10 Maintenance, Monitoring<br />

and Troubleshooting cont.<br />

10.1<br />

Help Screens<br />

67<br />

Troubleshooting<br />

The IQ range of actuators is the world’s<br />

first that can be commissioned and<br />

interrogated without removing electrical<br />

covers. Help Screen diagnostics enable<br />

fast and complete fault finding to be<br />

carried out.<br />

With power off, the actuator<br />

display is not backlit. Position<br />

indicator lamp not illuminated.<br />

With mains power on, the actuator’s<br />

display should be backlit (refer to<br />

Section 3.3 page 4 – The Actuator<br />

Display).<br />

Check that 3 phase supply is available<br />

and is of the correct voltage as stated<br />

on the actuator nameplate. Measure<br />

voltage phase to phase across terminals<br />

1, 2 and 3 of the actuator terminal<br />

bung.<br />

With power Off, the actuator does<br />

not display position.<br />

With mains power off the actuator<br />

battery supports position indication<br />

liquid crystal display only.<br />

(Refer to Section 3.3 page 4 – The<br />

Actuator Display).<br />

If the display is blank the actuator<br />

battery must be replaced and the limits<br />

of travel reset (refer to Section 10 page<br />

65 – The Actuator Battery).<br />

With the actuator powered up and<br />

Local or Stop selected, eight Help<br />

Screens can be accessed using the<br />

Setting Tool (refer to Fig. 9.1 page 30<br />

for their location).<br />

With Remote selected press the ◗ key<br />

on the Setting Tool twice. The Help<br />

Screens will displayed.<br />

Each screen uses bars to indicate the<br />

status of a particular control or<br />

indication function. Each bar reacts to<br />

changes in the status of its actuator<br />

function by turning ‘‘on’’ or ‘‘off’’.<br />

For troubleshooting, access the<br />

following Help Screens and refer to<br />

text:<br />

H1 – Factors inhibiting electrical<br />

operation.<br />

H2 – Monitor battery level and ESD<br />

control input.<br />

H3 – Monitor the position limit and<br />

actuator power supply status.<br />

H4 – Monitor remote control inputs to<br />

the actuator.<br />

H5 – Monitor remote interlocks local<br />

control inputs and motor<br />

thermostats.<br />

H6 – Monitor torque switch status and<br />

IR Setting Tool communication for<br />

vandal proof applications.<br />

H7 – Monitor travel limits, centre<br />

column and position limit status.<br />

H8 – Monitor the actuator’s positionsensing<br />

devices.<br />

H9 – Rotork use only.<br />

Help screen bars shown<br />

are undefined and may be ON, OFF or<br />

flashing.