<strong>Roof</strong> <strong>fans</strong><br />
TFDX 315-355<br />
• Speed-controllable<br />
• Integral thermistors<br />
• Vertical exhaust<br />
• Tilting frame included<br />
• Maintenance-free and reliable<br />
The TFDX models have impellers with backward-curved<br />
blades and maintenance-free external rotor motors. The<br />
casing is manufactured in galvanised sheet steel, with a<br />
brass or copper inlet cone. Powder-coated version available<br />
on request. The fan has a tilting mechanism for easy<br />
inspection and servicing. Exhaust air is directed vertically<br />
from the <strong>fans</strong> which prevents problems caused by wet<br />
snow and staining of the roof.<br />
To protect the motor from overheating these <strong>fans</strong> have integral<br />
thermistors with external leads which should be connected<br />
to the TUS 230 KIL motor protection relay.<br />
Explosion proof versions comply with EN 50014 and<br />
50019. Improved safety in accordance with EEx e ll T3.<br />
TFDX 315-4 TFDX 355-4<br />
Voltage/Frequency V/50 Hz 400 400<br />
Phase ~ 3 3<br />
Power W 118 252<br />
Current A 0,23 0,47<br />
Maximum air flow m 3 /s (m 3 /h) 0,42 (1515) 0,66 (2355)<br />
R.p.m. min -1 1350 1375<br />
Ambient temp. °C -20 till +40 -20 till +40<br />
Sound pressure level at 4/10 m dB(A) 44/36 52/44<br />
Weight kg 30 32<br />
Insulation class, motor F F<br />
Enclosure class, motor IP 44 IP 44<br />
Motor protection TUS 230 KIL TUS 230 KIL<br />
Certificate SP Ex 96.D.101X SP Ex 96.D.102X<br />
Speed control, five-step Transformer RTRD 2 + TUS 230 KIL RTRD 2 + TUS 230 KIL<br />
Speed control, five-step high/low Transformer RTRDU 2 + TUS 230 KIL RTRDU 2 + TUS 230 KIL<br />
Wiring diagram p. 11-13 11 11<br />
When using the RTRD or RTRDU together with the TUS 230 KIL, the internal motor protection in the transformer must be strapped<br />
Accessories<br />
TG p. 536 BTG p. 537<br />
234
<strong>Roof</strong> <strong>fans</strong><br />
TFDX 315-4<br />
Mid-frequency band, Hz<br />
Hz Tot 63 125 250 500 1k 2k 4k 8k<br />
L wA Inlet dB(A) 60 51 48 48 55 53 52 47 39<br />
L wA Surrounding dB(A) 67 45 55 61 60 62 58 50 43<br />
With TG 540-800<br />
L wA Inlet dB(A) 54 51 45 42 46 41 44 42 34<br />
With TG 540-1230<br />
L wA Inlet dB(A) 53 51 45 42 41 36 40 41 34<br />
With SSD 355/400<br />
L wA Inlet dB(A) 51 49 43 40 43 34 31 26 21<br />
Measuring point: q v = 0,24 m 3 /s, P s = 152 Pa<br />
TFDX 355-4<br />
Mid-frequency band, Hz<br />
Hz Tot 63 125 250 500 1k 2k 4k 8k<br />
L wA Inlet dB(A) 70 54 57 61 67 62 60 52 44<br />
L wA Surrounding dB(A) 75 51 61 68 70 70 65 56 48<br />
With TG 540-800<br />
L wA Inlet dB(A) 62 54 54 55 58 50 52 47 39<br />
With TG 540-1230<br />
L wA Inlet dB(A) 61 54 54 55 53 45 48 46 39<br />
With SSD 355/400<br />
L wA Inlet dB(A) 59 52 52 53 55 43 39 31 26<br />
Measuring point: q v = 0,39 m 3 /s, P s = 190 Pa<br />
Knock-out ø 23<br />
(electrical connection)<br />
Protection guard: standard on the exhaust<br />
side in accordance with EN 294<br />
TFDX G J<br />
315 356 322<br />
355 395 361<br />
Electrical accessories<br />
Transformer p. 486 Thermal protection p. 502<br />
235
<strong>Roof</strong> <strong>fans</strong><br />
TFDX 400-500<br />
Knock-out ø 23<br />
(electrical connection)<br />
Protection guard: standard on the exhaust<br />
side in accordance with EN 294<br />
See page 234 for further information<br />
TFDX 400-4 TFDX 450-4 TFDX 500-6<br />
Voltage/Frequency V/50 Hz 400 400 400<br />
Phase ~ 3 3 3<br />
Power W 393 646 371<br />
Current A 0,75 1,23 0,79<br />
Maximum air flow m 3 /s (m 3 /h) 0,92 (3295) 1,25 (4500) 1,13 (4080)<br />
R.p.m. min -1 1375 1360 870<br />
Ambient temp. °C -20 to +40 -20 to +40 -20 to +40<br />
Sound pressure level at 4/10 m dB(A) 55/47 60/52 51/43<br />
Weight kg 43 47 45<br />
Insulation class, motor F F F<br />
Enclosure class, motor IP 44 IP 44 IP 44<br />
Motor protection TUS 230 KIL TUS 230 KIL TUS 230 KIL<br />
Certificate SP Ex 96.D.103X SP Ex 96.D.104X SP Ex 96.D.105X<br />
Speed control, five-step Transformer RTRD 2 RTRD 2 RTRD 2<br />
Speed control, five-step high/low Transformer RTRDU 2 RTRDU 2 RTRDU 2<br />
Wiring diagram p. 11-13 11 11 11<br />
When using the RTRD or RTRDU together with the TUS 230 KIL, the internal motor protection in the transformer must be strapped<br />
