1-12 About the <strong>Very</strong> <strong>High</strong> <strong>Speed</strong> <strong>Counter</strong> <strong>Module</strong>s<br />

Store Count Mode 4: Store-Reset/Start<br />

In mode 4, the rising edge of a pulse input on the Z Gate/Reset<br />

terminal will store the current counter value in the Stored/<br />

Accumulated Count word and reset the counter to zero. The counter<br />

will continue counting while the Z Gate/Reset terminal is high. The<br />

stored count information will remain until it is overwritten with new<br />

data.<br />

Store-Reset/Start<br />

Start Counting<br />

Store Count,<br />

and Reset to zero<br />

Continue Counting<br />

Output Control<br />

To connect an output to a compare window, the user could program<br />

the module accordingly:<br />

• Tie Output 0 to Window 0<br />

• Program Window 0 ON Value to 2000<br />

• Program Window 0 OFF Value to 5000<br />

ON-OFF Operation of Output 0<br />

Output remains energized for 3000 additional counts<br />

Output turns ON at count value of 2000 Output turns OFF at count value of 5000<br />

If the OFF value is greater than the ON value, the output turns ON at<br />

2000 and OFF at 5000. If the ON value is greater than the OFF value,<br />

the output turns OFF at 2000 and ON at 5000.<br />

Publication 1734-UM003A-EN-P - August 2000