Expert Power Control NET - Manual - Gude Analog
Expert Power Control NET - Manual - Gude Analog
Expert Power Control NET - Manual - Gude Analog
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Expert</strong> <strong>Power</strong><br />
<strong>Control</strong> <strong>NET</strong><br />
<strong>Expert</strong> <strong>Power</strong> <strong>Control</strong> <strong>NET</strong><br />
1<br />
<strong>Expert</strong> <strong>Power</strong> <strong>Control</strong> <strong>NET</strong> IEC<br />
CONTACT<br />
<strong>Manual</strong><br />
<strong>Gude</strong> <strong>Analog</strong>- und Digitalsysteme<br />
GmbH<br />
Eintrachtstraße 113<br />
50668 Köln<br />
Germany<br />
tel.: +49-221-912 90 97<br />
fax: +49-221-912 90 98<br />
e-mail: info@<strong>Gude</strong>.info<br />
web: www.<strong>Gude</strong>.info<br />
TABLE OF CONTENTS<br />
After having modified the IP settings EPC <strong>NET</strong><br />
can be switched by all PCs of the same network 2 SWITCHING VIA ETHER<strong>NET</strong><br />
via the website http://”IP address of EPC <strong>NET</strong>“/<br />
1 OPENING INSTRUCTIONS<br />
(e.g. http://192.168.0.2/).<br />
Log in to the website http://”IP address of EPC<br />
<strong>NET</strong>”/ (e.g. http://192.168.0.2/). It might be<br />
1.1 Connection<br />
necessary to enter a password (see 3). Now<br />
1.2 IP Settings<br />
1.2 IP SETTINGS<br />
EPC <strong>NET</strong> can be switched.<br />
2 SWITCHING VIA ETHER<strong>NET</strong><br />
3 CONFIGURATION<br />
4 PRODUCT FEATURES<br />
4.1 Operating modi<br />
4.2 Changing of switching state<br />
4.3 Firmware Update<br />
4.4 Default settings<br />
4.5 LED<br />
4.6 Technical data<br />
FAQs<br />
1 OPENING INSTRUCTIONS<br />
1.1 CONNECTION<br />
<strong>Expert</strong> <strong>Power</strong> <strong>Control</strong> <strong>NET</strong> (EPC <strong>NET</strong>) must<br />
be connected to an electric circuit and the<br />
desired ethernet.<br />
For product version EPC <strong>NET</strong> IEC connect the<br />
device with enclosed IEC appliance connector<br />
as follows:<br />
Connection for device (female)<br />
Connection electric circuit (male)<br />
When EPC <strong>NET</strong> is connected to an electric<br />
circuit the LED at the front side shines red.<br />
When EPC <strong>NET</strong> is additionally connected to an<br />
existing ethernet, the green LED of the LAN<br />
jack shines.<br />
It is necessary that an IP address is allocated<br />
for EPC <strong>NET</strong> in order to switch it via ethernet.<br />
The IP address must belong to the desired<br />
subnetwork.<br />
The allocation can be accomplished automatically<br />
by a DHCP server (see 1.2.1) or<br />
manually. For a manual allocation under<br />
Windows we recommend the program<br />
EPCnet_conf.exe 2(see<br />
1.2.2).<br />
1.2.1 Allocation by DHCP server<br />
If there is a DHCP server available in the<br />
network, an unused IP address will be allocated<br />
automatically each time EPC <strong>NET</strong> is restarted<br />
3.<br />
This option can be disabled (see 3) or<br />
modified by an appropriate configuration of the<br />
DHCP server.<br />
1.2.2 Allocation via Windows software<br />
Start EPC <strong>NET</strong> in boot mode (see 4.1) and open<br />
2<br />
the program EPCnet_conf.exe . The program<br />
will look automatically for connected devices<br />
and will display their IP settings.<br />
If the displayed IP address accords with the<br />
default setting (192.168.0.2), there is either no<br />
DHCP server available in the network or no<br />
unsused IP address could be allocated.<br />
IP settings can be modified manually by using the program<br />
EPCnet_conf.exe.<br />
Enter an unused IP address and the gateway of<br />
the desired subnetwork. Save the changes with<br />
Program Device/ SaveConfig.<br />
After having changed the network settings EPC<br />
3<br />
<strong>NET</strong> must be restarted in normal mode (see<br />
4.1.).<br />
After restart click on Search in order to display<br />
the modified IP settings.<br />
Via the website http://”IP address of EPC <strong>NET</strong>”/ (e.g.<br />
http://192.168.1.221/) EPC <strong>NET</strong> can be switched.<br />
Besides there are the following options:<br />
Config<br />
The settings of EPC <strong>NET</strong> can be configured<br />
here (see 3).<br />
Batchmode<br />
Independently from the current switching<br />
state EPC <strong>NET</strong> can be switched on or<br />
switched off for a selectable delay (1-30<br />
sec. or 1-30 min.)<br />
After the chosen delay EPC <strong>NET</strong> will be<br />
switched off or switched on again automatically.<br />
Via Batchmode EPC <strong>NET</strong> can be switched off and<br />
switched on again automatically .<br />
Logout<br />
Only one user can be logged in at the same<br />
time. After three minutes without activity<br />
there will be an automatical log-out.<br />
EPC <strong>NET</strong> can also be switched automatically<br />
at defined times with the help of the command<br />
line tool EPC_<strong>Control</strong>.pl 2 and a taskplanner.<br />
More informations can be found on our website.
