1-10 About the <strong>Very</strong> <strong>High</strong> <strong>Speed</strong> <strong>Counter</strong> <strong>Module</strong>s<br />
Operating Mode Features<br />
The following table summarizes which features are active in each<br />
mode:<br />
Operating Feature<br />
<strong>Counter</strong><br />
Up / Down<br />
Encoder<br />
X1, X2 & X4<br />
Period<br />
/Rate<br />
Continuous<br />
/Rate<br />
Rate<br />
Measurement<br />
PWM<br />
Preset Y Y N N N N<br />
Rollover Y Y N N N N<br />
Software Reset Y Y Y Y Y Y<br />
Store Count -<br />
Z Gate / Reset<br />
4 modes<br />
Scale Input Count at<br />
Z Gate / Reset<br />
Y Y N N N N<br />
N N Y Y N N<br />
Z Gate / Reset Invert Bit Y Y Y Y N N<br />
Enable /Force Outputs Y Y Y Y Y Y<br />
Assign Outputs Y Y Y Y Y Y<br />
Operate Outputs<br />
(Based On)<br />
Y<br />
(Count)<br />
Y<br />
(Count)<br />
Y<br />
(Count)<br />
Y<br />
(Count)<br />
Y<br />
(Count)<br />
Y<br />
(PWM Value)<br />
Sample Period N N N N Y Y<br />
Operating Mode Features<br />
The Z Gate/Reset Terminal will operate in one of four modes when<br />
the Store Count feature is in use. The four figures below detail the<br />
operation in each mode.<br />
Store Count Mode 1: Store/Continue<br />
In mode 1, the rising edge of a pulse input on the Z Gate/Reset<br />
terminal will cause the current counter value to be read and stored in<br />
the Read Data file. The counter will continue counting. The stored<br />
count will be available in the Stored/Accumulated Count word. The<br />
stored count information will remain until it is overwritten with new<br />
data.<br />
Store/Continue<br />
Read, Store Count,<br />
and Continue Counting<br />
Publication 1734-UM003A-EN-P - August 2000