26.10.2014 Views

33 12 16.26 - 001-A - Response AAN-ANR Butterfly Valves - Garney ...

33 12 16.26 - 001-A - Response AAN-ANR Butterfly Valves - Garney ...

33 12 16.26 - 001-A - Response AAN-ANR Butterfly Valves - Garney ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

JO<br />

Position in Valve Opening<br />

Stroke for Timer to Stop<br />

Jn<br />

Contactor On Time<br />

Contactor Off Time<br />

JF JE ESD Override<br />

Interrupter Timer<br />

61<br />

Using the + or - key select the position<br />

for the TIMER TO STOP WHEN THE<br />

VALVE IS OPENING.<br />

[ ][] = valve closed<br />

[00] to [99] = percentage open<br />

[ ] = valve open<br />

Timer Set to Stop Pulsing<br />

when Opening Valve<br />

Reaches 25% Open<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

If timing is not required in the opening<br />

stroke select [JO] to [ ][].<br />

Press the ❖ key to display [Jn].<br />

Using the + or - key select the actuator<br />

run period in the range 1–99 seconds.<br />

Actuator Run Period<br />

Set for 5 Seconds<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Press the ❖ key to display [JF].<br />

Using the + or - key select the actuator<br />

stop period in the range 1–99 seconds.<br />

Actuator OFF Period<br />

Set for 25 Seconds<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Press the ❖ key to display [JE] (refer<br />

to note on Page 62).<br />

The interrupter timer may be overridden<br />

when the actuator is under ESD signal<br />

command. This will mean the actuator<br />

will run to limit without “stop/start”<br />

action under ESD command.<br />

Refer to A1–A3 (refer to page 34 for<br />

ESD settings).<br />

The default for ESD override interrupter<br />

timer is [OF]. The interrupter timer will<br />

continue “stop/start” action during ESD<br />

action.<br />

If ESD must override the timer use the<br />

+ or - to display [On].<br />

ESD Override Timer OFF<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.