9.17 Default Options<br />

[d1] and [d2]<br />

Rotork standard [d1] Default settings continued:<br />

Function [d1] Default Setting<br />

[A7] 2-wire Remote Control [SP] Stayput on 2-wire signal<br />

[A8] Interlocks [OF] I/L function disabled<br />

[A9] Conditional Control [OF] Function disabled<br />

[AE] Torque Switch Bypass [OF] Function disabled<br />

[OE] Option Extra Indication Contacts [OF] Unless fitted. See wiring diagram<br />

[OI] Option CPT [HI] 4mA at Closed<br />

[OF] Option Folomatic [OF] Unless fitted. See wiring diagram<br />

[Od] Remote Source [rE] Unless option fitted<br />

(refer to 9.7 page 42.)<br />

[OP] Option Bus System Control [OF] Unless fitted. See wiring diagram<br />

[OJ] Option Interrupter Timer [OF] Unless fitted. See wiring diagram<br />

[Or] Setting Tool Local Control [OF] Setting Tool Control disabled<br />

[OS] Power Loss Inhibit [OF] Protection off<br />

64<br />

The Rotork standard default settings are subject to change without notice.<br />

If specified with order, [d1] settings will be configured as requested.<br />

To reinstate [d1] settings, with [d1] displayed.<br />

PRESS THE KEY.<br />

The setting bars will flash, indicating the [d1] default settings have been reinstated.<br />

To reinstate factory set limits (actuator positioned at 50%) with [d2] displayed,<br />

PRESS THE KEY.<br />

The setting bars will flash, indicating the [d2] default limits have been reinstated.<br />

[d1] Displayed<br />

[d2] Displayed<br />

Option Extra Indication Contacts (when fitted) - refer to wiring diagram<br />

[r5] Indication Contact S5 [CI]/[nO] Close, normally open<br />

[r6] Indication Contact S6 [OP]/[nO] Open, normally open<br />

[r7] Indication Contact S7 [tI]/[nO] Torque Trip Mid Travel,<br />

normally open<br />

[r8] Indication Contact S8 [rE]/[nO] Remote Selected,<br />

normally open