‚þ¹ªþ¸þ<br />

ASHIDA NUMERICAL DIRECTIONAL<br />

3 O/C + <strong>1E</strong>/F <strong>IDMT</strong> <strong>RELAY</strong><br />

Type: ADR145A<br />

(ADITYA Series)<br />

(Preliminary)<br />

LED<br />

RESET<br />

ADR 145A<br />

Features:<br />

• 4 Element (3 Phase + EF) Over current <strong>IDMT</strong><br />

with instant trip.<br />

• Programmable (Non- Volatile) Setting By local<br />

keys as well as remote setting by communication<br />

port.<br />

• Back - lit LCD display for settings.<br />

• Display of fault current. / Load current.<br />

• Selection of Curve: Five selectable curves,<br />

Normal Inverse1 (C1), Normal Inverse2, (C2)<br />

Very inverse (C3), Extremely inverse (C4), Long<br />

time inverse (C5).<br />

• Design using DSP technology<br />

• Latching of fault current.<br />

• Direction OC/EF Characteristic.<br />

• Programmable MTA +30, +45and +60 for phase<br />

and – 14, -30, -45 for EF.<br />

• Pass-word protection for setting.<br />

General:<br />

The ADR145A is member of Ashida Numerical Relay<br />

family (Aditya Series) design to meet demand of low<br />

and medium switchgear control. The ADR145A is a<br />

Directional 3 OC and 1 EF relay with Instantaneous<br />

high set and programmable output to simplify feeder<br />

protection wiring. The ADR145A continuously<br />

monitors all 3 phase and earth current, through CT<br />

connections. The high-speed micro-controller<br />

samples this current through a 12-bit A/D converter.<br />

The micro-controller performs powerful Digital Algorithms to find out Amplitude of current signal,<br />

direction of power flow then this value is use for protection and metering function. All measurement is<br />

tuned to fundamental frequency. Each input current is also displayed on 16 x 2 LCD display for<br />

metering. The Relay is having main three functions 1) Protection 2) Self-Supervision 3) Measurement.<br />

1. Protection Functions:<br />

The ADR145A give maximum benefit/cost ratio. The ADR145A give all the advantage of numerical<br />

relay at affordable cost. Following is summery of different protection functions provided by relay.<br />

ANSI IEC Protection Functions<br />

50 I >> Instantaneous Over current Protection (OC-Inst.)<br />

50N I E >> Instantaneous Earth Fault Protection (EF-Inst.)<br />

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary<br />

slightly from that indicated above.<br />

ASHIDA ELECTRONICS PVT LTD.<br />

Plot No. A-308, Road No. 21,<br />

Wagle Industrial Estate,<br />

Thane (W)-400 604. INDIA.<br />

E-mail: sales@ashidaelectronics.com<br />

Web: www.ashidaelectronics.com<br />

Ref.: ADR145A<br />

Issue : 05 09.06.07<br />

Page 1 / 6


Type: ADR145A<br />

(ADITYA Series)<br />

(Preliminary)<br />

51 I>t, Ip Time Over current Protection (Phase) (OC-<strong>IDMT</strong>.)<br />

51N I E >t, I EP Time Over current Protection (Earth) (EF-<strong>IDMT</strong>.)<br />

67 I dir >, I dir >> I pdir Directional Time over current protection, Phase<br />

67N I Edir >, I Edir >> I Edir Directional Time over current protection, EF<br />

1.1. Over current / EF protection:<br />

The ADR145A has 4 sensing element 3 OC and 1 EF. The tripping current can be set from 50% to<br />

200% for phase and 5% to 80% for Earth fault in steps of 1% by Keys switch provided on front<br />

panel. The unit has got selection of <strong>IDMT</strong> characteristic of international IEC standard Very inverse /<br />

Extremely Inverse / Long Inverse and Standard inverse (both 3.0 sec and 1.3sec at 10 times). The<br />

unit also has Time Multiplier Setting (TMS) from x0.01 to x1.0 for <strong>IDMT</strong> delay multiplication. The<br />

instantaneous tripping function is having range of 100% - 3000% for phase and 100% - 1200% for<br />

EF and can be set in steps of 100%. The high speed CPU continuously monitor the all four current<br />

inputs and compare with <strong>IDMT</strong> as well as instantaneous setting. If any one current is above<br />

instantaneous setting the relay provide immediate trip command bypassing <strong>IDMT</strong> delay. If is input<br />

current is less than instantaneous setting but more than <strong>IDMT</strong> setting, CPU calculate <strong>IDMT</strong> delay as<br />

per selected <strong>IDMT</strong> characteristic multiply it with TMS setting and provide trip command if fault is<br />

persist even after this time delay. All the 4 elements are voltage polarised. That means the<br />

