12V<br />

DC<br />

Static<br />

Pressure<br />

Pressure<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch<br />

inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

0 0 470 280 2,3 480 280 2,5 0 0 0 0<br />

2,5 0,1 440 260 2,4 430 250 2,5 2,5 0,1 0 0<br />

5,0 0,2 420 250 2,5 370 220 2,5 5,0 0,2 0 0<br />

7,5 0,3 375 220 2,6 330 190 2,5 7,5 0,3 0 0<br />

10,0 0,4 285 170 2,6 270 160 2,6 10,0 0,4 0 0<br />

12,5 0,5 240 140 2,8 170 100 2,8 12,5 0,5 0 0<br />

15,0 0,6 180 110 2,9 120 70 2,9 15,0 0,6 0 0<br />

17,5 0,7 <strong>130</strong> 80 3,0 80 50 2,9 17,5 0,7 0 0<br />

20,0 0,8 70 40 3,1 50 30 3,0 20,0 0,8 0 0<br />

22,5 0,9 35 20 3,2 20 10 3,1 22,5 0,9 0 0<br />

25,0 1,0 0 0 3,3 0 0 3,2 25,0 1,0 0 0<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

�<br />

Test Voltage: 13,0 VOLT DC<br />

AXIAL FANS<br />

F01-12C001-01S Suction - Aspirante<br />

F01-12C001-01B Blowing - Soffiante<br />

SUCTION<br />

Aspirante<br />

BLOWING<br />

Soffiante<br />

Static<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

SUCTION<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.<br />

Test Voltage: 26,0 VOLT DC<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

BLOWING<br />

Aspirante Soffiante<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg


12V<br />

DC<br />

Test Voltage: 13,0 VOLT DC<br />

AXIAL FANS<br />

F01-12C003-01S Suction - Aspirante<br />

F01-12C003-01B Blowing - Soffiante<br />

Soffiante<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch<br />

inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

0 0 340 200 1,10 0 0 0 0 0<br />

2,5 0,1 295 170 1,15 0 2,5 0,1 0 0<br />

5,0 0,2 220 <strong>130</strong> 1,15 0 5,0 0,2 0 0<br />

7,5 0,3 115 70 1,25 0 7,5 0,3 0 0<br />

10,0 0,4 75 40 1,35 0 10,0 0,4 0 0<br />

12,5 0,5 0 0 1,45 0 12,5 0,5 0 0<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,37 Kg<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.<br />

Test Voltage: 26,0 VOLT DC<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

Static SUCTION BLOWING<br />

Static SUCTION BLOWING<br />

Pressure Aspirante<br />

WEIGHT 0,37 Kg<br />

LOW NOISE<br />

�<br />

Pressure<br />

Aspirante<br />

Soffiante<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm


12V<br />

DC<br />

Test Voltage: 13,0 VOLT DC<br />

�����������<br />

��������������������������������������<br />

��������������������������������������<br />

���������<br />

�� �������� �������� �������� �������� �������� �������� �� �������� �������� �������� ������� �������� �������<br />

����<br />

����<br />

��� ���� ����� ���� ���� ����� ����� ��� ���� ����� ���� ���� ����� ����<br />

� � ��� ��� ��� ��� ��� ��� � � � �<br />

��� ��� ��� ��� ��� ��� ��� ��� ��� ��� � �<br />

��� ��� ��� ��� ��� ��� ��� ��� ��� ��� � �<br />

��� ��� ��� ��� ��� ��� ��� ��� ��� ��� � �<br />

���� ��� ��� ��� 2,6 ��� ��� ��� ���� ��� � �<br />

���� ��� ��� ��� ��� ��� ��� ��� ���� ��� � �<br />

���� ��� ��� ��� ��� ��� �� ��� ���� ��� � �<br />

���� ��� ��� �� ��� �� �� ��� ���� ��� � �<br />

���� ��� �� �� ��� �� �� ��� ���� ��� � �<br />

���� ��� �� �� ��� �� �� ��� ���� ��� � �<br />

���� ��� � � ��� � � ��� ���� ��� � �<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

���������������<br />

���������<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “2H”.<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “2H”.<br />

������������������������������<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

�������� ������� ������� �������� ������� �������<br />

�������� ���������<br />

���������������<br />

���������<br />

�<br />

��������<br />

���������<br />

���������<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm


12V<br />

DC<br />

Static<br />

Pressure<br />

Pressure<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

0 0 340 200 1,10 0 0 0 0 0<br />

2,5 0,1 295 170 1,15 0 2,5 0,1 0 0<br />

5,0 0,2 220 <strong>130</strong> 1,15 0 5,0 0,2 0 0<br />

7,5 0,3 115 70 1,25 0 7,5 0,3 0 0<br />

10,0 0,4 75 40 1,35 0 10,0 0,4 0 0<br />

12,5 0,5 0 0 1,45 0 12,5 0,5 0 0<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,37 Kg<br />

LOW NOISE<br />

�<br />

Test Voltage: 13,0 VOLT DC<br />

SUCTION<br />

Aspirante<br />

AXIAL FANS<br />

F02-12C003-01S Suction - Aspirante<br />

F02-12C003-01B Blowing - Soffiante<br />

BLOWING<br />

Soffiante<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.<br />

Test Voltage: 26,0 VOLT DC<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

Static SUCTION BLOWING<br />

Aspirante Soffiante<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,37 Kg<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.


