7. Gerapid 2607/4207 - Current measurement system type SEL<br />

SEL–TheintegratedSolution<br />

Themainpurposeofthehighspeed<strong>DC</strong>circuitbreaker<br />

typeGerapidistheinterruptionofservicecurrentsand<br />

protection of mains against short circuit.. Current<br />

measuringrequirestheinstallationofexternaldevices<br />

e.g. shunt –buffer amplifier which needs mounting<br />

timeaswellasadditionalspace.<br />

Now the Gerapid offers the new feature – current<br />

measuring with the sophisticated current<br />

measurementsystem TypeSEL06-1....12-4<br />

Theadvantagescomparedwith theconventional<br />

systemsare<br />

thetransducerisintegratedin theGerapid<br />

noadditionalassemblywork<br />

noadditionalmountingspace<br />

low noisemeasur ing without anyfiltering<br />

ranges 6kAand 12kA<br />

3differentinterfaces<br />

applicableupto4000V<strong>DC</strong><br />

!<br />

!<br />

!<br />

!<br />

!<br />

Theoscillogramsbelowshowthehighaccuracyofthe<br />

current measurement system type SEL in comparison<br />

with the conventional method using ashunt -buffer<br />

amplifier.<br />

MeasurementwithShunt-BufferAmplifier<br />

1200<br />

1000<br />

800<br />

600<br />

400<br />

200<br />

0<br />

-200<br />

0 100 200 300 400 500 600<br />

Time t [ms]<br />

Measurementwith CurrentMeasurement<br />

SystemType SEL<br />

1200<br />

1000<br />

800<br />

600<br />

400<br />

200<br />

0<br />

-200<br />

0 100 200 300 400 500 600<br />

Time t [ms]<br />

Structure<br />

ThecurrentmeasurementsystemTypeSEL06-1...12-4<br />

consists of the components sensor and signal<br />

processingunit.<br />

Hall probes record the the magnetic field surrounding<br />

the current. The special design and the high<br />

performance shielding minimise the influence of<br />

interference.<strong>High</strong>build-upofcurrentisrecordedinreal<br />

time.<br />

Thesensorisintegratedintoaspeciallydesignedupper<br />

terminal of the Gerapid and connected by ascreened<br />

cablewiththesignalprocessingunit.<br />

This signal processing unit transfers the input signal<br />

whichisproportionaltothecurrentsignalintodifferent<br />

outputsignals.<br />

Theusercanselectbetweentheinterfaces<br />

!<br />

!<br />

!<br />

Technical Data<br />

Type SEL 06-1 06-2 06-4 12-1 12-2 12-4<br />

Input -6 to 6 kA -12 to 12kA<br />

U Ne[V] 1000 2000 4000 1000 2000 4000<br />

Relating to rated current<br />

I Ne<br />

4...20mA,<br />

+/-20mA,<br />

+/-10V<br />

All interfaces are potential free. Phase failures are<br />

automaticallydetectedundindicatedbyazero-signal<br />

onthe4...20mAoutput.<br />

Output<br />

4...20mA<br />

-20...20mA<br />

-10...10V<br />

U Ni[kV] 12 18 40 12 18 40<br />