237. Seating, Tables and Work Surfaces - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />
TOTAL EST: $18,216.00<br />
238. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
Page 30 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
239. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 4 l.f. $86.08 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
240. Aisles - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />
TOTAL EST: $7,115.62<br />
241. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 1<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
242. Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />
by DSA / Fire Life Safety.<br />
TOTAL EST: $612.51<br />
244. Signage - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />
TOTAL EST: $490.00<br />
246. Clear Space at Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate furniture to provide clear space. 4 ea. $43.04 $172.16 $189.38 $213.05 $245.01 $245.01<br />
TOTAL EST: $245.01<br />
Page 31 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
247. Signage - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Relocate existing signage. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />
TOTAL EST: $980.02<br />
248. Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />
TOTAL EST: $5,573.87<br />
250. Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
251. Tactile Exit Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 3<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
252. Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Adjust door for opening pressure/closing times unless accepted<br />
by DSA / Fire Life Safety.<br />
1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />
TOTAL EST: $306.26<br />
Page 32 of 33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue Qty Unit<br />
Sub<br />
Contractor<br />
Sub<br />
Total<br />
(10%)<br />
Concealed<br />
Conditions<br />
(12.5%)<br />
Security<br />
Conditions<br />
(15%)<br />
General<br />
Conditions<br />
Total<br />
254. Signage - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Priority: 2<br />
RECOMMENDATIONS AND RETROFIT COSTS:<br />
Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />
TOTAL EST: $183.75<br />
REPORT TOTALS: $290,897.43 $319,987.17 $359,985.57 $413,983.41 $413,983.41<br />
Page 33 of 33
Survey
Americans with Disabilities Act of 1990<br />
Site Assessment Report<br />
Report: UCR P5508 <strong>Pierce</strong><br />
<strong>Annex</strong><br />
900 University Avenue<br />
Riverside, CA 93012<br />
Inspection Date: 08/25/2009<br />
Prepared for:<br />
University of California at Riverside<br />
Prepared by:<br />
National Access Consultants, LLC<br />
2321 Abbot Kinney Blvd. Suite 200<br />
Venice, California 90291<br />
(805)497-6116
Contents<br />
1. Stairways - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1<br />
2. Stairway Handrails - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 2<br />
3. Stairway Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4<br />
4. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5<br />
5. Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 7<br />
6. Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9<br />
7. Tactile Exit Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10<br />
8. Floors and Levels - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11<br />
9. Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 12<br />
10. Clear Space at Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 14<br />
11. Identification Symbols, Restrooms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. 16<br />
12. Single Accommodation Toilet - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . 17<br />
13. Toilet Grab Bars - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 19<br />
14. Lavatories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 21<br />
15. Accessories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 23<br />
16. Visual/Audible Alarms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 25<br />
17. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex Restroom to the Left on the 1st Floor<br />
of <strong>Pierce</strong> <strong>Annex</strong> . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26<br />
18. Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong> . . . . . . . . . . . . . . . . 27<br />
19. Clear Space at Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 29<br />
20. Identification Symbols, Restrooms - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. 31<br />
21. Single Accommodation Toilet - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . 32<br />
22. Toilet Grab Bars - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 34<br />
23. Lavatories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 36<br />
24. Accessories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 38<br />
25. Visual/Audible Alarms - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 40<br />
26. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex Restroom to the Right on the 1st Floor<br />
of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41<br />
27. Corridors - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
28. Water Fountains (Drinking) - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 44<br />
29. Controls, Operating Mechanisms & Vending Machines. - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . 46<br />
30. Visual/Audible Alarms - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 47<br />
31. Electrical Controls & Receptacles/Fire Alarm Boxes - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 48<br />
32. Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 50<br />
33. Clear Space at Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 52<br />
34. Signage - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54<br />
35. Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 56<br />
36. Clear Space at Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 58<br />
37. Signage - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 60<br />
38. Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 62<br />
39. Clear Space at Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . 64<br />
40. Sales and Service Counters - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 66<br />
41. Sinks - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 67<br />
42. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69<br />
43. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70<br />
44. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71<br />
45. Seating, Tables and Work Surfaces - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 72<br />
46. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 73<br />
47. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 74<br />
48. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 75<br />
49. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. 76<br />
50. Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 78<br />
51. Clear Space at Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 80<br />
52. Signage - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 82<br />
53. Seating, Tables and Work Surfaces - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 84<br />
54. Doors - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 85<br />
55. Clear Space at Doors - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . 87
56. Signage - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 89<br />
57. Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90<br />
58. Elevator Control (Panel & Hall Call) - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 93<br />
59. Visual and Audible Signals For Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 95<br />
60. Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . 96<br />
61. Clear Space at Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 98<br />
62. Stairways - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 100<br />
63. Stairway Handrails - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 101<br />
64. Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 103<br />
65. Clear Space at Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 105<br />
66. Signage - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 107<br />
67. Sales and Service Counters - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 109<br />
68. Sinks - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 110<br />
69. Controls, Operating Mechanisms & Vending Machines. - Room #109 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112<br />
70. Doors - Between Room #109 and Room #111 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 113<br />
71. Clear Space at Doors - Between Room #109 and Room #111 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 115<br />
72. Signage - Between Room #109 and Room #111 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 117<br />
73. Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 119<br />
74. Clear Space at Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 121<br />
75. Signage - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 123<br />
76. Sales and Service Counters - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 125<br />
77. Sinks - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 126<br />
78. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128<br />
79. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130<br />
80. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131<br />
81. Seating, Tables and Work Surfaces - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 132<br />
82. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 133<br />
83. Aisles - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 134
84. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 135<br />
85. Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 136<br />
86. Clear Space at Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 138<br />
87. Signage - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 140<br />
88. Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 142<br />
89. Clear Space at Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 144<br />
90. Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 146<br />
91. Tactile Exit Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 147<br />
92. Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . 148<br />
93. Clear Space at Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 150<br />
94. Stairways - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 151<br />
95. Stairway Handrails - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 152<br />
96. Stairway Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 154<br />
97. Hazards - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 155<br />
98. Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 156<br />
99. Clear Space at Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 158<br />
100.Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 160<br />
101.Tactile Exit Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 161<br />
102.Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 162<br />
103.Clear Space at Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 164<br />
104.Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 166<br />
105.Tactile Exit Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 167<br />
106.Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 168<br />
107.Clear Space at Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 170<br />
108.Identification Symbols, Restrooms - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 172<br />
109.Single Accommodation Toilet - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 173<br />
110.Toilet Grab Bars - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 175<br />
111.Lavatories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 177<br />
112.Accessories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 179<br />
113.Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 181
114.Clear Space at Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 183<br />
115.Identification Symbols, Restrooms - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 185<br />
116.Single Accommodation Toilet - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 186<br />
117.Toilet Grab Bars - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 188<br />
118.Lavatories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 190<br />
119.Accessories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 192<br />
120.Water Fountains (Drinking) - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 194<br />
121.Controls, Operating Mechanisms & Vending Machines. - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . 196<br />
122.Seating, Tables and Work Surfaces - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 197<br />
123.Controls, Operating Mechanisms & Vending Machines. - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . 198<br />
124.Visual/Audible Alarms - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 199<br />
125.Electrical Controls & Receptacles/Fire Alarm Boxes - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . 200<br />
126.Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 202<br />
127.Clear Space at Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 204<br />
128.Signage - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 206<br />
129.Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 207<br />
130.Clear Space at Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 209<br />
131.Signage - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 211<br />
132.Seating, Tables and Work Surfaces - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . 213<br />
133.Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . 214<br />
134.Clear Space at Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 216<br />
135.Signage - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 218<br />
136.Sales and Service Counters - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 219<br />
137.Sinks - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 220<br />
138.Controls, Operating Mechanisms & Vending Machines. - Room #205 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222<br />
139.Controls, Operating Mechanisms & Vending Machines. - Room #205 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224<br />
140.Seating, Tables and Work Surfaces - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . 225<br />
141.Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 226<br />
142.Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 227
143.Aisles - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 228<br />
144.Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 230<br />
145.Clear Space at Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 232<br />
146.Signage - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 234<br />
147.Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 236<br />
148.Clear Space at Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 238<br />
149.Signage - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 240<br />
150.Sales and Service Counters - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 242<br />
151.Sinks - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 243<br />
152.Controls, Operating Mechanisms & Vending Machines. - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245<br />
153.Controls, Operating Mechanisms & Vending Machines. - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246<br />
154.Controls, Operating Mechanisms & Vending Machines. - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248<br />
155.Seating, Tables and Work Surfaces - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . 249<br />
156.Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 250<br />
157.Aisles - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 251<br />
158.Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 253<br />
159.Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 254<br />
160.Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 255<br />
161.Clear Space at Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 257<br />
162.Signage - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 259<br />
163.Sales and Service Counters - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 261<br />
164.Sinks - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 262<br />
165.Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264<br />
166.Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266<br />
167.Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268<br />
168.Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 269<br />
169.Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 270
170.Aisles - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 271<br />
171.Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 272<br />
172.Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 273<br />
173.Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 274<br />
174.Clear Space at Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 276<br />
175.Signage - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 278<br />
176.Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 280<br />
177.Clear Space at Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 281<br />
178.Signage - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 282<br />
179.Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 284<br />
180.Clear Space at Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 286<br />
181.Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 288<br />
182.Tactile Exit Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 289<br />
183.Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . 290<br />
184.Clear Space at Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . 292<br />
185.Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . 294<br />
186.Tactile Exit Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . . 295<br />
187.Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . . . . . 296<br />
188.Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . 298<br />
189.Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . . . . 300<br />
190.Tactile Exit Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . . 301<br />
191.Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 302<br />
192.Clear Space at Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 304<br />
193.Identification Symbols, Restrooms - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 306<br />
