33 12 16.26 - 001-A - Response AAN-ANR Butterfly Valves - Garney ...

33 12 16.26 - 001-A - Response AAN-ANR Butterfly Valves - Garney ... 33 12 16.26 - 001-A - Response AAN-ANR Butterfly Valves - Garney ...

team.garney.com
from team.garney.com More from this publisher
26.10.2014 Views

H1 Local Controls Error Factors Inhibiting Electrical Operation Phase Loss Battery Low on Power-up H1 Position Error Help Screen 1 POSITION ERROR Bar ON = Current Position Error Present. During power up the actuator position processor compares the current position to that stored in the Eeprom. If there is a discrepancy this is shown as a current position error. Re-setting of both actuator limits should now be carried out (refer to page 27). BATTERY LOW ON POWER UP Bar ON = Low battery detected On Power Up. If [OS] is selected [On] (set as default ) the actuator operation will be inhibited when powered up with a discharged battery (refer to [OS] page 58). The battery should be replaced at the earliest opportunity (refer to page 65). LOCAL CONTROLS ERROR Bar ON = Invalid Local Control Signals Detected. For example if a Local Open and Close signal is detected at the same time this would be classed as an invalid or fault condition. PHASE LOSS Bar ON = Phase Lost (3 Phase Actuators Only). Loss of third monitored power supply phase connected to actuator terminal 3. H2 Low Battery Battery Discharged Battery Level and ESD Control Input H2 ESD Active Help Screen 2 BATTERY DISCHARGED Bar ON = Battery Discharged. Bar ON when the battery is no longer able to support actuator functions under loss of power conditions. The battery must be replaced (refer to Section 10 page 65) and limit positions reset (refer to [LC] and [LO] page 27). 68 LOW BATTERY Bar ON = Battery level low. Bar OFF = Battery OK. Bar ON when the battery is low but still able to support the necessary actuator functions. The battery should be replaced at the earliest possible opportunity. ESD SIGNAL ACTIVE Bar ON = ESD Signal is present. When applied, an Emergency Shutdown Signal will override any existing local or remote control signal, causing the actuator to respond in the direction selected for ESD. The ESD function will be determined by the settings on Control Mode Configuration screens [A1] to [A5] (refer to Section 9.3 page 34). The actuator will not respond to any local or remote control while an ESD signal is maintained.

H3 Factors Inhibiting Electrical Operation H3 Clockwise Limit H4 Remote Control Inputs H4 Remote Remote Maintain 2 Open 1 REMOTE CLOSE 1 Bar OFF = Remote Close Signal Present. ESD 1 Bar OFF = ESD signal present. H5 Remote Interlocks, Local Control Inputs, & T/stat Local Stop not Selected H5 Open Interlock 69 Inhibit Help Screen 3 CLOCKWISE LIMIT Bar ON = Actuator has reached clockwise limit of travel. ANTI-CLOCKWISE LIMIT Bar ON = Actuator has reached Anti-clockwise limit. INHIBIT Bar ON = Actuator inhibited. Possible Causes: Phase Loss (3 phase only). Power Loss Inhibit (page 62). Internal Failure. Anti Clockwise Limit ESD 2 Remote Close 1 Remote Close 2 ESD 1 Remote Remote Open 2 Maintain 1 Help Screen 4 All remote signals designated with ‘1’ are standard hard wired remote inputs. When a Pakscan, Profibus or Foundation Fieldbus card is fitted, remote control inputs are designated with a ‘2’. REMOTE OPEN 1 Bar OFF = Remote Open Signal Present. REMOTE MAINTAIN 1 Bar OFF = Remote Maintain signal present. Bar ON = Remote Maintain not present and/or Remote Stop active. REMOTE OPEN 2 Bar OFF = Remote Open signal present from BUS option pcb. REMOTE CLOSE 2 Bar OFF = Remote Close signal present from BUS option pcb. ESD 2 Bar OFF = ESD signal present from BUS option pcb. REMOTE MAINTAIN 2 Bar OFF = Remote Maintain signal present from BUS option pcb. Thermostat Tripped Local Open not Present Local Close Remote not not Present Selected Help Screen 5 Close Interlock Local not Selected OPEN INTERLOCK Bar ON = Open Interlock Active. (Actutator disabled) Unauthorised Open electrical operation can be prevented by interlocking the actuator (Open) control with an external interlock contact. If external interlocks are not required the interlock function must be selected OFF.

H1<br />

Local<br />

Controls<br />

Error<br />

Factors Inhibiting<br />

Electrical Operation<br />

Phase<br />

Loss<br />

Battery Low<br />

on<br />

Power-up<br />

H1<br />

Position<br />

Error<br />

Help Screen 1<br />

POSITION ERROR<br />

Bar ON = Current Position Error<br />

Present.<br />

During power up the actuator position<br />

processor compares the current position<br />

to that stored in the Eeprom. If there is<br />

a discrepancy this is shown as a current<br />

position error.<br />

Re-setting of both actuator limits<br />

should now be carried out (refer to<br />

page 27).<br />

BATTERY LOW ON POWER UP<br />

Bar ON = Low battery detected On<br />

Power Up.<br />

If [OS] is selected [On] (set as default )<br />

the actuator operation will be inhibited<br />

when powered up with a discharged<br />

battery (refer to [OS] page 58).<br />

The battery should be replaced at the<br />

earliest opportunity (refer to page 65).<br />

LOCAL CONTROLS ERROR<br />

Bar ON = Invalid Local Control<br />

Signals Detected.<br />

For example if a Local Open and Close<br />

signal is detected at the same time this<br />

would be classed as an invalid or fault<br />

condition.<br />

PHASE LOSS<br />

Bar ON = Phase Lost (3 Phase<br />

Actuators Only).<br />

Loss of third monitored power supply<br />

phase connected to actuator terminal 3.<br />

H2<br />

Low<br />

Battery<br />

Battery<br />

Discharged<br />

Battery Level and<br />

ESD Control Input<br />

H2<br />

ESD<br />

Active<br />

Help Screen 2<br />

BATTERY DISCHARGED<br />

Bar ON = Battery Discharged.<br />

Bar ON when the battery is no longer<br />

able to support actuator functions<br />

under loss of power conditions.<br />

The battery must be replaced (refer to<br />

Section 10 page 65) and limit positions<br />

reset (refer to [LC] and [LO] page 27).<br />

68<br />

LOW BATTERY<br />

Bar ON = Battery level low.<br />

Bar OFF = Battery OK.<br />

Bar ON when the battery is low but still<br />

able to support the necessary actuator<br />

functions.<br />

The battery should be replaced at the<br />

earliest possible opportunity.<br />

ESD SIGNAL ACTIVE<br />

Bar ON = ESD Signal is present.<br />

When applied, an Emergency<br />

Shutdown Signal will override any<br />

existing local or remote control signal,<br />

causing the actuator to respond in the<br />

direction selected for ESD.<br />

The ESD function will be determined by<br />

the settings on Control Mode<br />

Configuration screens [A1] to [A5]<br />

(refer to Section 9.3 page 34).<br />

The actuator will not respond to any<br />

local or remote control while an ESD<br />

signal is maintained.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!