12V<br />

DC<br />

Pressure Aspirante Soffiante<br />

Pressure Aspirante<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

0 0 430 250 2,50 0 0 0 0 0<br />

2,5 0,1 390 230 2,60 0 2,5 0,1 0 0<br />

5,0 0,2 355 210 2,65 0 5,0 0,2 0 0<br />

7,5 0,3 315 190 2,70 0 7,5 0,3 0 0<br />

10,0 0,4 230 140 2,70 0 10,0 0,4 0 0<br />

12,5 0,5 165 100 2,80 0 12,5 0,5 0 0<br />

15,0 0,6 125 70 2,90 0 15,0 0,6 0 0<br />

17,5 0,7 90 50 3,00 0 17,5 0,7 0 0<br />

20,0 0,8 55 30 3,05 0 20,0 0,8 0 0<br />

22,5 0,9 0 0 3,20 0 22,5 0,9 0 0<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

�<br />

AXIAL FANS<br />

F08-12C001-01S Suction - Aspirante<br />

F08-12C001-01B Blowing - Soffiante<br />

Test Voltage: 13,0 VOLT DC<br />

Static SUCTION BLOWING<br />

Static<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

Test Voltage: 26,0 VOLT DC<br />

SUCTION<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

BLOWING<br />

Soffiante<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.


12V<br />

DC<br />

Static<br />

Pressure<br />

F08-12C003-01S Suction - Aspirante<br />

F08-12C003-01B Blowing - Soffiante<br />

Test Voltage: 13,0 VOLT DC<br />

SUCTION<br />

Aspirante<br />

AXIAL FANS<br />

BLOWING<br />

Soffiante<br />

FAN DIAMETER<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch<br />

inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

24V<br />

DC<br />

0 0 335 200 1,10 0 0 0 0 0<br />

2,5 0,1 290 170 1,20 0 2,5 0,1 0 0<br />

5,0 0,2 210 120 1,20 0 5,0 0,2 0 0<br />

7,5 0,3 120 70 1,25 0 7,5 0,3 0 0<br />

10,0 0,4 75 40 1,35 0 10,0 0,4 0 0<br />

12,5 0,5 30 20 1,40 0 12,5 0,5 0 0<br />

15,0 0,6 0 0 1,50 0 15,0 0,6 0 0<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

�<br />

Static<br />

Pressure<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

Diametro Ventola<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.<br />

Test Voltage: 26,0 VOLT DC<br />

SUCTION<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.<br />

BLOWING<br />

Aspirante Soffiante<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm


12V<br />

DC<br />

Static<br />

Pressure<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

0 0 430 250 2,50 0 0 0 0 0<br />

2,5 0,1 390 230 2,60 0 2,5 0,1 0 0<br />

5,0 0,2 355 210 2,65 0 5,0 0,2 0 0<br />

7,5 0,3 315 190 2,70 0 7,5 0,3 0 0<br />

10,0 0,4 230 140 2,70 0 10,0 0,4 0 0<br />

12,5 0,5 165 100 2,80 0 12,5 0,5 0 0<br />

15,0 0,6 125 70 2,90 0 15,0 0,6 0 0<br />

17,5 0,7 90 50 3,00 0 17,5 0,7 0 0<br />

20,0 0,8 55 30 3,05 0 20,0 0,8 0 0<br />

22,5 0,9 0 0 3,20 0 22,5 0,9 0 0<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

�<br />

Test Voltage: 13,0 VOLT DC<br />

SUCTION<br />

Aspirante<br />

AXIAL FANS<br />

F09-12C001-01S Suction - Aspirante<br />

F09-12C001-01B Blowing - Soffiante<br />

BLOWING<br />

Soffiante<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

Static SUCTION BLOWING<br />

Pressure<br />

Test Voltage: 26,0 VOLT DC<br />

Aspirante Soffiante


12V<br />

DC<br />

Pressure Aspirante Soffiante<br />

Pressure Aspirante<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

0 0 335 200 1,10 0 0 0 0 0<br />

2,5 0,1 290 170 1,20 0 2,5 0,1 0 0<br />

5,0 0,2 210 120 1,20 0 5,0 0,2 0 0<br />

7,5 0,3 120 70 1,25 0 7,5 0,3 0 0<br />

10,0 0,4 75 40 1,35 0 10,0 0,4 0 0<br />

12,5 0,5 30 20 1,40 0 12,5 0,5 0 0<br />

15,0 0,6 0 0 1,50 0 15,0 0,6 0 0<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