Accessories<br />
TG p. 536 BTG p. 537<br />
236
<strong>Roof</strong> <strong>fans</strong><br />
TFDX 400-4<br />
Mid-frequency band, Hz<br />
Hz Tot 63 125 250 500 1k 2k 4k 8k<br />
L wA Inlet dB(A) 71 62 62 60 65 65 62 57 52<br />
L wA Surrounding dB(A) 78 55 65 70 73 73 68 61 56<br />
With TG 640-800<br />
L wA Inlet dB(A) 66 61 60 56 58 56 56 53 48<br />
With SSD 450/499/500<br />
L wA Inlet dB(A) 63 60 57 52 52 45 40 36 34<br />
Measuring point: q v = 0,49 m 3 /s, P s = 254 Pa<br />
TFDX 450-4<br />
Mid-frequency band, Hz<br />
Hz Tot 63 125 250 500 1k 2k 4k 8k<br />
L wA Inlet dB(A) 76 62 66 67 72 70 68 62 56<br />
L wA Surrounding dB(A) 83 60 70 76 78 78 72 65 60<br />
With TG 640-800<br />
L wA Inlet dB(A) 71 61 64 63 65 61 62 58 52<br />
With SSD 450/499/500<br />
L wA Inlet dB(A) 66 60 61 59 59 50 46 41 38<br />
Measuring point: q v = 0,63 m 3 /s, P s = 324 Pa<br />
TFDX 500-6<br />
Mid-frequency band, Hz<br />
Hz Tot 63 125 250 500 1k 2k 4k 8k<br />
L wA Inlet dB(A) 69 60 56 60 64 63 60 55 47<br />
L wA Surrounding dB(A) 74 55 59 67 69 69 63 57 50<br />
With TG 640-800<br />
L wA Inlet dB(A) 64 59 54 56 57 54 54 51 43<br />
With SSD 450/499/500<br />
L wA Inlet dB(A 60 58 51 52 51 43 38 34 29<br />
Measuring point: q v = 0,66 m 3 /s, P s = 144 Pa<br />
Electrical accessories<br />
Transformer p. 486 Thermal protection p. 502<br />
237
<strong>Roof</strong> <strong>fans</strong><br />
TFDX 560-630<br />
• Speed-controllable<br />
• Integral thermistors<br />
• Vertical exhaust<br />
• Tilting frame included<br />
• Maintenance-free and reliable<br />
The TFDX models have impellers with backward-curved<br />
blades and maintenance-free external rotor motors. The<br />
casing is manufactured in galvanised sheet steel, with a<br />
brass or copper inlet cone. Powder-coated version available<br />
on request. The fan has a tilting mechanism for easy<br />
inspection and servicing. Exhaust air is directed vertically<br />
from the <strong>fans</strong> which prevents problems caused by wet<br />
snow and staining of the roof.<br />
To protect the motor from overheating these <strong>fans</strong> have integral<br />
thermistors with external leads which should be connected<br />
to the TUS 230 KIL motor protection relay.<br />
Explosion proof versions comply with EN 50014 and<br />
50019. Improved safety in accordance with EEx e ll T3.<br />
TFDX 560-6 TFDX 630-6<br />
Voltage/Frequency V/50 Hz 400 400<br />
Phase ~ 3 3<br />
Power W 624 997<br />
Current A 1,18 2,1<br />
Maximum air flow m 3 /s (m 3 /h) 1,82 (6560) 2,36 (8500)<br />
R.p.m. min -1 890 880<br />
Ambient temp. °C -20 till +40 -20 till +40<br />
Sound pressure at 4/10 m dB(A) 52/44 59/51<br />
Weight kg 82 88<br />
Insulation class, motor F F<br />
Enclosure class, motor IP 44 IP 44<br />
Motor protection TUS 230 KIL TUS 230 KIL<br />
Certificate SP Ex 96.D.106X SP Ex 96.D.107X<br />
Speed control, five-step Transformer RTRD 2 RTRD 4<br />
Speed control, five-step high/low Transformer RTRDU 2 RTRDU 4<br />
Wiring diagram p. 11-13 11 11<br />
When using the RTRD or RTRDU together with the TUS 230 KIL, the internal motor protection in the transformer must be strapped<br />
Accessories<br />
TG p. 536 BTG p. 537<br />
238
<strong>Roof</strong> <strong>fans</strong><br />
TFDX 560-6<br />
Mid-frequency band, Hz<br />
Hz Tot 63 125 250 500 1k 2k 4k 8k<br />
L wA Inlet dB(A) 68 61 57 60 61 61 59 55 48<br />
L wA Outlet dB(A) 75 57 63 70 70 70 64 57 50<br />
With TG 940-1230<br />
L wA Inlet dB(A) 64 61 55 56 53 54 54 51 44<br />
With SSD 560/630<br />
L wA Inlet dB(A) 61 59 52 52 49 43 38 35 30<br />
Measuring point: q v = 1,00 m 3 /s, P s = 223 Pa<br />
Knock-out ø 23<br />
(electrical connection)<br />
TFDX 630-6<br />
Mid-frequency band, Hz<br />
Hz Tot 63 125 250 500 1k 2k 4k 8k<br />
L wA Inlet dB(A) 72 64 62 64 65 65 63 56 52<br />
L wA Outlet dB(A) 82 60 69 79 74 74 69 62 55<br />
With TG 940-1230<br />
L wA Inlet dB(A) 78 73 72 71 67 67 67 64 60<br />
With SSD 710<br />
L wA Inlet dB(A) 75 71 69 67 64 56 52 48 46<br />
Measuring point: q v = 1,16 m 3 /s, P s = 295 Pa<br />
Protection guard: standard on the exhaust<br />
side in accordance with EN 294<br />
Electrical accessories<br />
Transformer p. 486 Thermal protection p. 502<br />
239