194.Single Accommodation Toilet - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 307<br />
195.Toilet Grab Bars - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 309<br />
196.Lavatories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 311<br />
197.Accessories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 313<br />
198.Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 315<br />
199.Clear Space at Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 317
200.Identification Symbols, Restrooms - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 319<br />
201.Single Accommodation Toilet - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 320<br />
202.Toilet Grab Bars - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 322<br />
203.Lavatories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 324<br />
204.Accessories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 326<br />
205.Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex Restroom on the Right on the 3rd Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328<br />
206.Corridors - 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330<br />
207.Water Fountains (Drinking) - Corridor on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 332<br />
208.Controls, Operating Mechanisms & Vending Machines. - Corridor on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 334<br />
209.Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 335<br />
210.Clear Space at Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 337<br />
211.Signage - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 339<br />
212.Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 340<br />
213.Clear Space at Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 342<br />
214.Signage - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 344<br />
215.Sales and Service Counters - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 346<br />
216.Sinks - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 347<br />
217.Controls, Operating Mechanisms & Vending Machines. - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349<br />
218.Controls, Operating Mechanisms & Vending Machines. - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351<br />
219.Controls, Operating Mechanisms & Vending Machines. - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353<br />
220.Seating, Tables and Work Surfaces - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 354<br />
221.Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 355<br />
222.Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 356<br />
223.Aisles - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 357<br />
224.Floors and Levels - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 358<br />
225.Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 359<br />
226.Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 360<br />
227.Clear Space at Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 362
228.Signage - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 364<br />
229.Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 366<br />
230.Clear Space at Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 368<br />
231.Signage - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 370<br />
232.Sales and Service Counters - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 372<br />
233.Sinks - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 373<br />
234.Controls, Operating Mechanisms & Vending Machines. - Rooms #307 and #304 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375<br />
235.Controls, Operating Mechanisms & Vending Machines. - Rooms #307 and #304 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377<br />
236.Controls, Operating Mechanisms & Vending Machines. - Rooms #307 and #304 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379<br />
237.Seating, Tables and Work Surfaces - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 380<br />
238.Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 381<br />
239.Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 382<br />
240.Aisles - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 383<br />
241.Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 384<br />
242.Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 385<br />
243.Clear Space at Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 387<br />
244.Signage - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 389<br />
245.Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 391<br />
246.Clear Space at Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 393<br />
247.Signage - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 395<br />
248.Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 397<br />
249.Clear Space at Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 399<br />
250.Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 401<br />
251.Tactile Exit Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 402<br />
252.Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 403<br />
253.Clear Space at Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 405<br />
254.Signage - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 407
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
1. Stairways - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
44” min. width if occupant load is more than 50.<br />
All treads are slip resistant.<br />
Nosing projection is less than 1-1/2”.<br />
All risers are closed.<br />
All steps have uniform riser height and tread width.<br />
11” min. tread width.<br />
Stairs do not accumulate water.<br />
Ext. - Top landing and all steps have color striping minimum 2” wide and a maximum 4” wide parallel to, and not<br />
more than 1” maximum from tread nose or landing.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-1-1 (originally 0001-400)<br />
1
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
2. Stairway Handrails - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Handrails are provided on both sides and are continuous for the full length of the stairway.<br />
1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.<br />
1-1/2” clearance provided between rail and wall.<br />
Handrails do not rotate in their fittings.<br />
Wall or adjacent surface is free of sharp or abrasive elements.<br />
Ends of rails are rounded or returned smoothly to wall or floor.<br />
Handrail is smooth with no sharp edges.<br />
Handrails do not protrude into pathways.<br />
Inner rails that double back or turn are continuous.<br />
Areas not meeting new construction standards:<br />
Rails are 34” - 38” above stair nosing. (32-1/2” high.)<br />
12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned. (10”.)<br />
12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being<br />
returned. (9-1/2”+ tread.)<br />
Recommendation:<br />
Raise/Lower existing handrail height.<br />
Install top or bottom extensions to existing handrail.<br />
2
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-2-1 (originally 0002-400)<br />
3
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
3. Stairway Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Identification signage is located at each floor level in all enclosed stairways in buildings two or more stories in height.<br />
Signs are a min. of 12” x 12” in size.<br />
Sign identifies the stairway location, floor level number, and upper and lower terminus of stairway.<br />
Information is presented with raised Arabic numerals and corresponding Grade II Braille.<br />
Sign is centered 60” above the floor landing immediately adjacent to the door on the strike side.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-3-1 (originally 0003-400)<br />
4
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
4. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate exterior doors. (7 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-4-1 (originally 0004-400)<br />
5
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-4-2 (originally 0005-400)<br />
6
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
5. Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-5-1 (originally 0006-400)<br />
7
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-5-2 (originally 0007-400)<br />
8
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
6. Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (No sign for door.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-6-1 (originally 0008-400)<br />
9
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
7. Tactile Exit Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />
exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />
appropriate. (Not proper wording.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-7-1 (originally 0009-400)<br />
10
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
8. Floors and Levels - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />
Memo:<br />
Four carpets / mats.<br />
Areas noted in compliance:<br />
Floor surface is slip resistant.<br />
Changes in level do not exceed 1/4” vertical or 1/2” with 1:2 bevel.<br />
Areas not meeting new construction standards:<br />
Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)<br />
Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not fastened.)<br />
Recommendation:<br />
Secure loose doormat.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-8-1 (originally 0010-400)<br />
11
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
9. Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (11 lbs.)<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-9-1 (originally 0011-400)<br />
12
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-9-2 (originally 0012-400)<br />
13
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
10. Clear Space at Doors - Unisex Restroom to the Left on the 1st Floor<br />
of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />
to water closet.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-10-1 (originally 0013-400)<br />
14
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-10-2 (originally 0014-400)<br />
15
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
11. Identification Symbols, Restrooms - Unisex Restroom to the Left on<br />
the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />
contrasts with the door, light on dark background or dark on light background. (No sign.)<br />
Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />
Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />
identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />
Recommendation:<br />
Install door-mounted sign on single door.<br />
Install wall-mounted sign at single entrance.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-11-1 (originally 0015-400)<br />
16
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
12. Single Accommodation Toilet - Unisex Restroom to the Left on the<br />
1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Space for 30” x 48” wheelchair to enter and permit door to close.<br />
Privacy lock, push button, lever release.<br />
28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />
the water closet to opposite wall or partition.<br />
18” between centerline of water closet and side wall or partition. (18-1/2” (within dimensional tolerance).)<br />
42” min. clearance between centerline of water closet and opposite wall.<br />
The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />
(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />
44” max. height to flush valve.<br />
Flush valve is on wide side of the water closet<br />
5 lb. max. force is required to operate the flush valve.<br />
19” min. height to toilet paper dispenser.<br />
Toilet paper dispenser provides continuous flow.<br />
Areas not meeting new construction standards:<br />
60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />
into the required clear space. (50”.)<br />
A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44-1/4” deep.)<br />
Front of toilet paper dispenser is within 36” of the back wall. (37-1/2”.)<br />
The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />
seat. (13” and above grab bar.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />
17
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-12-1 (originally 0016-400)<br />
18
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
13. Toilet Grab Bars - Unisex Restroom to the Left on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #12 for additional recommendations.<br />
Areas noted in compliance:<br />
1-1/4” to 1-1/2” diameter of bars.<br />
1-1/2” clearance between bars and each wall or partition.<br />
The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />
(33-1/2” high.)<br />
The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />
tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2” high.)<br />
Side bar has 42” min. length.<br />
Side bar begins a max. of 12” from back wall.<br />
Back bar has 36” min. length.<br />
Back bar begins a max. of 6” from side wall.<br />
Bars are smooth with a min. edge radius of 1/8”.<br />
Grab bars do not rotate within their fittings.<br />
Min. structural strength to support 250 lb. point load.<br />
Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />
Areas not meeting new construction standards:<br />
The front of the side grab bar extends 54” from back wall in single accommodation stall. (50-1/4”.)<br />
Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />
items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-3/4”.)<br />
Recommendation:<br />
Relocate grab bar.<br />
Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />
19
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-13-1 (originally 0017-400)<br />
20
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
14. Lavatories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />
space).<br />
Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />
34” max. height to rim or counter above floor surface.<br />
29” min. clearance from bottom of apron to floor surface.<br />
27” high x 8” deep knee clearance under front lip.<br />
30” wide x 9” high x 17” deep clearance from front of lavatory.<br />
Drain and piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under lavatory.<br />
Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />
5 lb. max. force required to operate controls.<br />
Areas not meeting new construction standards:<br />
18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />
Recommendation:<br />
Replace/Install accessible lavatory.<br />
21
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-14-1 (originally 0018-400)<br />
22
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
15. Accessories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
See Sequence #12 and #13 for additional recommendations. Soap dispenser - 44” high / seat cover dispenser - 48” high<br />
/ paper towel dispenser - 45” high / toilet paper dispenser - 42-1/2” high.<br />
Areas noted in compliance:<br />
40” maximum height to bottom of reflective surface of mirror.<br />
Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />
A maximum of 5 lbs. force is required to operate mechanisms.<br />
Areas not meeting new construction standards:<br />
40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />
recepatacles, etc.). (See memo.)<br />
height above floor surface is recom-<br />
Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />
mended). (66-1/2” high.)<br />
A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />
(Seat cover dispenser.)<br />
Recommendation:<br />
Install accessible coat hook.<br />
Relocate the soap dispenser.<br />
Relocate the paper towel dispenser / hand dryer.<br />
23
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-15-1 (originally 0019-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-15-2 (originally 0020-400)<br />
24
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
16. Visual/Audible Alarms - Unisex Restroom to the Left on the 1st Floor<br />
of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />
(79-1/2” high.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-16-1 (originally 0021-400)<br />
25
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
17. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex<br />
Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong> .<br />
Memo:<br />
Areas noted in compliance:<br />
The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />
max. above the floor or working platform.<br />
The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />
or working platform.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-17-1 (originally 0022-400)<br />
26
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
18. Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong> .<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (10 lbs.)<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-18-1 (originally 0023-400)<br />
27
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-18-2 (originally 0024-400)<br />
28
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
19. Clear Space at Doors - Unisex Restroom to the Right on the 1st Floor<br />
of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-19-1 (originally 0025-400)<br />
29
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-19-2 (originally 0026-400)<br />
30
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
20. Identification Symbols, Restrooms - Unisex Restroom to the Right on<br />
the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />
contrasts with the door, light on dark background or dark on light background. (No sign.)<br />
Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />
Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />
identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />
Recommendation:<br />
Install door-mounted sign on single door.<br />
Install wall-mounted sign at single entrance.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-20-1 (originally 0027-400)<br />
31
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
21. Single Accommodation Toilet - Unisex Restroom to the Right on the<br />
1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Space for 30” x 48” wheelchair to enter and permit door to close.<br />
Privacy lock, push button, lever release.<br />
60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />
into the required clear space.<br />
28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />
the water closet to opposite wall or partition.<br />
18” between centerline of water closet and side wall or partition. (17-1/4” (within dimensional tolerance).)<br />