3 CONFIGURATION 4 PRODUCT FEATURES<br />
Settings of EPC <strong>NET</strong> can be changed via the<br />
website http://”IP address of EPC <strong>NET</strong>”/ (e.g.<br />
http://192.168.0.2/).<br />
The modification of name and password will<br />
be applied immediately. To apply the modification<br />
of other settings EPC <strong>NET</strong> has to be<br />
restarted 3.<br />
Label<br />
A name with a maximum of 15 characters<br />
can be allocated here.<br />
IP Settings<br />
IP Settings of EPC <strong>NET</strong> can be modified<br />
here.<br />
TCP/IP settings by DHCP<br />
Each time EPC <strong>NET</strong> is restarted 3 it will be<br />
checked if a DHCP server is available in the<br />
network. In this case IP settings will be<br />
requested and saved. If there is no DHCP<br />
server in the network it is advisable to<br />
disable this option.<br />
After <strong>Power</strong>Up switch<br />
The switching state of EPC <strong>NET</strong> after a<br />
restart 3 can be defined here (on, off, last<br />
state).<br />
Password<br />
A password with a maximum of 15<br />
characters can be allocated here if required.<br />
The user name for the password is ”admin”.<br />
The settings of EPC <strong>NET</strong> can be modified in the configuration<br />
menu.<br />
4.1 OPERATING MODI<br />
EPC <strong>NET</strong> can be started in two ways:<br />
Boot mode<br />
To start EPC <strong>NET</strong> in boot mode, the button<br />
at the back or front side must be pushed for<br />
at least two seconds when restarting 3 EPC<br />
<strong>NET</strong>. While EPC <strong>NET</strong> is in boot mode the<br />
LED at the front side blinks red.<br />
By using the program EPCnet_conf.exe 2 it<br />
is possible to disable the password, to<br />
update the firmware and to restore the<br />
default settings.<br />
In boot mode EPC <strong>NET</strong> is not switched. A<br />
change of the switching state is not possible.<br />
Normal mode<br />
After a restart EPC <strong>NET</strong> is automatically in<br />
normal mode .<br />
In normal mode EPC <strong>NET</strong> can be switched<br />
and configured.<br />
4.2 CHANGING OF SWITCHING STATE<br />
A device that is connected to EPC <strong>NET</strong> can be<br />
turned off and on again automatically by using<br />
the batchmode function (see 2).<br />
The current switching state of EPC <strong>NET</strong> can be<br />
changed by pushing the button at the back or<br />
front side for at least three seconds.<br />
4.3 FIRMWARE UPDATE<br />
In order to update the firmware both the program<br />
EPCnet_conf.exe2 and the latest firmware2<br />
are needed.<br />
Start EPC <strong>NET</strong> in boot mode (see 4.1) and open<br />
2<br />
the program EPCnet_conf.exe . On the left<br />
side of the program window all EPC <strong>NET</strong>s that<br />
are in the network are listed. Select the one that<br />
should be updated and click on Program<br />
Device/ Firmware Update .<br />
4.4 DEFAULT SETTINGS<br />
In order to restore the default settings EPC <strong>NET</strong><br />
must be started in boot mode (see 4.1). Besides<br />
that the program EPCnet_conf.exe2 is needed.<br />
When opening the program all EPC <strong>NET</strong>s that<br />
are in the network will be listed on the left side of<br />
the program window. Select the one of which<br />
settings should be restored and click on<br />
Program Device/Format Eeprom.<br />
Please notice<br />
that all current<br />