�<br />

AXIAL FANS<br />

F09-12C003-01S Suction - Aspirante<br />

F09-12C003-01B Blowing - Soffiante<br />

Test Voltage: 13,0 VOLT DC<br />

Static SUCTION BLOWING<br />

Static<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

Test Voltage: 26,0 VOLT DC<br />

SUCTION<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

BLOWING<br />

Soffiante<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.


12V<br />

DC<br />

�������� ��������� ��������� �������� ���������<br />

�� �������� �������� �������� �������� �������� �������� �� �������� �������� �������� ������� �������� �������<br />

���� ����<br />

��� ���� ����� ���� ���� ����� ����� ��� ���� ����� ���� ���� ����� ����<br />

� � ��� ��� ��� ��� ��� ��� � � � �<br />

��� ��� ��� ��� ��� ��� ��� ��� ��� ��� � �<br />

��� ��� ��� ��� ��� ��� ��� ��� ��� ��� � �<br />

��� ��� ��� ��� ��� ��� ��� ��� ��� ��� � �<br />

���� ��� ��� ��� 2,6 ��� ��� ��� ���� ��� � �<br />

���� ��� ��� ��� ��� ��� ��� ��� ���� ��� � �<br />

���� ��� ��� ��� ��� ��� �� ��� ���� ��� � �<br />

���� ��� ��� �� ��� �� �� ��� ���� ��� � �<br />

���� ��� �� �� ��� �� �� ��� ���� ��� � �<br />

���� ��� �� �� ��� �� �� ��� ���� ��� � �<br />

���� ��� � � ��� 0 � 3,2 ���� ��� � �<br />

���������������<br />

���������<br />

�<br />

�����������<br />

��������������������������������������<br />

��������������������������������������<br />

Test Voltage: 13,0 VOLT DC<br />

�������� ������� ������� ��������<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

���������<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

������������������������������<br />

�������<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “2H”.<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

�������<br />

���������<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

���������������<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “2H”.<br />

F17-12C001-01S 01.xls


12V<br />

DC<br />

Static<br />

Pressure<br />

<strong>mm</strong> Airflow Airflow Current Airflow Airflow Current <strong>mm</strong> Airflow Airflow Current Airflow Airflow Current<br />

inch inch<br />

H2O m3/h cfm/h Amp. m3/h cfm/h Amp . H2O m3/h cfm/h Amp. m3/h cfm/h Amp.<br />

0 0 340 200 1,10 0 0 0 0 0<br />

2,5 0,1 295 170 1,15 0 2,5 0,1 0 0<br />

5,0 0,2 220 <strong>130</strong> 1,15 0 5,0 0,2 0 0<br />

7,5 0,3 115 70 1,25 0 7,5 0,3 0 0<br />

10,0 0,4 75 40 1,35 0 10,0 0,4 0 0<br />

12,5 0,5 0 0 1,45 0 12,5 0,5 0 0<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

�<br />

Test Voltage: 13,0 VOLT DC<br />

SUCTION<br />

Aspirante<br />

AXIAL FANS<br />

F17-12C003-01S Suction - Aspirante<br />

F17-12C003-01B Blowing - Soffiante<br />

BLOWING<br />

Soffiante<br />

For the Axial Fans exposed to the water, mounted with motor-up and blade-down, we reco<strong>mm</strong>end to require the<br />

2 holes for the water discharge on the blade hub. At the end of the fan description please write “ 2H”.<br />

Per Elettroventole esposte all’acqua, e montate con il motore sopra e la ventola sotto, si raccomanda di chiedere<br />

i 2 fori di drenaggio sul mozzo della ventola. Aggiungere alla fine della descrizione prodotto la sigla “ 2H”.<br />

Static Pressure: 1 <strong>mm</strong> H2O = 0,04 inch H2O 1 <strong>mm</strong> H2O = 9,8 Pa<br />

Airflow rate: 1 m3/h = 0,59 cfm<br />

WEIGHT 0,42 Kg<br />

LOW NOISE<br />

The dimensions are in <strong>mm</strong>. ( 25,4 <strong>mm</strong>. = 1 inch )<br />

FAN DIAMETER<br />

24V<br />

DC<br />

Diametro Ventola<br />

<strong>130</strong> <strong>mm</strong>.<br />

5 inch<br />

Static SUCTION BLOWING<br />

Pressure<br />

Test Voltage: 26,0 VOLT DC<br />

Aspirante Soffiante

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!