42” min. clearance between centerline of water closet and opposite wall.<br />
The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />
(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />
44” max. height to flush valve.<br />
Flush valve is on wide side of the water closet<br />
5 lb. max. force is required to operate the flush valve.<br />
19” min. height to toilet paper dispenser.<br />
Toilet paper dispenser provides continuous flow.<br />
Areas not meeting new construction standards:<br />
A minimum 60” wide and 48” deep clear floor space is provided in front of water closet.<br />
Front of toilet paper dispenser is within 36” of the back wall. (39”.)<br />
The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />
seat. (14” and above grab bar.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />
32
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-21-1 (originally 0028-400)<br />
33
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
22. Toilet Grab Bars - Unisex Restroom to the Right on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #21 for additional recommendations.<br />
Areas noted in compliance:<br />
1-1/4” to 1-1/2” diameter of bars.<br />
1-1/2” clearance between bars and each wall or partition.<br />
The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />
(33-1/2” high.)<br />
The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />
tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2” high.)<br />
Side bar has 42” min. length.<br />
Side bar begins a max. of 12” from back wall.<br />
Back bar has 36” min. length.<br />
Back bar begins a max. of 6” from side wall.<br />
Bars are smooth with a min. edge radius of 1/8”.<br />
Grab bars do not rotate within their fittings.<br />
Min. structural strength to support 250 lb. point load.<br />
Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />
Areas not meeting new construction standards:<br />
The front of the side grab bar extends 54” from back wall in single accommodation stall. (50-3/4”.)<br />
Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />
items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-3/4”.)<br />
Recommendation:<br />
Relocate grab bar.<br />
Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />
34
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-22-1 (originally 0029-400)<br />
35
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
23. Lavatories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />
space).<br />
Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />
34” max. height to rim or counter above floor surface.<br />
29” min. clearance from bottom of apron to floor surface.<br />
27” high x 8” deep knee clearance under front lip.<br />
30” wide x 9” high x 17” deep clearance from front of lavatory.<br />
Drain and piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under lavatory.<br />
Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />
5 lb. max. force required to operate controls.<br />
Areas not meeting new construction standards:<br />
18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />
Recommendation:<br />
Replace/Install accessible lavatory.<br />
36
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-23-1 (originally 0030-400)<br />
37
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
24. Accessories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
See Sequence #21 and #22 for additional recommendations. Soap dispenser - 43” / seat cover dispenser - 48” / paper<br />
towel dispenser - 45” / toilet paper dispenser - 42-1/4”.<br />
Areas noted in compliance:<br />
40” maximum height to bottom of reflective surface of mirror.<br />
Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />
A maximum of 5 lbs. force is required to operate mechanisms.<br />
Areas not meeting new construction standards:<br />
40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />
recepatacles, etc.). (See memo.)<br />
height above floor surface is recom-<br />
Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />
mended). (66-1/2” high.)<br />
A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />
(Seat cover dispenser.)<br />
Recommendation:<br />
Install accessible coat hook.<br />
Relocate the soap dispenser.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-24-1 (originally 0031-400)<br />
38
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-24-2 (originally 0032-400)<br />
39
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
25. Visual/Audible Alarms - Unisex Restroom to the Right on the 1st<br />
Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
The alarm is integrated into the building or facility alarm system.<br />
Lamp is a xenon strobe type or equivalent.<br />
The color is clear and nominal white (unfiltered) or clear filtered white light.<br />
The maximum pulse duration is two-tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent.<br />
The intensity is a maximum of 75 candela.<br />
The flash rate is a minimum of 1Hz and a maximum of 3Hz.<br />
The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />
When provided/required, audible emergency alarms meet applicable requirements.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-25-1 (originally 0033-400)<br />
40
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
26. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex<br />
Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />
max. above the floor or working platform.<br />
The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />
or working platform.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
41
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
27. Corridors - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
44” minimum width for occupant loads of 10 or more.<br />
and 60” x 60” turning space at central location, or,<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-27-1 (originally 0035-400)<br />
42
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-27-2 (originally 0036-400)<br />
43
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
28. Water Fountains (Drinking) - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
32” minimum wide and 18” minimum deep alcove provided.<br />
18” minimum depth of fountain.<br />
27” high x 8” deep clear knee space under fountain.<br />
9” high x 17” deep toe clearance.<br />
Lever or push bar control is located 6” max. from front edge.<br />
Bubbler outlet is 6” maximum from front.<br />
Bubbler outlet is 36” maximum from floor.<br />
4” minimum height of stream.<br />
Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty<br />
bending or stooping.<br />
Areas not meeting new construction standards:<br />
Stream of bubbler is parallel to front edge. (On angle.)<br />
The force required to activate controls does not exceed 5lbf. (7 lbs.)<br />
Recommendation:<br />
Adjust angle of stream.<br />
Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />
44
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-28-1 (originally 0037-400)<br />
45
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
29. Controls, Operating Mechanisms & Vending Machines. - 1st Floor<br />
Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fire extinguisher cabinets.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-29-1 (originally 0038-400)<br />
46
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
30. Visual/Audible Alarms - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
There are no places in common corridors or hallways that are more than 50’ from required signaling appliances.<br />
Areas not meeting new construction standards:<br />
The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />
(79-1/2” high.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-30-1 (originally 0039-400)<br />
47
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
31. Electrical Controls & Receptacles/Fire Alarm Boxes - 1st Floor<br />
Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />
max. above the floor or working platform.<br />
The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />
or working platform.<br />
The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the<br />
floor level to the highest point of the activating handle or lever of the box.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-31-1 (originally 0040-400)<br />
48
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-31-2 (originally 0042-400)<br />
49
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
32. Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Four office doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
5 lb. maximum pressure to operate interior doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-32-1 (originally 0044-400)<br />
50
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-32-2 (originally 0045-400)<br />
51
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
33. Clear Space at Doors - 1st Floor Rooms #124, #123, #103 and<br />
#102 at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Four office doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PUSH side of door: 0”.<br />
Areas not meeting new construction standards:<br />
60” min. clear space in direction of door swing. (50” to boxes at Room #102.)<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (9” to the furniture at Room<br />
#102.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Modify, relocate, replace or remove restricting objects.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-33-1 (originally 0046-400)<br />
52
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-33-2 (originally 0047-400)<br />
53
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
34. Signage - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (54-3/4”.)<br />
Recommendation:<br />
Relocate permanent ID sign to latch side of door.<br />
54
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-34-1 (originally 0048-400)<br />
55
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
35. Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (8 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-35-1 (originally 1417-400)<br />
56
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-35-2 (originally 1418-400)<br />
57
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
36. Clear Space at Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (0” to furniture.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-36-1 (originally 1419-400)<br />
58
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-36-2 (originally 1420-400)<br />
59
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
37. Signage - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Interior door inside of Room #107.<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
60
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-37-1 (originally 1421-400)<br />
61
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
38. Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
5 lb. maximum pressure to operate interior doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-38-1 (originally 1422-400)<br />
62
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-38-2 (originally 1423-400)<br />
63
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
39. Clear Space at Doors - Behind Room #107 Toward Lab on the 1st<br />
Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PUSH side of door: 0”.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (18” wide x 36” deep.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-39-1 (originally 1424-400)<br />
64
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-39-2 (originally 1425-400)<br />
65
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
40. Sales and Service Counters - Room #106 on the 1st Floor of <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and;<br />
Areas not meeting new construction standards:<br />
Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and; (25” high.)<br />
Recommendation:<br />
Install accessible counter.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-40-1 (originally 1426-400)<br />
66
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
41. Sinks - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Required clear space adjoins or overlaps an accessible route.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
34” maximum height of rim or counter above floor surfaces. (35” high.)<br />
Sink is a maximum of 6-1/2” deep. (12”.)<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink. (0” deep.)<br />
Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />
Recommendation:<br />
Replace/Install accessible sink.<br />
Insulate pipes under lavatory (or sink when applicable).<br />
Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />
67
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-41-1 (originally 1427-400)<br />
68
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
42. Controls, Operating Mechanisms & Vending Machines. - Room #106<br />
on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-42-1 (originally 1428-400)<br />
69
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
43. Controls, Operating Mechanisms & Vending Machines. - Room #106<br />
on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-43-1 (originally 1429-400)<br />
70
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
44. Controls, Operating Mechanisms & Vending Machines. - Room #106<br />
on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (59”.)<br />
Recommendation:<br />
Replace the fume hood with an accessible fume hood workstation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-44-1 (originally 1430-400)<br />
71
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
45. Seating, Tables and Work Surfaces - Room #106 on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. See Sequence #44 for recommendation.<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />
27” high, 30” wide and 19” deep knee clearance provided.<br />
Areas not meeting new construction standards:<br />
28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-45-1 (originally 1431-400)<br />
72
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
46. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (5” projection.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-46-1 (originally 1432-400)<br />
73
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
47. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Power control boxes.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6” projection.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-47-1 (originally 1433-400)<br />
74
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
48. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Emergency eyewash.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6” projection.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-48-1 (originally 1434-400)<br />
75
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
49. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #106 on<br />
the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />
max. above the floor or working platform.<br />
The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />
or working platform. (85” high / Others at ground level.)<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-49-1 (originally 1435-400)<br />
76
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-49-2 (originally 1436-400)<br />
77
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
50. Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (7 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-50-1 (originally 1438-400)<br />
78
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-50-2 (originally 1439-400)<br />
79
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
51. Clear Space at Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-51-1 (originally 1440-400)<br />
80
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-51-2 (originally 1441-400)<br />
81
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
52. Signage - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
82
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-52-1 (originally 1442-400)<br />
83
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
53. Seating, Tables and Work Surfaces - Room #111 on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />
27” high, 30” wide and 19” deep knee clearance provided.<br />
28” - 34” height of table or work surface that is 36” wide.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-53-1 (originally 1443-400)<br />
84
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
54. Doors - Door to Courtyard from Room #111 on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
32” minimum clear width of doorway. (30-1/4”.)<br />
5 lb. maximum pressure to operate exterior doors. (10 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall).<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-54-1 (originally 1444-400)<br />
85
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-54-2 (originally 1445-400)<br />
86
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
55. Clear Space at Doors - Door to Courtyard from Room #111 on the<br />
1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-55-1 (originally 1446-400)<br />
87
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-55-2 (originally 1447-400)<br />
88
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
56. Signage - Door to Courtyard from Room #111 on the 1st Floor of<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-56-1 (originally 1448-400)<br />
89
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
57. Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Located near major path of travel and are accessible at all times the building is occupied.<br />
54” min. depth of the car platform (rear wall to door)<br />
51” min. clearance from the rear wall to return panel.<br />
36” min. clear width of doorway when fully open.<br />
Handrail is provided (1 minimum) on one wall of the car (rear preferred).<br />
Operation of doors (opening and closing) is automatic.<br />
Elevator is self leveling within 1/2” of floor landings.<br />
Emergency communication device does not require voice communication.<br />
The car inside allows for the turning of a wheelchair (enter the car, maneuver within reach of controls, and exit from the car).<br />
32” (+or- 1”) height of the handrail from the floor.<br />
Minimum of 1-1/2” clearance of the handrail from the wall.<br />
Handrail is smooth, no sharp edges.<br />
Doors are side-slide type (power-operated horizontally sliding).<br />
The clearance between the car platform sill and the edge of the hoistway landing is no greater than 1-1/4”.<br />