<strong>IDMT</strong> elements can be made directional or non-directional via. Key board setting.<br />

All the settings are password protected to prevent unauthorised change.<br />

1.2. Extra Alarm Contact:<br />

Any Protection panel required extra contacts for provide visual ALARM and ANNUNCIATION<br />

indication for operator. Also some status contacts for SCADA or remote indications. Usually<br />

separate electromechanical relay used for contact multiplication of protection relay contacts. This<br />

added extra wiring and extra hardware. The ADR141A provide separate programmable ALARM<br />

contact for such application. Maximum 4 nos. of extra contacts can be provided. These contacts can<br />

be programmed as follows<br />

Function ANN1 ANN2 ANN3 ANN4<br />

Type 1 OC1 OC2 EF OC3<br />

Type 2 OC–<strong>IDMT</strong> OC-Inst. EF-<strong>IDMT</strong> EF-Inst.<br />

2. Supervision Function:<br />

2.1. Self-supervision:<br />

The continuously keeping track on its internal hardware and the movement it detect any failure of<br />

any component, it give message on LCD display, This feature is very useful to give pre information<br />

to avoid any mall - operation. In such situation it use some default setting and remain in protection<br />

mode.<br />

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary<br />

slightly from that indicated above.<br />

ASHIDA ELECTRONICS PVT LTD.<br />

Plot No. A-308, Road No. 21,<br />

Wagle Industrial Estate,<br />

Thane (W)-400 604. INDIA.<br />

E-mail: sales@ashidaelectronics.com<br />

Web: www.ashidaelectronics.com<br />

Ref.: ADR145A<br />

Issue : 05 09.06.07<br />

Page 2 / 6


Type: ADR145A<br />

(ADITYA Series)<br />

(Preliminary)<br />

3. Measurement Function:<br />

In normal condition this display shows all settings. Via keyboard the display can be program to show<br />

the actual current flowing through the relay. If current excesses set value the relay gives trip<br />

command. The type of fault is displayed on LCD display. During the fault condition the relay<br />

measure the fault current and store in non-volatile memory. The fault current can be read via<br />

keyboard on LCD display Last 3 fault values along with tripping counter can be view via keyboard.<br />

All settings are save in Electrically erasable read only memory and remain.<br />

