9.4 Option Extra<br />

Indication Contacts<br />

OE<br />

Display Extra Contact<br />

Set-up Screens<br />

37<br />

Extra indication contacts S5 [r5], S6<br />

[r6], S7 [r7] and S8 [r8] are available as<br />

an option.<br />

Check actuator circuit diagram for<br />

inclusion.<br />

When the Extra Contact Option is<br />

included the set-up procedure and<br />

available contact functions for S5 – S8<br />

are identical to S1–S4 (refer to Section<br />

9.2 page 32).<br />

Unless specified with order the default<br />

setting for the extra indication contacts<br />

will be as follows:<br />

S5 [r5] Close limit indication<br />

S6 [r6] Open limit indication<br />

S7 [r7] Torque trip mid travel<br />

S8 [r8] Remote control selected<br />

NOTE: If the Extra Contact Option is<br />

not included in the actuator build, any<br />

settings made for S5–S8 will have no<br />

effect on the indication output of the<br />

actuator.<br />

The action of turning on the Extra<br />

Contact Option makes an additional<br />

series of set-up screens available<br />

Enabled Disabled<br />

Extra Contact Set-up Displays<br />

Press the + or - key to select the Extra<br />

Contact Option set-up screens [On].<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

PRESS THE ◗ KEY TO ACCESS S5<br />

TO S8 SET-UP DISPLAYS.<br />

The procedure for setting S5 to S8<br />

is the same as that for S1 to S4<br />

(refer to Section 9.2 page 32).