Doors remain fully open a minimum of 5 seconds when initially activated.<br />
Door jambs at all landings identify the floor by both raised Arabic numerals (minimum of 2” in height) and Braille<br />
symbols (immediately to left of numerals).<br />
Raised characters are on a contrasting background.<br />
Doorjamb markings are centered at 60” above the floor on both sides of the door.<br />
Emergency communication device is a maximum of 48” from the floor.<br />
The level of illumination at the platform, car threshold and landing sill is at least 5 foot-candles.<br />
Areas not meeting new construction standards:<br />
68” min. width of the car platform with off-center door panels. (65”.)<br />
Elevator doors have an automatic reopening device. The device opens the doors when objects pass through the opening<br />
at heights of 5” and 29” from the floor without requiring contact. Doors remain open for 20 seconds minimum. (5 seconds.)<br />
At grade level, a raised five-pointed star with an outside diameter of 2” is placed to the left of the raised character.<br />
90
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
(1” star.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Repair door operation.<br />
Provide a raised five pointed star at the ground level.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-57-1 (originally 1449-400)<br />
91
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-57-2 (originally 1450-400)<br />
92
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
58. Elevator Control (Panel & Hall Call) - Southeast Side at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Elevator car controls are located on a front wall in cars that have center opening doors, and at the side wall or at the front<br />
wall next to the door if the car has side opening doors.<br />
Elevator floor buttons comply with reach range requirements (48” front reach; 54” side reach to centerline of buttons).<br />
Control buttons are square shouldered, and are a minimum of 3/4” and raised 1/8” plus of minus 1/32” above the<br />
sorrounding surface.<br />
Control buttons are illuminated and are activated by a mechanical motion that is detectable.<br />
All buttons are designated by a 5/8” minimum Arabic Numeral, alphabet or other standard sans serif uppercase character,<br />
or standard raised symbol immediately to the left of the control button.<br />
All raised characters are white on a black background.<br />
Grade 2 Braille symbols are located immediately below the raised characters.<br />
Emergency controls (stop and alarm) are a minimum of 35” from the floor.<br />
The centerline of hall call buttons in elevator lobbies are located at 42” above the floor.<br />
Hall call buttons are a minimum of 3/4” in size and raised 1/8” plus or minus 1/32” above the sorrounding surface.<br />
Hall call button provides visual indication that shows each call registered and extinguishes when answered.<br />
Objects adjacent to and below hall call buttons do not project more than 4”.<br />
Hall call buttons are internally illuminated with a white light over the entire surface of the button.<br />
Areas not meeting new construction standards:<br />
3/8” minimum distance between the rows of the control buttons.<br />
Recommendation:<br />
None.<br />
93
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-58-1 (originally 1451-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-58-2 (originally 1452-400)<br />
94
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
59. Visual and Audible Signals For Elevators - Southeast Side at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Elevator has visual and audible signals indicating the position of the car on or between floors. The indication is positioned<br />
above the car control panel or over the door.<br />
The visual signal for each direction is a minimum of 2-1/2” x 2-1/2”, and visible from the proximity of the hall call<br />
button. NOTE: An automatic verbal announcement of the floor number at which a car stops or which a car passes may<br />
be substituted for the audible signal.<br />
Audible signal sounds are once for up and twice for down. (or equivalent)<br />
Audible signal is no less than 20 decibels with a frequency no higher than 1500 Hz.<br />
Centerline of the fixture is a minimum of 6’ (72”) in height above the lobby floor. NOTE: The use of in-car lanterns,<br />
located in or on the door jambs, visible from the proximity of the call buttons and conforming to items 1, 2, & 3 above<br />
shall or will be acceptable.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-59-1 (originally 1453-400)<br />
95
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
60. Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
32” minimum clear width of doorway. (30-1/4”.)<br />
5 lb. maximum pressure to operate exterior doors. (10 lbs.)<br />
The international symbol of accessibility is posted at all primary entrances.<br />
Recommendation:<br />
Replace door(s) and frame (stud wall).<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Post a sign/decal displaying the ”International Symbol of Accessibility” at the primary entrance.<br />
96
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-60-1 (originally 1454-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-60-2 (originally 1455-400)<br />
97
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
61. Clear Space at Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-61-1 (originally 1456-400)<br />
98
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-61-2 (originally 1457-400)<br />
99
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
62. Stairways - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Two staircases.<br />
Areas noted in compliance:<br />
44” min. width if occupant load is more than 50.<br />
All treads are slip resistant.<br />
Nosing projection is less than 1-1/2”.<br />
All risers are closed.<br />
11” min. tread width.<br />
Stairs do not accumulate water.<br />
Ext. - Top landing and all steps have color striping minimum 2” wide and a maximum 4” wide parallel to, and not<br />
more than 1” maximum from tread nose or landing.<br />
Areas not meeting new construction standards:<br />
All steps have uniform riser height and tread width. (6-1/2” - 7-1/4” risers.)<br />
Recommendation:<br />
Remove/Replace existing stairways or steps.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-62-1 (originally 1458-400)<br />
100
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
63. Stairway Handrails - Southeast Entrance on the 1st Floor to <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Two stair cases.<br />
Areas noted in compliance:<br />
Handrails are provided on both sides and are continuous for the full length of the stairway.<br />
1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.<br />
1-1/2” clearance provided between rail and wall.<br />
Handrails do not rotate in their fittings.<br />
Wall or adjacent surface is free of sharp or abrasive elements.<br />
Ends of rails are rounded or returned smoothly to wall or floor.<br />
Handrail is smooth with no sharp edges.<br />
Handrails do not protrude into pathways.<br />
Areas not meeting new construction standards:<br />
Rails are 34” - 38” above stair nosing. (33” high.)<br />
12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned. (9”.)<br />
12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being<br />
returned. (9”+ tread.)<br />
Recommendation:<br />
Raise/Lower existing handrail height.<br />
101
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-63-1 (originally 1459-400)<br />
102
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
64. Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (8 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-64-1 (originally 1460-400)<br />
103
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-64-2 (originally 1461-400)<br />
104
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
65. Clear Space at Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-65-1 (originally 1462-400)<br />
105
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-65-2 (originally 1463-400)<br />
106
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
66. Signage - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
107
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-66-1 (originally 1464-400)<br />
108
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
67. Sales and Service Counters - Room #109 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-67-1 (originally 1465-400)<br />
109
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
68. Sinks - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
Required clear space adjoins or overlaps an accessible route.<br />
34” maximum height of rim or counter above floor surfaces.<br />
Sink is a maximum of 6-1/2” deep.<br />
Drain and hot water piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink. (0” deep.)<br />
Recommendation:<br />
Insulate pipes under lavatory (or sink when applicable).<br />
Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />
110
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-68-1 (originally 1468-400)<br />
111
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
69. Controls, Operating Mechanisms & Vending Machines. - Room #109<br />
on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Paper towel dispenser.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (54” high.)<br />
Recommendation:<br />
Relocate existing paper towel dispenser.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-69-1 (originally 1470-400)<br />
112
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
70. Doors - Between Room #109 and Room #111 on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
5 lb. maximum pressure to operate interior doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-70-1 (originally 1471-400)<br />
113
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-70-2 (originally 1472-400)<br />
114
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
71. Clear Space at Doors - Between Room #109 and Room #111 on the<br />
1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-71-1 (originally 1473-400)<br />
115
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-71-2 (originally 1474-400)<br />
116
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
72. Signage - Between Room #109 and Room #111 on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Not required here.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-72-1 (originally 1475-400)<br />
117
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-72-2 (originally 1476-400)<br />
118
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
73. Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (6 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-73-1 (originally 1477-400)<br />
119
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-73-2 (originally 1478-400)<br />
120
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
74. Clear Space at Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (12” to wall.)<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (2” to trash can.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Modify door to swing opposite hand.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-74-1 (originally 1479-400)<br />
121
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-74-2 (originally 1480-400)<br />
122
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
75. Signage - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
123
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-75-1 (originally 1481-400)<br />
124
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
76. Sales and Service Counters - Room #105 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-76-1 (originally 1482-400)<br />
125
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
77. Sinks - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Required clear space adjoins or overlaps an accessible route.<br />
34” maximum height of rim or counter above floor surfaces.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
Sink is a maximum of 6-1/2” deep. (10” deep.)<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink.<br />
Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />
Recommendation:<br />
Replace/Install accessible sink.<br />
Insulate pipes under lavatory (or sink when applicable).<br />
Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />
126
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-77-1 (originally 1484-400)<br />
127
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
78. Controls, Operating Mechanisms & Vending Machines. - Room #105<br />
on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knob.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-78-1 (originally 1487-400)<br />
128
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-78-2 (originally 1488-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-78-3 (originally 1489-400)<br />
129
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
79. Controls, Operating Mechanisms & Vending Machines. - Room #105<br />
on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Thermogravimetric analyzer.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (56” high.)<br />
Recommendation:<br />
Lower the machine.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-79-1 (originally 1490-400)<br />
130
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
80. Controls, Operating Mechanisms & Vending Machines. - Room #105<br />
on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. See Sequence #81 for recommendation.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (59” high.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-80-1 (originally 1491-400)<br />
131
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
81. Seating, Tables and Work Surfaces - Room #105 on the 1st Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />
space.<br />
Areas not meeting new construction standards:<br />
27” high, 30” wide and 19” deep knee clearance provided. (0” deep.)<br />
28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />
Recommendation:<br />
Replace the fume hood with an accessible fume hood workstation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-81-1 (originally 1492-400)<br />
132
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
82. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (5-1/2” projection.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-82-1 (originally 1493-400)<br />
133
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
83. Aisles - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
36” minimum width of aisles. (25” - 35”.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-83-1 (originally 1494-400)<br />
134
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
84. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Emergency eye wash.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-84-1 (originally 1495-400)<br />
135
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
85. Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Three doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (8 - 11 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-85-1 (originally 1496-400)<br />
136
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-85-2 (originally 1497-400)<br />
137
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
86. Clear Space at Doors - Room #105 and Room #106 on the 1st Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Three doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-86-1 (originally 1498-400)<br />
138
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-86-2 (originally 1499-400)<br />
139
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
87. Signage - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
140
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-87-1 (originally 1500-400)<br />
141
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
88. Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
32” minimum clear width of doorway. (31”.)<br />
5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall).<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-88-1 (originally 1501-400)<br />
142
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-88-2 (originally 1502-400)<br />
143
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
89. Clear Space at Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-89-1 (originally 1503-400)<br />
144
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-89-2 (originally 1504-400)<br />
145
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
90. Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-90-1 (originally 1505-400)<br />
146
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
91. Tactile Exit Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />
exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />
appropriate. (Not proper wording.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-91-1 (originally 1505-400)<br />
147
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
92. Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Exit only door.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate exterior doors. (9 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-92-1 (originally 1506-400)<br />
148
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-92-2 (originally 1507-400)<br />
149
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
93. Clear Space at Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Exit door only.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-93-1 (originally 1508-400)<br />
150
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
94. Stairways - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
44” min. width if occupant load is more than 50.<br />
All treads are slip resistant.<br />
Nosing projection is less than 1-1/2”.<br />
All risers are closed.<br />
All steps have uniform riser height and tread width.<br />
11” min. tread width.<br />
Stairs do not accumulate water.<br />
Int. - Top landing and lower tread have color striping minimum 2” wide and a maximum 4” wide parallel to, and<br />
not more than 1” maximum from tread nose or landing.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-94-1 (originally 1510-400)<br />
151
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
95. Stairway Handrails - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Handrails are provided on both sides and are continuous for the full length of the stairway.<br />
1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.<br />