Ordering Information:<br />

While Ordering Specify the following Information for ADR145A Relay<br />

Definition of Model No of Aditya Series of Relays<br />

AM XXX–XX – X – X – XX – X<br />

Reserved for Future Use<br />

PT Secondary<br />

1 = 63.5V ac<br />

2 = 110V ac<br />

3 = 230V ac<br />

CT Secondary<br />

1 = 1 Amp.<br />

2 = 5 Amp.<br />

3 = 1 Amp. / 5 Amp. Selectable<br />

Auxiliary Supply<br />

01 = 18 – 52 V dc 06 = 110 V dc<br />

02 = 77 – 250 V dc 07 = 220 V dc<br />

03 = 24 V dc<br />

04 = 30 V dc<br />

05 = 48 V dc<br />

AM XXX XX X<br />

3OC + <strong>1E</strong>F Relays<br />

001 01 Relay without extra contacts, With site selectable CT. CSD – 150 3<br />

02 Relay with 4 extra contacts, two contact for LBB & site<br />

selectable CT.<br />

CSD – 150 3<br />

Ordering information :<br />

A D R 1 4 5 A - A M - X X X - X X - X - X - X X - X<br />

Example<br />

ADR145A – AM-001-02-3-0-02-0<br />

Type : ADR145A<br />

Back Terminal Layout : Relay with extra contact - - -<br />

Cabinet Type : CSD-150 non Drawout<br />

CT sec : 5 Amp.<br />

Auxiliary Supply : 77 - 250 V dc<br />

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary<br />

slightly from that indicated above.<br />

ASHIDA ELECTRONICS PVT LTD.<br />

Plot No. A-308, Road No. 21,<br />

Wagle Industrial Estate,<br />

Thane (W)-400 604. INDIA.<br />

E-mail: sales@ashidaelectronics.com<br />

Web: www.ashidaelectronics.com<br />

Ref.: ADR145A<br />

Issue : 05 09.06.07<br />

Page 3 / 6


Technical Specifications:<br />

Sr. No. Specification Particulars<br />

Type: ADR145A<br />

(ADITYA Series)<br />

(Preliminary)<br />

I. CT Inputs : Suitable for CT secondary 1.0 Amp or 5.0 Amp. (To be specified.)<br />

II. PT Input : Suitable for PT secondary of 110Vac<br />

III.<br />

Protection Relay Setting<br />

Range<br />

MTA setting<br />

: For Phase - 50 - 200 % in step of 1%.<br />

: For EF - 5 - 80 % in step of 1%<br />

: Phase Instantaneous: - 100 - 3000% in steps of 100% and bypass<br />

: EF Instantaneous: - 100 to 1200% in steps of 100%.<br />

: Phase - +30 , +45 & +60 or non directional<br />

: EF - -10 , +30 ,-45 ,–60 or non directional<br />

IV. Pickup Current : Within 1.1 times of set current value.<br />

V. Resetting Current : Within 90% of set value.<br />

VI. Operating Time : Time: 5 selectable <strong>IDMT</strong> curve C1, to C5.<br />

: Instantaneous Time < 40ms on 2 times current of setting.<br />

VII. Time Accuracy : Within class 2.5 As per IS: 3231.<br />

VIII. Burden on CTs : Less than 0.2VA.<br />

IX. Aux. Supply : 18 - 52VDC or 77 - 250VDC. To be specified while ordering.<br />

X. Burden on Aux. Supply : Less than 10VA on any supply.<br />

XI. Control Contacts : 2 NO contacts (SR ) are given for Trip & Annunciation. - Trip Duty<br />

XII. Contact Rating Trip Duty : Make and carry for 3sec. – 7500VA with max. 30A & 660VAC/DC<br />

: Make and carry for continuous - 1250VA with max. 5A & 660VAC/DC<br />

: Break AC - 1250 VA DC - 100 W resistive 50W inductive.<br />

XIII.<br />

XIV.<br />

Operational Indicators (Flags)<br />

ON<br />

FAULT<br />

PKP<br />

TRIP<br />

Thermal Withstand<br />

Capacity<br />

XV. High Voltage Test : IEC 60255-5<br />

: Green LED indicates Relay OK<br />

: In case of following condition led become off<br />

1. Problem in relay Hardware.<br />

2. Auxiliary supply is not sufficient for relay operation.<br />

: Red LED’s indicates the OC/EF relay trip, Hand Reset (HR) Type.<br />

: Red LED indicates OC/EF relay Pickup.<br />

: Indicates that Trip pulse is being executed. When BYPASS P.B. is<br />

pressed, actual trip is not executed.<br />

: x40 times the normal current for 3sec.<br />

: x2 Continuous<br />

: Except DC Voltage – 2.0 kV (RMS), 50Hz<br />

: Only DC voltage - 2.8 kV DC<br />

: Between Open contact of TRIP / CLOSE 1.5kV (RSM) 50Hz<br />

: Between Open contact of ALARM – 1kV (RSM) 50Hz<br />

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary<br />

slightly from that indicated above.<br />

ASHIDA ELECTRONICS PVT LTD.<br />

Plot No. A-308, Road No. 21,<br />

Wagle Industrial Estate,<br />

Thane (W)-400 604. INDIA.<br />

E-mail: sales@ashidaelectronics.com<br />

Web: www.ashidaelectronics.com<br />

Ref.: ADR145A<br />

Issue : 05 09.06.07<br />

Page 4 / 6


Type: ADR145A<br />

(ADITYA Series)<br />

(Preliminary)<br />

XVI.<br />

Impulse Voltage Test (all<br />

circuit class – III)<br />

: IEC60255-5<br />

: 5kV (peak) 1.2 / 50us, 0.5 J, 3 positive and 3 negative impulse at interval of<br />

5 sec<br />

XVII. High Frequency test : IEC 60255-22-1, Class III<br />

: 2.5 kV (peak) 1MHz , τ = 15µs 400 surges / s duration 2 s<br />

XVIII. Electro static Discharge : IEC 60255-22-2 Class III and IEC 61000-4-2 class III<br />

: 4kV/6kV contact discharge, 8kV air discharge, both polarities 150pF, Ri 330<br />

