NF C 33-226 12/20 (24) kV aluminum cable - Nexans
NF C 33-226 12/20 (24) kV aluminum cable - Nexans
NF C 33-226 12/20 (24) kV aluminum cable - Nexans
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Contact<br />
Power LV and MV <strong>cable</strong>s and<br />
components (up to 110 <strong>kV</strong>)<br />
Phone: +7 495 545 05 38<br />
ilya.kostikov@nexans.com<br />
<strong>NF</strong> C <strong>33</strong>-<strong>226</strong> <strong>12</strong>/<strong>20</strong> (<strong>24</strong>) <strong>kV</strong> <strong>aluminum</strong> <strong>cable</strong><br />
FR-N<strong>20</strong>XA8E<br />
MV <strong>cable</strong>s <strong>NF</strong> C <strong>33</strong>-<strong>226</strong><br />
Description<br />
Usage<br />
<strong>NF</strong> C <strong>33</strong>-<strong>226</strong> <strong>cable</strong>s are the new generation of <strong>cable</strong>s for public power distribution<br />
network <strong>12</strong>/<strong>20</strong> <strong>kV</strong>. They are AD8 following <strong>NF</strong> C 13-<strong>20</strong>0 with a water pressure <<br />
0,2 bar. Sheath is anti-termite resistant.<br />
Design<br />
The <strong>cable</strong> is made of 1 or 3 bunched cores.<br />
Aluminium screen is made to ground short-circuit currents of EdF network, up to<br />
1000 A for 1 s. for underground networks.<br />
Options<br />
<strong>NF</strong> C <strong>33</strong>-<strong>226</strong> <strong>cable</strong>s can be manufactured with the following options:<br />
• Copper conductor<br />
• Other voltage<br />
• Other section<br />
• Grounding conductor<br />
• Thicker aluminium screen<br />
• Bunch<br />
• Re-enforced burying resistance (EDR) is ensured with an extruded<br />
polyethylene protection.<br />
Standards<br />
National <strong>NF</strong> C <strong>33</strong>-<strong>226</strong>; <strong>NF</strong> C <strong>33</strong>-<strong>226</strong><br />
Conductor exibility<br />
Stranded class 2<br />
Cable exibility<br />
Rigid<br />
Water proof<br />
AD8<br />
Version v1.3 Generated 6/18/14 - http://www.nexans.ru Page 1 / 2<br />
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of<br />
<strong>Nexans</strong> is indicative only and shall not be binding on <strong>Nexans</strong> or be treated as constituting a representation on the part of <strong>Nexans</strong>.
Contact<br />
Power LV and MV <strong>cable</strong>s and<br />
components (up to 110 <strong>kV</strong>)<br />
Phone: +7 495 545 05 38<br />
ilya.kostikov@nexans.com<br />
<strong>NF</strong> C <strong>33</strong>-<strong>226</strong> <strong>12</strong>/<strong>20</strong> (<strong>24</strong>) <strong>kV</strong> <strong>aluminum</strong> <strong>cable</strong><br />
Characteristics<br />
Construction characteristics<br />
Conductor exibility Stranded class 2<br />
Material of the inner semi-conductor<br />
Extruded<br />
Insulation<br />
XLPE (chemical)<br />
Material of the external semi-conductor<br />
Extruded strippable grooved elastomer<br />
Material used for longitudinal water tightness<br />
Swelling powder<br />
Screen<br />
ALU/PET tape screening foil<br />
Dimensional characteristics<br />
Screen thickness 150 µm<br />
Mechanical characteristics<br />
Cable exibility<br />
Rigid<br />
Usage characteristics<br />
Water proof<br />
AD8<br />
Selling information<br />
Marking<br />
Example NEXANS - plant number- BGN7 <strong>NF</strong> C <strong>33</strong>-<strong>226</strong> int. designation- section - Al - <strong>12</strong>/<strong>20</strong> (<strong>24</strong>) <strong>kV</strong> - year -<br />
month - installation guide type - G sheath thickness - SC semi-conductor thickness - EC screen thickness - C2 RT<br />
installation temperature<br />
Core identication: 1, 2, 3 helix-wise.<br />
The marking is metric over one core sheath, as well as a tracing mark.<br />
Conductor exibility<br />
Stranded class 2<br />
Cable exibility<br />
Rigid<br />
Water proof<br />
AD8<br />
Version v1.3 Generated 6/18/14 - http://www.nexans.ru Page 2 / 2<br />
All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of<br />
<strong>Nexans</strong> is indicative only and shall not be binding on <strong>Nexans</strong> or be treated as constituting a representation on the part of <strong>Nexans</strong>.