1-1/2” clearance provided between rail and wall.<br />
Handrails do not rotate in their fittings.<br />
Wall or adjacent surface is free of sharp or abrasive elements.<br />
Ends of rails are rounded or returned smoothly to wall or floor.<br />
Handrail is smooth with no sharp edges.<br />
Handrails do not protrude into pathways.<br />
Inner rails that double back or turn are continuous.<br />
Areas not meeting new construction standards:<br />
Rails are 34” - 38” above stair nosing. (32” - 32-1/2” high.)<br />
12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned. (9”.)<br />
12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being<br />
returned. (Tread - 9”+.)<br />
Recommendation:<br />
Raise/Lower existing handrail height.<br />
152
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-95-1 (originally 1511-400)<br />
153
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
96. Stairway Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Every sign in stairwell.<br />
Areas noted in compliance:<br />
Identification signage is located at each floor level in all enclosed stairways in buildings two or more stories in height.<br />
Signs are a min. of 12” x 12” in size.<br />
Sign identifies the stairway location, floor level number, and upper and lower terminus of stairway.<br />
Information is presented with raised Arabic numerals and corresponding Grade II Braille.<br />
Sign is centered 60” above the floor landing immediately adjacent to the door on the strike side.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-96-1 (originally 1512-400)<br />
154
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
97. Hazards - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Underneath stairwell.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Any obstrution that overhangs a pedestrian way is a minimum 80” above the walking surface (measured from the bottom<br />
of the obstruction). (27” - 80”.)<br />
Sidewalks are clear of hazards.<br />
If vertical clearance of an area adjoining an accessible route is reduced to less than 80”, a barrier to warn blind or<br />
visually impaired persons is provided. (No barrier.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-97-1 (originally 1513-400)<br />
155
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
98. Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-98-1 (originally 1514-400)<br />
156
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-98-2 (originally 1515-400)<br />
157
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
99. Clear Space at Doors - North Entrance on the 1st Floor to <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-99-1 (originally 1516-400)<br />
158
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-99-2 (originally 1517-400)<br />
159
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
100. Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-100-1 (originally 1518-400)<br />
160
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
101. Tactile Exit Signage - North Entrance on the 1st Floor to <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Each grade-level exterior exit door shall be identified by a tactile sign with the word ”EXIT”. (None.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-101-1 (originally 1519-400)<br />
161
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
102. Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate exterior doors. (8 - 9 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-102-1 (originally 1520-400)<br />
162
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-102-2 (originally 1521-400)<br />
163
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
103. Clear Space at Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-103-1 (originally 1522-400)<br />
164
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-103-2 (originally 1523-400)<br />
165
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
104. Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (No door sign.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-104-1 (originally 1524-400)<br />
166
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
105. Tactile Exit Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />
exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />
appropriate. (Improper wording.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-105-1 (originally 1525-400)<br />
167
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
106. Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (12 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-106-1 (originally 1526-400)<br />
168
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-106-2 (originally 1527-400)<br />
169
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
107. Clear Space at Doors - Unisex Restroom to the Left on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />
to water closet.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-107-1 (originally 1528-400)<br />
170
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-107-2 (originally 1529-400)<br />
171
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
108. Identification Symbols, Restrooms - Unisex Restroom to the Left on<br />
the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />
contrasts with the door, light on dark background or dark on light background. (No signage.)<br />
Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />
Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />
identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />
Recommendation:<br />
Install door-mounted sign on single door.<br />
Install wall-mounted sign at single entrance.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-108-1 (originally 1530-400)<br />
172
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
109. Single Accommodation Toilet - Unisex Restroom to the Left on the<br />
2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Space for 30” x 48” wheelchair to enter and permit door to close.<br />
Privacy lock, push button, lever release.<br />
28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />
the water closet to opposite wall or partition.<br />
18” between centerline of water closet and side wall or partition.<br />
42” min. clearance between centerline of water closet and opposite wall.<br />
The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />
(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />
44” max. height to flush valve.<br />
Flush valve is on wide side of the water closet<br />
5 lb. max. force is required to operate the flush valve.<br />
The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />
seat.<br />
19” min. height to toilet paper dispenser.<br />
Toilet paper dispenser provides continuous flow.<br />
Areas not meeting new construction standards:<br />
60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />
into the required clear space. (50”.)<br />
A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44-1/4”.)<br />
Front of toilet paper dispenser is within 36” of the back wall. (38”.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />
173
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-109-1 (originally 1531-400)<br />
174
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
110. Toilet Grab Bars - Unisex Restroom to the Left on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #109 for additional recommendations.<br />
Areas noted in compliance:<br />
1-1/4” to 1-1/2” diameter of bars.<br />
1-1/2” clearance between bars and each wall or partition.<br />
The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />
(33-1/2”.)<br />
The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />
tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2”.)<br />
Side bar has 42” min. length.<br />
Side bar begins a max. of 12” from back wall.<br />
Back bar has 36” min. length.<br />
Back bar begins a max. of 6” from side wall.<br />
Bars are smooth with a min. edge radius of 1/8”.<br />
Grab bars do not rotate within their fittings.<br />
Min. structural strength to support 250 lb. point load.<br />
Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />
Areas not meeting new construction standards:<br />
The front of the side grab bar extends 54” from back wall in single accommodation stall. (51-1/4”.)<br />
Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />
items are allowed). (Toilet paper dispenser - 8” / seat cover dispenser - 5-3/4”.)<br />
Recommendation:<br />
Relocate grab bar.<br />
Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />
175
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-110-1 (originally 1531-400)<br />
176
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
111. Lavatories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />
space).<br />
Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />
29” min. clearance from bottom of apron to floor surface.<br />
27” high x 8” deep knee clearance under front lip.<br />
30” wide x 9” high x 17” deep clearance from front of lavatory.<br />
Drain and piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under lavatory.<br />
Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />
5 lb. max. force required to operate controls.<br />
Areas not meeting new construction standards:<br />
18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />
34” max. height to rim or counter above floor surface. (34-1/4”.)<br />
Recommendation:<br />
Replace/Install accessible lavatory.<br />
177
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-111-1 (originally 1532-400)<br />
178
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
112. Accessories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
See Sequence #109 and #110 for additional recommendations.<br />
Areas noted in compliance:<br />
40” maximum height to bottom of reflective surface of mirror.<br />
Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />
A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />
A maximum of 5 lbs. force is required to operate mechanisms.<br />
Areas not meeting new construction standards:<br />
40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />
recepatacles, etc.). (Soap dispenser - 44” / seat covers - 48” / paper towels - 45-1/2” / toilet paper - 42-1/2”.)<br />
height above floor surface is recom-<br />
Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />
mended). (Coat hook - 66-1/2”.)<br />
Recommendation:<br />
Install accessible coat hook.<br />
Relocate the soap dispenser.<br />
Relocate the paper towel dispenser / hand dryer.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-112-1 (originally 1533-400)<br />
179
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-112-2 (originally 1534-400)<br />
180
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
113. Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (10 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-113-1 (originally 1538-400)<br />
181
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-113-2 (originally 1539-400)<br />
182
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
114. Clear Space at Doors - Unisex Restroom to the Right on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />
to the water closet.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-114-1 (originally 1540-400)<br />
183
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-114-2 (originally 1541-400)<br />
184
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
115. Identification Symbols, Restrooms - Unisex Restroom to the Right<br />
on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />
contrasts with the door, light on dark background or dark on light background. (No signage.)<br />
Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />
Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />
identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />
Recommendation:<br />
Install door-mounted sign on single door.<br />
Install wall-mounted sign at single entrance.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-115-1 (originally 1542-400)<br />
185
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
116. Single Accommodation Toilet - Unisex Restroom to the Right on the<br />
2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Space for 30” x 48” wheelchair to enter and permit door to close.<br />
Privacy lock, push button, lever release.<br />
28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />
the water closet to opposite wall or partition.<br />
18” between centerline of water closet and side wall or partition. (18-3/4” (within dimensional tolerance).)<br />
42” min. clearance between centerline of water closet and opposite wall.<br />
The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />
(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />
44” max. height to flush valve.<br />
Flush valve is on wide side of the water closet<br />
5 lb. max. force is required to operate the flush valve.<br />
19” min. height to toilet paper dispenser.<br />
Toilet paper dispenser provides continuous flow.<br />
Areas not meeting new construction standards:<br />
60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />
into the required clear space. (50”.)<br />
A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44”.)<br />
Front of toilet paper dispenser is within 36” of the back wall. (39-1/2”.)<br />
The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />
seat. (13” and above.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />
186
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-116-1 (originally 1543-400)<br />
187
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
117. Toilet Grab Bars - Unisex Restroom to the Right on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #116 for additional recommendations.<br />
Areas noted in compliance:<br />
1-1/4” to 1-1/2” diameter of bars.<br />
1-1/2” clearance between bars and each wall or partition.<br />
The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />
(33-1/2”.)<br />
The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />
tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2”.)<br />
Side bar has 42” min. length.<br />
Side bar begins a max. of 12” from back wall.<br />
Back bar has 36” min. length.<br />
Back bar begins a max. of 6” from side wall.<br />
Bars are smooth with a min. edge radius of 1/8”.<br />
Grab bars do not rotate within their fittings.<br />
Min. structural strength to support 250 lb. point load.<br />
Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />
Areas not meeting new construction standards:<br />
The front of the side grab bar extends 54” from back wall in single accommodation stall. (52”.)<br />
Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />
items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-3/4”.)<br />
Recommendation:<br />
Relocate grab bar.<br />
188
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-117-1 (originally 1544-400)<br />
189
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
118. Lavatories - Unisex Restroom to the Right on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />
space).<br />
Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />
34” max. height to rim or counter above floor surface.<br />
29” min. clearance from bottom of apron to floor surface.<br />
27” high x 8” deep knee clearance under front lip.<br />
30” wide x 9” high x 17” deep clearance from front of lavatory.<br />
Drain and piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under lavatory.<br />
Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />
5 lb. max. force required to operate controls.<br />
Areas not meeting new construction standards:<br />
18” minimum from center of fixture to side wall or partition. (17”.)<br />
Recommendation:<br />
Replace/Install accessible lavatory.<br />
190
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-118-1 (originally 1545-400)<br />
191
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
119. Accessories - Unisex Restroom to the Right on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #116 and #117 for additional recommendations. Soap dispenser - 44-12” / paper towel dispenser - 45” /<br />
seat cover dispenser - 48” / toilet paper dispenser - 43”.<br />
Areas noted in compliance:<br />
40” maximum height to bottom of reflective surface of mirror.<br />
Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />
A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />
A maximum of 5 lbs. force is required to operate mechanisms.<br />
Areas not meeting new construction standards:<br />
40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />
recepatacles, etc.). (See memo.)<br />
height above floor surface is recom-<br />
Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />
mended). (Hook - 66”.)<br />
Recommendation:<br />
Install accessible coat hook.<br />
Relocate the soap dispenser.<br />
Relocate the paper towel dispenser / hand dryer.<br />
192
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-119-1 (originally 1546-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-119-2 (originally 1547-400)<br />
193
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
120. Water Fountains (Drinking) - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
32” minimum wide and 18” minimum deep alcove provided.<br />
18” minimum depth of fountain.<br />
27” high x 8” deep clear knee space under fountain.<br />
9” high x 17” deep toe clearance.<br />
Lever or push bar control is located 6” max. from front edge.<br />
Bubbler outlet is 6” maximum from front.<br />
Bubbler outlet is 36” maximum from floor.<br />
4” minimum height of stream.<br />
Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty<br />
bending or stooping.<br />
Areas not meeting new construction standards:<br />
Stream of bubbler is parallel to front edge. (On angle.)<br />
The force required to activate controls does not exceed 5lbf. (6 lbs.)<br />
Recommendation:<br />
Adjust water pressure of existing fountain.<br />
Adjust angle of stream.<br />
194
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-120-1 (originally 1548-400)<br />
195
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
121. Controls, Operating Mechanisms & Vending Machines. - 2nd Floor<br />
Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fire extinguisher cabinet.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-121-1 (originally 1549-400)<br />
196
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
122. Seating, Tables and Work Surfaces - 2nd Floor Corridor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />
27” high, 30” wide and 19” deep knee clearance provided.<br />
