H6<br />

Torque Switch Status &<br />

IR Setting Tool Comms for<br />

Vandal Proof Applications cont.<br />

IR OPEN SIGNAL NOT PRESENT<br />

Bar OFF = IR Open signal present.<br />

IR CLOSE SIGNAL NOT PRESENT<br />

Bar OFF = IR Close signal present.<br />

IR LOCAL CONTROL DISABLED<br />

Bar OFF = IR Local control enabled.<br />

To operate the actuator locally with the<br />

IR Setting Tool refer to the option<br />

selection screen [Or] Section 9.14 page<br />

62.<br />

[Or] must be selected to [On].<br />

IR REMOTE CONTROL NOT<br />

SELECTED<br />

Bar OFF = IR Remote control<br />

selected (vandal-proof units only).<br />

When actuator is supplied without local<br />

controls for vandal proof applications<br />

the option selection screen [Or] must<br />

be set to [rE] for<br />

Remote operation (refer to Section 9.14<br />

page 62).<br />

H7<br />

Relay 3<br />

Relay 2<br />

Travel Limits,<br />

Centre Column &<br />

Remote Indication Outputs<br />

Relay 4<br />

H7<br />

Open<br />

Limit<br />

Relay 1<br />

Help Screen 7<br />

Close<br />

Actuator<br />

Moving<br />

OPEN LIMIT<br />

Bar ON = Actuator has reached<br />

open limit.<br />

CLOSE LIMIT<br />

Bar ON = Actuator has reached<br />

Close limit.<br />

ACTUATOR MOVING<br />

Bar ON = Actuator moving.<br />

SWITCH CONTACTS S1, S2, S3, S4<br />

Bar ON = S contact is close circuit.<br />

Bar indication is real time and reactive<br />

(refer to Section 9.2 [r1] page 32 for<br />

configuration of ‘‘ S’’contacts).<br />

H3<br />

Actuator Position<br />

Sensing Devices<br />

H8<br />

Position<br />

Sensor A<br />

Help Screen 8<br />

Position<br />

Sensor B<br />

POSITION SENSOR A<br />

Senses output rotation. Used for the<br />

position sensing circuit. Correct<br />

operation of the sensor is indicated by<br />

the bar being ON (and OFF) <strong>12</strong> times<br />

per output revolution. When the motor<br />

is running, ON and OFF bit duration<br />

should be equal.<br />

POSITION SENSOR B<br />

Senses output rotation. Used for the<br />

position sensing circuit. Correct<br />

operation of the sensor is indicated by<br />

the bar being ON (and OFF) <strong>12</strong> times<br />

per output revolution.<br />

When the motor is running, ON and<br />

OFF bit duration should be equal.<br />

For the two sensors, A and B, correct<br />

operation is indicated by the following<br />

truth table.<br />

To observe this function, select manual<br />

operation and turn the actuator<br />

handwheel clockwise, starting with all<br />

sensors OFF:<br />

CLOCKWISE 30 Deg.<br />

Sensor B 0 1 1 0 0<br />

Sensor A 0 0 1 1 0<br />

71