settings will be<br />
deleted. When<br />
restarting3<br />
EPC <strong>NET</strong> the<br />
next time the<br />
default settings<br />
will be loaded.<br />
After having restored the default settings EPC<br />
<strong>NET</strong> must be put into operation again (see 1).<br />
4.5 LED<br />
EPC <strong>NET</strong> is not connected to an electric<br />
circuit<br />
EPC <strong>NET</strong> is connected to an electric<br />
circuit and is switched off<br />
EPC <strong>NET</strong> is connected to an electric<br />
circuit and is switched on<br />
If the LED blinks red, EPC <strong>NET</strong> is in boot mode<br />
( see 4.1 ).<br />
4.6 TECHNICAL DATA<br />
Default settings<br />
Name: Exp<strong>Power</strong><strong>Control</strong><br />
IP address: 192.168.0.2<br />
Netmask: 255.255.255.0<br />
Gateway: 192.168.0.0<br />
DHCP: enabled<br />
Password: disabled<br />
After restart: switched off<br />
Network connection: 10MBit 10base T<br />
Ethernet<br />
Protocol: TCP/IP<br />
Switched power: max. 2000W<br />
Switched voltage: 230V<br />
Operating temperature: 0°C-50°C<br />
Product version: EPC <strong>NET</strong><br />
Dimensions (LxWxH): 13,5 x 7,5 x 6,5 cm<br />
Weight: approx. 210g<br />
1<br />
Product version: EPC <strong>NET</strong> IEC<br />
Dimensions (LxWxH): 12,0 x 6,4 x 5,5 cm<br />
Weight: approx. 320g<br />
FAQs<br />
Connection<br />
EPC <strong>NET</strong> is connected but...<br />
...the LED doesn’t shine<br />
Please check the connection to the electric<br />
circuit.<br />
...the green LED of the LAN jack doesn’t<br />
shine<br />
Please check the network connection.<br />
...I can’t open the website<br />
Please assure that both EPC <strong>NET</strong> and your PC<br />
are in the same subnetwork.<br />
Where can I find the IP settings of my subnetwork?<br />
Open the Windows MSDOS command prompt<br />
(Start/Accessories/Comand Prompt and Start/<br />
Programs/MSDOSPrompt respectively) and enter the<br />
command line ipconfig/all.<br />
How can I check if EPC <strong>NET</strong> is connected<br />
properly?<br />
2<br />
Open the program EPCnet_conf.exe and click on<br />
Search. If EPC <strong>NET</strong> is connected properly it will be<br />
displayed in the left part of the program window.<br />
Switching<br />
I can’t log in at EPC <strong>NET</strong>’s website<br />
If the message „Access denied. Used by …“ is<br />
displayed another user is logged in at the moment.<br />
Alternatively check the network connection (green<br />
LED at the LAN jack must shine) and assure that<br />
both EPC <strong>NET</strong> and your PC are in the same<br />
subnetwork.<br />
I forgot my password<br />
Restart EPC <strong>NET</strong> in boot mode and open the<br />
2<br />
program EPCnet_conf.exe . Disable the password<br />
protection and restart EPC <strong>NET</strong> in normal mode.<br />
The switching state doesn’t change when<br />
pushing the button<br />
Restart EPC <strong>NET</strong> in normal mode.<br />
Program EPCnet_conf.exe<br />
The program doesn’t find EPC <strong>NET</strong><br />
Check the connection to the electric circuit (LED at<br />
the front side must shine green or red) and the<br />
network (green LED at the LAN jack must shine).<br />
1 product version EPC <strong>NET</strong> IEC for IEC appliance<br />
connector. Operation is the same as for EPC<br />
<strong>NET</strong>.<br />
2 free download on our website www.gude.info<br />
3 restart means seperate and reconnect EPC <strong>NET</strong>