28” - 34” height of table or work surface that is 36” wide.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-122-1 (originally 1550-400)<br />
197
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
123. Controls, Operating Mechanisms & Vending Machines. - 2nd Floor<br />
Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Copy machine.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-123-1 (originally 1551-400)<br />
198
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
124. Visual/Audible Alarms - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-124-1 (originally 1552-400)<br />
199
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
125. Electrical Controls & Receptacles/Fire Alarm Boxes - 2nd Floor<br />
Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />
max. above the floor or working platform.<br />
The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />
or working platform.<br />
The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the<br />
floor level to the highest point of the activating handle or lever of the box.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-125-1 (originally 1553-400)<br />
200
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-125-2 (originally 1554-400)<br />
201
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
126. Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
15 lb. maximum pressure to operate fire doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-126-1 (originally 1555-400)<br />
202
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-126-2 (originally 1556-400)<br />
203
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
127. Clear Space at Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-127-1 (originally 1557-400)<br />
204
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-127-2 (originally 1558-400)<br />
205
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
128. Signage - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-128-1 (originally 1559-400)<br />
206
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
129. Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (7 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-129-1 (originally 1565-400)<br />
207
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-129-2 (originally 1566-400)<br />
208
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
130. Clear Space at Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-130-1 (originally 1567-400)<br />
209
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-130-2 (originally 1568-400)<br />
210
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
131. Signage - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
211
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-131-1 (originally 1569-400)<br />
212
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
132. Seating, Tables and Work Surfaces - Room #204 on the 2nd Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />
27” high, 30” wide and 19” deep knee clearance provided.<br />
28” - 34” height of table or work surface that is 36” wide.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-132-1 (originally 1570-400)<br />
213
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
133. Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
5 lb. maximum pressure to operate interior doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-133-1 (originally 1571-400)<br />
214
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-133-2 (originally 1572-400)<br />
215
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
134. Clear Space at Doors - Behind Room #204 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (3” to chair.)<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (0” to furniture.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-134-1 (originally 1573-400)<br />
216
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-134-2 (originally 1574-400)<br />
217
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
135. Signage - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-135-1 (originally 1575-400)<br />
218
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
136. Sales and Service Counters - Room #205 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and;<br />
Areas not meeting new construction standards:<br />
Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and; (25” high.)<br />
Recommendation:<br />
Cut skirt on the counter to comply with knee clearance.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-136-1 (originally 1576-400)<br />
219
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
137. Sinks - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Required clear space adjoins or overlaps an accessible route.<br />
Sink is a maximum of 6-1/2” deep.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
34” maximum height of rim or counter above floor surfaces. (34-1/2” high.)<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink. (15” deep.)<br />
Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />
Recommendation:<br />
Replace/Install accessible sink.<br />
Insulate pipes under lavatory (or sink when applicable).<br />
Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />
220
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-137-1 (originally 1577-400)<br />
221
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
138. Controls, Operating Mechanisms & Vending Machines. - Room<br />
#205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-138-1 (originally 1580-400)<br />
222
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-138-2 (originally 1581-400)<br />
223
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
139. Controls, Operating Mechanisms & Vending Machines. - Room<br />
#205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. See Sequence #140 for recommendation.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (58-1/2”.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-139-1 (originally 1582-400)<br />
224
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
140. Seating, Tables and Work Surfaces - Room #205 on the 2nd Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. Relocate the flammable box.<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />
28” - 34” height of table or work surface that is 36” wide.<br />
Areas not meeting new construction standards:<br />
27” high, 30” wide and 19” deep knee clearance provided. (2” deep.)<br />
Recommendation:<br />
Replace the fume hood with an accessible fume hood workstation.<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-140-1 (originally 1583-400)<br />
225
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
141. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-141-1 (originally 1584-400)<br />
226
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
142. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Emergency eyewash.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-142-1 (originally 1585-400)<br />
227
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
143. Aisles - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
36” minimum width of aisles. (21” - 27”.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-143-1 (originally 1586-400)<br />
228
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-143-2 (originally 1587-400)<br />
229
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
144. Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Three doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (7 - 8 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-144-1 (originally 1588-400)<br />
230
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-144-2 (originally 1589-400)<br />
231
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
145. Clear Space at Doors - Rooms #205 and #206 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Three doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-145-1 (originally 1590-400)<br />
232
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-145-2 (originally 1591-400)<br />
233
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
146. Signage - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
234
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-146-1 (originally 1592-400)<br />
235
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
147. Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-147-1 (originally 1593-400)<br />
236
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-147-2 (originally 1594-400)<br />
237
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
148. Clear Space at Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (5” to the table.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-148-1 (originally 1595-400)<br />
238
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-148-2 (originally 1596-400)<br />
239
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
149. Signage - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
240
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-149-1 (originally 1597-400)<br />
241
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
150. Sales and Service Counters - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Work counter.<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-150-1 (originally 1600-400)<br />
242
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
151. Sinks - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Required clear space adjoins or overlaps an accessible route.<br />
34” maximum height of rim or counter above floor surfaces.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
Sink is a maximum of 6-1/2” deep. (10” deep.)<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink. (25” high.)<br />
Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />
Recommendation:<br />
Replace/Install accessible sink.<br />
Insulate pipes under lavatory (or sink when applicable).<br />
Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />
243
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-151-1 (originally 1601-400)<br />
244
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
152. Controls, Operating Mechanisms & Vending Machines. - Room<br />
#206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-152-1 (originally 1602-400)<br />
245
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
153. Controls, Operating Mechanisms & Vending Machines. - Room<br />
#206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-153-1 (originally 1603-400)<br />
246
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-153-2 (originally 1604-400)<br />
247
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
154. Controls, Operating Mechanisms & Vending Machines. - Room<br />
#206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. See Sequence #155 for recommendation.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63” high.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-154-1 (originally 1605-400)<br />
248
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
155. Seating, Tables and Work Surfaces - Room #206 on the 2nd Floor<br />
at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />
space.<br />
Areas not meeting new construction standards:<br />
28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />
Recommendation:<br />
Replace the fume hood with an accessible fume hood workstation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-155-1 (originally 1606-400)<br />
249
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
156. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-156-1 (originally 1607-400)<br />
250
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
157. Aisles - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
36” minimum width of aisles. (30” - 33”.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-157-1 (originally 1608-400)<br />
251
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-157-2 (originally 1609-400)<br />
252
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
158. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Emergency eye wash.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-158-1 (originally 1610-400)<br />
253
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
159. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
MB RO B-G machine.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (15” projection.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-159-1 (originally 1611-400)<br />
254
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
160. Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Two doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (11 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-160-1 (originally 1612-400)<br />
255
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-160-2 (originally 1613-400)<br />
256
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
161. Clear Space at Doors - Rooms #222 and #219 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (3” - 4” to shelves.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-161-1 (originally 1614-400)<br />
257
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-161-2 (originally 1615-400)<br />
258
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
162. Signage - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
259
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-162-1 (originally 1616-400)<br />
260
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
163. Sales and Service Counters - Rooms #222 and #219 on the 2nd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-163-1 (originally 1619-400)<br />
261
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
164. Sinks - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Required clear space adjoins or overlaps an accessible route.<br />
34” maximum height of rim or counter above floor surfaces.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
Sink is a maximum of 6-1/2” deep. (10” deep.)<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink. (24” high.)<br />
Drain and hot water piping is insulated or configured to prevent contact. (None.)<br />
Recommendation:<br />
Replace/Install accessible sink.<br />
Insulate pipes under lavatory (or sink when applicable).<br />
Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />
262
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-164-1 (originally 1620-400)<br />
263
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
165. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-165-1 (originally 1622-400)<br />
264
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-165-2 (originally 1623-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-165-3 (originally 1624-400)<br />
265
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
166. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (58” high x 60”<br />
high.)<br />
Recommendation:<br />
Relocate existing paper towel dispenser.<br />
Lower the machine.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-166-1 (originally 1625-400)<br />
266
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-166-2 (originally 1626-400)<br />
267
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
167. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. See Sequence #168 for recommendation.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63” high.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-167-1 (originally 1627-400)<br />
268
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
168. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the<br />
2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />
space.<br />
Areas not meeting new construction standards:<br />
28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />
Recommendation:<br />
Replace the fume hood with an accessible fume hood workstation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-168-1 (originally 1628-400)<br />
269
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
169. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-169-1 (originally 1629-400)<br />
270
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
170. Aisles - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
36” minimum width of aisles. (29” - 35”.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-170-1 (originally 1630-400)<br />
271
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
171. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Emergency eyewash.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />
Recommendation:<br />
Modify, relocate, replace or remove restricting objects.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-171-1 (originally 1631-400)<br />
272
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
172. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the<br />
2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />
28” - 34” height of table or work surface that is 36” wide.<br />
Areas not meeting new construction standards:<br />
30” x 48” min. clear floor space is provided.<br />
27” high, 30” wide and 19” deep knee clearance provided. (28” wide.)<br />
Recommendation:<br />
Provide accessible table.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-172-1 (originally 1632-400)<br />
273
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
173. Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Three doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (8 - 10 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-173-1 (originally 1633-400)<br />
274
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-173-2 (originally 1634-400)<br />
275
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
174. Clear Space at Doors - Rooms #218 and #221 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-174-1 (originally 1635-400)<br />
276
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-174-2 (originally 1636-400)<br />
277
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
175. Signage - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />
Recommendation:<br />
Relocate existing signage.<br />
278
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-175-1 (originally 1637-400)<br />
279
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
176. Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Four office doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
5 lb. maximum pressure to operate interior doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-176-1 (originally 1638-400)<br />
280
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
177. Clear Space at Doors - Rooms #202, #203, #225 and #224 on the<br />
2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Four office doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PUSH side of door: 0”.<br />
