The activation magnet is mounted at the front of the<br />

breaker and is equipped with a grounded casing.<br />

The drive includes a self-interrupt control circuit (SUcontrol).<br />

This circuit enables a short activation with a<br />

minimum command duration of approximately<br />

300ms, causes the voltage applied to the magnet to<br />

be switched off after approximately 400ms and prevents,<br />

during continuous operation, repeated activation<br />

(anti-pumping) due to an existing short circuit. In<br />

addition, the switch-in mechanism is electrically<br />

blocked for approximately 10s after activation. This<br />

prevents premature activation following a short circuit.<br />

The breaker is equipped with up to ten isolated<br />

form C auxiliary contacts (1 NO/NC each). The<br />

auxiliary contacts are activated by the movable main<br />

contact. They are wired to 15-pin control plugs. As<br />

an accessory the circuit breaker can be equipped<br />

with auxiliary switches for indication of short circuit<br />

tripping and for the presence of the arc chute.<br />

2. Installation and Operation<br />

2.1 Transportation<br />

The circuit breaker must always be transported to<br />

the installation site properly and fully packed. The<br />

packaging protects the device against damage and<br />

dust; it should only be removed prior to installation.<br />

If the packaging is damaged, the breaker and the<br />

arc chute must be inspected for damage. Ensure<br />

that all packaging materials have been carefully removed<br />

prior to breaker installation.<br />

2.2 Installation<br />

The breakers, as delivered, are IP00 protected.<br />

They must be installed in a dry, preferably dust-free<br />

room. They must not be subjected to strong vibrations.<br />

The lower and upper connections must be<br />

connected directly to the main cables and busbars.<br />

The breaker must only be used in an upright<br />

operation position with the arc chute in place<br />

and fully secured. After installation, both the arc<br />

chute and special threaded joints must be checked<br />

for tightness.<br />

The safety distances as shown in the dimensional<br />

drawings must be maintained to grounded or insulated<br />

parts. Suitable measures must be taken to<br />

protect personnel from arcs.<br />

Strong, external magnetic fields, caused by<br />

improperly located supply conductors or stray fields<br />

from other devices, can lead to a shift of the trip setting<br />

thresholds. This may result in premature tripping,<br />

or no tripping at al, during low-level short circuit<br />

current events. This has to be accounted for<br />

when installing and operating the device with<br />

shielding added if appropriate.<br />

The control wires must be connected as shown in<br />

the schematic circuit diagram [Fig.8].<br />

The protective grounding wire must be connected at<br />

the marked contact.<br />

2.3 Setting the Overload Release<br />

The adjustment of the static overload release [Fig.1]<br />

within a specific adjustment range is made by turning<br />

the regulating screw. This procedure requires an<br />

SW6 hexagon wrench. The adjustment must only be<br />

carried out after the breaker has been disconnected<br />

from the main circuit and has been grounded. Turning<br />

the adjustment screw clockwise decreased the<br />

trip threshold, turning the screw counter-clockwise<br />

increased the tripping threshold.<br />

Adjustment is performed by aligning both the arrow<br />

and the marking line to one line.<br />