About the <strong>Very</strong> <strong>High</strong> <strong>Speed</strong> <strong>Counter</strong> <strong>Module</strong>s 1-3<br />
[B = <strong>High</strong>, Count = Down; B = Low or floating (not connected), Count<br />
= Up]<br />
The Channel B input may be tied high or low for unidirectional<br />
counting, or toggled for bidirectional counting.<br />
EXAMPLE<br />
Example of <strong>Counter</strong> Mode<br />
Single Phase Pulse Generator<br />
A Input<br />
B Direction<br />
Z (Store Count)<br />
(Gate / Reset )<br />
Input A<br />
Input B<br />
Input Z<br />
1734-VHSC<br />
Count Up<br />
Count Down<br />
A Input<br />
B Input<br />
Count<br />
0<br />
1 2 3<br />
2 1 0<br />
Outputs<br />
Updated<br />
Continuously<br />
Encoder Modes<br />
The encoder mode reads incoming pulses and returns a binary<br />
number (0 - 16,777,215 max ) to the PointBus. The encoder mode only<br />
accepts 2 phase quadrature inputs. The module senses the<br />
relationship between the 2 phases, and counts up or down<br />
accordingly.<br />
There are two basic encoder types, absolute and incremental. A<br />
single output incremental encoder is called a tachometer encoder. A<br />
dual channel incremental encoder with one channel leading the other<br />
by 90° is called a quadrature encoder.<br />
A system using a quadrature encoder may include an optional zero<br />
pulse, or index, serving as a reference mark for system reset. The<br />
principal disadvantage of a system using incremental encoders is that<br />
a power interruption causes the loss of position reference, so a system<br />
must be reinitialized or returned to a known zero position.<br />
Publication 1734-UM003A-EN-P - August 2000