Areas not meeting new construction standards:<br />
60” min. clear space in direction of door swing. (Varies.)<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (Varies.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-177-1 (originally 1639-400)<br />
281
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
178. Signage - Rooms #202, #203, #225 and #224 on the 2nd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Four office doors.<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (55”.)<br />
Recommendation:<br />
Relocate existing signage.<br />
282
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-178-1 (originally 1640-400)<br />
283
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
179. Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
32” minimum clear width of doorway. (31” wide.)<br />
5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall).<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-179-1 (originally 1641-400)<br />
284
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-179-2 (originally 1642-400)<br />
285
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
180. Clear Space at Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-180-1 (originally 1643-400)<br />
286
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-180-2 (originally 1644-400)<br />
287
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
181. Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-181-1 (originally 1645-400)<br />
288
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
182. Tactile Exit Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />
exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />
appropriate. (Improper wording.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-182-1 (originally 1645-400)<br />
289
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
183. Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-183-1 (originally 1646-400)<br />
290
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-183-2 (originally 1647-400)<br />
291
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
184. Clear Space at Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd<br />
Floor.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-184-1 (originally 1648-400)<br />
292
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-184-2 (originally 1649-400)<br />
293
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
185. Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right.<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-185-1 (originally 1650-400)<br />
294
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
186. Tactile Exit Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd<br />
Floor.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Each grade-level exterior exit door shall be identified by a tactile sign with the word ”EXIT”. (No sign.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-186-1 (originally 1651-400)<br />
295
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
187. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-187-1 (originally 1652-400)<br />
296
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-187-2 (originally 1653-400)<br />
297
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
188. Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd<br />
Floor.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-188-1 (originally 1654-400)<br />
298
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-188-2 (originally 1655-400)<br />
299
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
189. Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (No door sign.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-189-1 (originally 1656-400)<br />
300
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
190. Tactile Exit Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd<br />
Floor.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />
exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />
appropriate. (Improper wording.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-190-1 (originally 1657-400)<br />
301
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
191. Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (12 lbs.)<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-191-1 (originally 1658-400)<br />
302
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-191-2 (originally 1659-400)<br />
303
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
192. Clear Space at Doors - Unisex Restroom on the Left on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />
to the water closet.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-192-1 (originally 1660-400)<br />
304
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-192-2 (originally 1661-400)<br />
305
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
193. Identification Symbols, Restrooms - Unisex Restroom on the Left on<br />
the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />
contrasts with the door, light on dark background or dark on light background. (No signage.)<br />
Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />
Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />
identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />
Recommendation:<br />
Install door-mounted sign on single door.<br />
Install wall-mounted sign at single entrance.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-193-1 (originally 1662-400)<br />
306
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
194. Single Accommodation Toilet - Unisex Restroom on the Left on the<br />
3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Space for 30” x 48” wheelchair to enter and permit door to close.<br />
Privacy lock, push button, lever release.<br />
28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />
the water closet to opposite wall or partition.<br />
18” between centerline of water closet and side wall or partition. (18-1/2” (within dimensional tolerance).)<br />
42” min. clearance between centerline of water closet and opposite wall.<br />
A minimum 60” wide and 48” deep clear floor space is provided in front of water closet.<br />
The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />
(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />
44” max. height to flush valve.<br />
Flush valve is on wide side of the water closet<br />
5 lb. max. force is required to operate the flush valve.<br />
19” min. height to toilet paper dispenser.<br />
Toilet paper dispenser provides continuous flow.<br />
Areas not meeting new construction standards:<br />
60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />
into the required clear space. (50”.)<br />
Front of toilet paper dispenser is within 36” of the back wall. (37”.)<br />
The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />
seat. (Above grab bar.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />
307
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-194-1 (originally 1663-400)<br />
308
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
195. Toilet Grab Bars - Unisex Restroom on the Left on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #194 for additional recommendations.<br />
Areas noted in compliance:<br />
1-1/4” to 1-1/2” diameter of bars.<br />
1-1/2” clearance between bars and each wall or partition.<br />
The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />
(33-3/4”.)<br />
The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />
tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-3/4”.)<br />
Side bar has 42” min. length.<br />
Side bar begins a max. of 12” from back wall.<br />
Back bar has 36” min. length.<br />
Back bar begins a max. of 6” from side wall.<br />
Bars are smooth with a min. edge radius of 1/8”.<br />
Grab bars do not rotate within their fittings.<br />
Min. structural strength to support 250 lb. point load.<br />
Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />
Areas not meeting new construction standards:<br />
The front of the side grab bar extends 54” from back wall in single accommodation stall. (51-1/2”.)<br />
Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />
items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-1/2”.)<br />
Recommendation:<br />
Relocate grab bar.<br />
Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />
309
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-195-1 (originally 1663-400)<br />
310
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
196. Lavatories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />
space).<br />
Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />
29” min. clearance from bottom of apron to floor surface.<br />
27” high x 8” deep knee clearance under front lip.<br />
30” wide x 9” high x 17” deep clearance from front of lavatory.<br />
Drain and piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under lavatory.<br />
Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />
5 lb. max. force required to operate controls.<br />
Areas not meeting new construction standards:<br />
18” minimum from center of fixture to side wall or partition. (17-1/4”.)<br />
34” max. height to rim or counter above floor surface. (34-1/4”.)<br />
Recommendation:<br />
Replace/Install accessible lavatory.<br />
311
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-196-1 (originally 1664-400)<br />
312
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
197. Accessories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
See Sequence #194 and #195 for additional recommendations. Soap dispenser - 43” / paper towel dispenser - 45” / seat<br />
cover dispenser - 48” / toilet paper dispenser - 42-1/4”.<br />
Areas noted in compliance:<br />
40” maximum height to bottom of reflective surface of mirror.<br />
Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />
A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />
A maximum of 5 lbs. force is required to operate mechanisms.<br />
Areas not meeting new construction standards:<br />
40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />
recepatacles, etc.). (See memo.)<br />
height above floor surface is recom-<br />
Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />
mended). (66-1/2”.)<br />
Recommendation:<br />
Install accessible coat hook.<br />
Relocate the soap dispenser.<br />
Relocate the paper towel dispenser / hand dryer.<br />
313
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-197-1 (originally 1666-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-197-2 (originally 1667-400)<br />
314
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
198. Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-198-1 (originally 1671-400)<br />
315
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-198-2 (originally 1672-400)<br />
316
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
199. Clear Space at Doors - Unisex Restroom on the Right on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Areas not meeting new construction standards:<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />
to the water closet.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-199-1 (originally 1673-400)<br />
317
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-199-2 (originally 1674-400)<br />
318
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
200. Identification Symbols, Restrooms - Unisex Restroom on the Right<br />
on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />
contrasts with the door, light on dark background or dark on light background. (No signage.)<br />
Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />
Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />
identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />
Recommendation:<br />
Install door-mounted sign on single door.<br />
Install wall-mounted sign at single entrance.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-200-1 (originally 1675-400)<br />
319
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
201. Single Accommodation Toilet - Unisex Restroom on the Right on the<br />
3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Space for 30” x 48” wheelchair to enter and permit door to close.<br />
Privacy lock, push button, lever release.<br />
28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />
the water closet to opposite wall or partition.<br />
18” between centerline of water closet and side wall or partition.<br />
42” min. clearance between centerline of water closet and opposite wall.<br />
The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />
(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />
44” max. height to flush valve.<br />
Flush valve is on wide side of the water closet<br />
5 lb. max. force is required to operate the flush valve.<br />
19” min. height to toilet paper dispenser.<br />
Toilet paper dispenser provides continuous flow.<br />
Areas not meeting new construction standards:<br />
60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />
into the required clear space. (50”.)<br />
A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44”.)<br />
Front of toilet paper dispenser is within 36” of the back wall. (37-1/2”.)<br />
The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />
seat. (13” and above grab bar.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />
320
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-201-1 (originally 1676-400)<br />
321
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
202. Toilet Grab Bars - Unisex Restroom on the Right on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #201 for additional recommendations.<br />
Areas noted in compliance:<br />
1-1/4” to 1-1/2” diameter of bars.<br />
1-1/2” clearance between bars and each wall or partition.<br />
The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />
(33-1/2”.)<br />
The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />
tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2”.)<br />
Side bar has 42” min. length.<br />
Side bar begins a max. of 12” from back wall.<br />
Back bar has 36” min. length.<br />
Back bar begins a max. of 6” from side wall.<br />
Bars are smooth with a min. edge radius of 1/8”.<br />
Grab bars do not rotate within their fittings.<br />
Min. structural strength to support 250 lb. point load.<br />
Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />
Areas not meeting new construction standards:<br />
The front of the side grab bar extends 54” from back wall in single accommodation stall. (52”.)<br />
Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />
items are allowed). (Toilet paper dispenser - 8” / seat cover dispenser - 5-1/2”.)<br />
Recommendation:<br />
Relocate grab bar.<br />
Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />
322
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-202-1 (originally 1677-400)<br />
323
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
203. Lavatories - Unisex Restroom on the Right on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />
space).<br />
Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />
34” max. height to rim or counter above floor surface.<br />
29” min. clearance from bottom of apron to floor surface.<br />
27” high x 8” deep knee clearance under front lip.<br />
30” wide x 9” high x 17” deep clearance from front of lavatory.<br />
Drain and piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under lavatory.<br />
Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />
5 lb. max. force required to operate controls.<br />
Areas not meeting new construction standards:<br />
18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />
Recommendation:<br />
Replace/Install accessible lavatory.<br />
324
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-203-1 (originally 1679-400)<br />
325
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
204. Accessories - Unisex Restroom on the Right on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
See Sequence #201 and #202 for additional recommendations.<br />
Areas noted in compliance:<br />
40” maximum height to bottom of reflective surface of mirror.<br />
Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />
A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />
A maximum of 5 lbs. force is required to operate mechanisms.<br />
Areas not meeting new construction standards:<br />
40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />
recepatacles, etc.). (Soap dispenser - 44-1/2” / paper towels - 45” / seat covers - 48” / toilet paper - 42-1/2”.)<br />
height above floor surface is recom-<br />
Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />
mended). (66-1/2”.)<br />
Recommendation:<br />
Install accessible coat hook.<br />
Relocate the paper towel dispenser / hand dryer.<br />
Relocate the soap dispenser.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-204-1 (originally 1680-400)<br />
326
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-204-2 (originally 1681-400)<br />
327
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
205. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex<br />
Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />
max. above the floor or working platform.<br />
The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />
or working platform.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-205-1 (originally 1682-400)<br />
328
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-205-2 (originally 1683-400)<br />
329
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
206. Corridors - 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
44” minimum width for occupant loads of 10 or more.<br />
Corridors over 200’ must have ONE of: 60” minimum clear width,<br />
and 60” x 60” turning space at central location, or,<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-206-1 (originally 1684-400)<br />
330
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-206-2 (originally 1685-400)<br />
331
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
207. Water Fountains (Drinking) - Corridor on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
32” minimum wide and 18” minimum deep alcove provided.<br />
18” minimum depth of fountain.<br />
27” high x 8” deep clear knee space under fountain.<br />
9” high x 17” deep toe clearance.<br />
Lever or push bar control is located 6” max. from front edge.<br />
Bubbler outlet is 6” maximum from front.<br />
Bubbler outlet is 36” maximum from floor.<br />
4” minimum height of stream.<br />
Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty<br />
bending or stooping.<br />
Areas not meeting new construction standards:<br />
Stream of bubbler is parallel to front edge. (On angle.)<br />