Ω<br />

XIX.<br />

XX.<br />

Irradiation with radio<br />

frequency field, pulsemodulated,<br />

Fast transient<br />

interference/bursts<br />

: IEC 60255-22-3 and IEC 61000-4-2 class III<br />

: 10V/m; 80 to 1000MHz; 80%; 1kHz AM<br />

: IEC 60255-22-3 and IEC 61000-4-3, class III<br />

: 4kV; 5/50ns; 5kHz burst duration = 15ms;<br />

: Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.<br />

XXI. Shock Test : IEC 60255-21-2 class 1<br />

: Semi-Sinusoidal<br />

: 5g acceleration, duration 11ms,<br />

: Each 3 shocks in both direction of the 3 axes<br />

XXII. Vibration Test : IEC 60255-21-1 class 1 / IEC 60068-2-6<br />

: Sinusoidal 10 to 60Hz ±0.035 mm<br />

: Amplitude, 60 to 150Hz, 0.5g acceleration<br />

: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal<br />

XXIII. Seismic Test : IEC 60255-21-3<br />

: In single axis sine sweep in X-axis<br />

1. sweep (@a sweep rate of 1 octave/minute) vibration in the frequency<br />

range (5-40 Hz) at amplitude of 3.5mm or 1.0gn (whichever is less)<br />

: In single axis sine sweep in Y-axis<br />

1. - weep (@a sweep rate of 1 octave/minute) vibration in the frequency<br />

range (5-40 Hz) at amplitude of 1.5mm or 0.5gn (whichever is less)<br />

XXIV. Bump Test : IEC 60255-21-2 Class-1<br />

: 1000 bumps of 10gn peak acceleration and 16ms pulse duration in each of<br />

the two opposite direction per axis as per IEC60255-21-2 class 1 No. of<br />

axes . 3.<br />

XXV. Shock Withstand : IEC 60255-21-2 Clas-1<br />

: 3 shocks of 15gn peak acceleration and 11ms pulse in each of two opposite<br />

direction . No. of axis : 3<br />

XXVI. Shock Response Test : IEC 60255-21-2 Clas-1<br />

: 3 shocks of 1gn peak acceleration and 11ms pulse in each of two opposite<br />

direction . No. of axis : 3<br />

XXVII. Vibration Endurance Test : IEC60255-21-1<br />

20-sweeps (@ a sweep rate of 1octave / minutes) vibration in the frequency<br />

range (10-150Hz) at 1 gn (9,8m/s2) acceleration in each of the 3 mutually<br />

perpendicular axes<br />

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary<br />

slightly from that indicated above.<br />

ASHIDA ELECTRONICS PVT LTD.<br />

Plot No. A-308, Road No. 21,<br />

Wagle Industrial Estate,<br />

Thane (W)-400 604. INDIA.<br />

E-mail: sales@ashidaelectronics.com<br />

Web: www.ashidaelectronics.com<br />

Ref.: ADR145A<br />

Issue : 05 09.06.07<br />

Page 5 / 6


Type: ADR145A<br />

(ADITYA Series)<br />

(Preliminary)<br />

XXVIII.<br />

XXIX.<br />

Environmental withstand : IEC60068-2<br />

(cold, Dry heat & steady Cold – 2 hours operational condition at –(40 +/- 3) deg C as per IEC60068-2-<br />

state Damp Heat)<br />

1<br />

Dry – 2 Hours dry heat operational condition at(55+/2 2 deg. C as per<br />

IEC60068-2-2<br />

Steady state damp heat - 2 hours steady sate damp heat operational<br />

condition at temperature at (55 +/- 2) deg. C & humidity 95% RH as per<br />

IEC60068-2-78<br />

Drawing References : For Cabinet Type CSD -150 (MAC00402)<br />

: For Operating Characteristics C1 - APR02201<br />

C2 - APR01801<br />

C3 - APR05101<br />

C4 - APR05201<br />

C5 - APR05301<br />

: For Electrical Connection & Back Terminal<br />

AM00101<br />

- APD01602<br />

: For Electrical Connection AM00102 - APD01604<br />

: For Back Terminal AM00102 - APD01606<br />

: Directional Characteristics - APR01901<br />

• Datasheet Change Log for ADR145A<br />

Issue No. Date Description /Changes<br />

(Revision)<br />

01 24.12.04 Original Revision<br />

02 15.01.06 Colour Front added<br />

03 23.03.06 Electrical Connection Revised<br />

04 15.04.06 Ordering Information added<br />

04A 09.03.07 Reset value change from 80% ….to 90%<br />

05 09.06-07 IEC Test added<br />

Seismic Test<br />

Bump Test<br />

Shock Withstand<br />

Shock Response Test<br />

Vibration Endurance Test<br />

Environmental withstand (cold, Dry heat & steady state Damp Heat)<br />

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary<br />

slightly from that indicated above.<br />

ASHIDA ELECTRONICS PVT LTD.<br />

Plot No. A-308, Road No. 21,<br />

Wagle Industrial Estate,<br />

Thane (W)-400 604. INDIA.<br />

E-mail: sales@ashidaelectronics.com<br />

Web: www.ashidaelectronics.com<br />

Ref.: ADR145A<br />

Issue : 05 09.06.07<br />

Page 6 / 6