The force required to activate controls does not exceed 5lbf. (7 lbs.)<br />
Recommendation:<br />
Adjust angle of stream.<br />
Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />
332
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-207-1 (originally 1686-400)<br />
333
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
208. Controls, Operating Mechanisms & Vending Machines. - Corridor on<br />
the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fire extinguisher.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-208-1 (originally 1687-400)<br />
334
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
209. Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
15 lb. maximum pressure to operate fire doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-209-1 (originally 1688-400)<br />
335
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-209-2 (originally 1689-400)<br />
336
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
210. Clear Space at Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
One set of double doors.<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-210-1 (originally 1690-400)<br />
337
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-210-2 (originally 1691-400)<br />
338
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
211. Signage - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-211-1 (originally 1692-400)<br />
339
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
212. Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (8 - 10 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-212-1 (originally 1693-400)<br />
340
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-212-2 (originally 1694-400)<br />
341
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
213. Clear Space at Doors - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-213-1 (originally 1695-400)<br />
342
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-213-2 (originally 1696-400)<br />
343
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
214. Signage - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />
Recommendation:<br />
Relocate existing signage.<br />
344
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-214-1 (originally 1697-400)<br />
345
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
215. Sales and Service Counters - Rooms #321 and #318 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-215-1 (originally 1699-400)<br />
346
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
216. Sinks - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
Required clear space adjoins or overlaps an accessible route.<br />
34” maximum height of rim or counter above floor surfaces.<br />
Sink is a maximum of 6-1/2” deep.<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink.<br />
Drain and hot water piping is insulated or configured to prevent contact.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
347
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-216-1 (originally 1700-400)<br />
348
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
217. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-217-1 (originally 1701-400)<br />
349
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-217-2 (originally 1702-400)<br />
350
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
218. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knob.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-218-1 (originally 1703-400)<br />
351
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-218-2 (originally 1704-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-218-3 (originally 1705-400)<br />
352
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
219. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. See Sequence #220 for recommendation.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63” high.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-219-1 (originally 1706-400)<br />
353
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
220. Seating, Tables and Work Surfaces - Rooms #321 and #318 on the<br />
3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />
27” high, 30” wide and 19” deep knee clearance provided.<br />
Areas not meeting new construction standards:<br />
28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />
Recommendation:<br />
Replace the fume hood with an accessible fume hood workstation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-220-1 (originally 1707-400)<br />
354
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
221. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Eight fume hoods.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-221-1 (originally 1708-400)<br />
355
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
222. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Two emergency eyewash controls.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-222-1 (originally 1709-400)<br />
356
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
223. Aisles - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
36” minimum width of aisles. (32”.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-223-1 (originally 1710-400)<br />
357
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
224. Floors and Levels - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Four carpets / mats.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)<br />
Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not fastened.)<br />
Recommendation:<br />
Secure loose doormat.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-224-1 (originally 1711-400)<br />
358
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
225. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Shelf on machine.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (9”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-225-1 (originally 1712-400)<br />
359
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
226. Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Three doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (7 - 11 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-226-1 (originally 1713-400)<br />
360
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-226-2 (originally 1714-400)<br />
361
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
227. Clear Space at Doors - Rooms #319 and #317 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-227-1 (originally 1715-400)<br />
362
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-227-2 (originally 1716-400)<br />
363
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
228. Signage - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />
Recommendation:<br />
Relocate existing signage.<br />
364
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-228-1 (originally 1717-400)<br />
365
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
229. Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (9 - 10 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-229-1 (originally 1718-400)<br />
366
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-229-2 (originally 1719-400)<br />
367
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
230. Clear Space at Doors - Rooms #307 and #304 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-230-1 (originally 1720-400)<br />
368
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-230-2 (originally 1721-400)<br />
369
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
231. Signage - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />
Recommendation:<br />
Relocate existing signage.<br />
370
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-231-1 (originally 1722-400)<br />
371
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
232. Sales and Service Counters - Rooms #307 and #304 on the 3rd<br />
Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />
A minimum 30” x 48” clear floor space is provided at the counter and;<br />
One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-232-1 (originally 1724-400)<br />
372
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
233. Sinks - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />
Required clear space adjoins or overlaps an accessible route.<br />
34” maximum height of rim or counter above floor surfaces.<br />
There are no sharp or abrasive elements under sink.<br />
Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />
Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />
5 lb. maximum force required to activate controls.<br />
Areas not meeting new construction standards:<br />
Sink is a maximum of 6-1/2” deep. (10” deep.)<br />
Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />
sink. (24” high.)<br />
Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />
Recommendation:<br />
Replace/Install accessible sink.<br />
Insulate pipes under lavatory (or sink when applicable).<br />
373
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-233-1 (originally 1725-400)<br />
374
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
234. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-234-1 (originally 1726-400)<br />
375
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-234-2 (originally 1727-400)<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-234-3 (originally 1728-400)<br />
376
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
235. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Various machines.<br />
Areas noted in compliance:<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-235-1 (originally 1729-400)<br />
377
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-235-2 (originally 1730-400)<br />
378
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
236. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />
#307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood. See Sequence #237 for recommendation.<br />
Areas noted in compliance:<br />
Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />
require tight grasping, pinching or twisting of the wrist to operate.<br />
Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />
Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />
Areas not meeting new construction standards:<br />
Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63”.)<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-236-1 (originally 1731-400)<br />
379
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
237. Seating, Tables and Work Surfaces - Rooms #307 and #304 on the<br />
3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
30” x 48” min. clear floor space is provided.<br />
One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />
space.<br />
Areas not meeting new construction standards:<br />
27” high, 30” wide and 19” deep knee clearance provided. (0” deep.)<br />
28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />
Recommendation:<br />
Replace the fume hood with an accessible fume hood workstation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-237-1 (originally 1732-400)<br />
380
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
238. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Fume hood.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-238-1 (originally 1733-400)<br />
381
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
239. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Two eyewash controls.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-239-1 (originally 1734-400)<br />
382
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
240. Aisles - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
36” minimum width of aisles. (32”.)<br />
Recommendation:<br />
Requires engineering/architectural evaluation.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-240-1 (originally 1736-400)<br />
383
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
241. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Shelf on machine.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />
or aisles if lower edge of object is above 27” and below 80”. (9”.)<br />
Recommendation:<br />
Install cane detectable barrier below object.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-241-1 (originally 1737-400)<br />
384
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
242. Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Three doors.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate interior doors. (8 - 10 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-242-1 (originally 1738-400)<br />
385
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-242-2 (originally 1739-400)<br />
386
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
243. Clear Space at Doors - Rooms #306 and #305 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-243-1 (originally 1740-400)<br />
387
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-243-2 (originally 1741-400)<br />
388
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
244. Signage - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />
Recommendation:<br />
Relocate existing signage.<br />
389
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-244-1 (originally 1742-400)<br />
390
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
245. Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
No access into Room #324 due to radioactivity in progress.<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
5 lb. maximum pressure to operate interior doors.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-245-1 (originally 1748-400)<br />
391
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-245-2 (originally 1749-400)<br />
392
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
246. Clear Space at Doors - Rooms #323, #324, #303 and #302 on the<br />
3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PUSH side of door: 0”.<br />
Areas not meeting new construction standards:<br />
60” min. clear space in direction of door swing. (Varies.)<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (Varies.)<br />
Recommendation:<br />
Relocate furniture to provide clear space.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-246-1 (originally 1750-400)<br />
393
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-246-2 (originally 1751-400)<br />
394
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
247. Signage - Rooms #323, #324, #303 and #302 on the 3rd Floor at<br />
<strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />
Raised characters are 5/8” to 2” high.<br />
Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />
Braille dots are raised a minimum 1/40” above the background.<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />
on the right.<br />
Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />
standing w/in the swing of a door.<br />
Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />
Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />
Areas not meeting new construction standards:<br />
Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />
Recommendation:<br />
Relocate existing signage.<br />
395
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-247-1 (originally 1752-400)<br />
396
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
248. Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
32” minimum clear width of doorway. (31” wide.)<br />
5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Replace door and frame (concrete or block wall).<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-248-1 (originally 1753-400)<br />
397
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-248-2 (originally 1754-400)<br />
398
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
249. Clear Space at Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-249-1 (originally 1755-400)<br />
399
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-249-2 (originally 1756-400)<br />
400
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
250. Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (No door sign.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-250-1 (originally 1757-400)<br />
401
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
251. Tactile Exit Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />
exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />
appropriate. (Improper wording.)<br />
Recommendation:<br />
Provide compliant sign.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-251-1 (originally 1757-400)<br />
402
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
252. Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Opens a min. of 90 degrees.<br />
1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />
32” minimum clear width of doorway.<br />
Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />
Hardware is 30” to 44” above floor.<br />
3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />
Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />
opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />
Areas not meeting new construction standards:<br />
5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />
Recommendation:<br />
Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-252-1 (originally 1758-400)<br />
403
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-252-2 (originally 1759-400)<br />
404
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
253. Clear Space at Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong><br />
<strong>Annex</strong>.<br />
Memo:<br />
Areas noted in compliance:<br />
Floor or landing is level and clear (2% max. slope).<br />
60” min. clear space in direction of door swing.<br />
44” min. clear space opposite direction of door swing (48” with latch and closer).<br />
Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />
Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />
Areas not meeting new construction standards:<br />
None observed.<br />
Recommendation:<br />
None.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-253-1 (originally 1760-400)<br />
405
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-253-2 (originally 1761-400)<br />
406
University of California at Riverside<br />
Site Evaluation Survey<br />
Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />
900 University Avenue<br />
254. Signage - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />
Memo:<br />
No signage.<br />
Areas noted in compliance:<br />
None observed.<br />
Areas not meeting new construction standards:<br />
Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />
leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />
the right. (None.)<br />
Recommendation:<br />
Install permanent ID sign to latch side of door.<br />
Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-254-1 (originally 1762-400)<br />
407