A8<br />

External Interlocks<br />

A9<br />

Conditional Control<br />

At<br />

Torque Switch Bypass<br />

36<br />

Actuators are delivered with the<br />

interlock facility disabled [OF] Refer to<br />

the actuator wiring diagram or<br />

publication E<strong>12</strong>0E for interlock control<br />

circuits.<br />

To enable remote external interlocks<br />

press the + or - key.<br />

The display will change to [On].<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Interlocks Disabled<br />

Note: If interlocking is required in only<br />

one direction, it will be necessary to<br />

connect a link between the actuator<br />

terminals associated with the other<br />

direction.<br />

Where a high level of safety integrity is<br />

required, Conditional Control can be<br />

configured. In this mode two discreet<br />

signals are required for remote<br />

operation. Remote control will be<br />

conditional on both a control signal<br />

(open or close) and the appropriate<br />

interlock signal being applied<br />

simultaneously. Failure of either or a<br />

spurious signal will not cause operation.<br />

Interlocks [A8] must be set [On].<br />

Interlock signals are not required for<br />

local operation.<br />

The default setting for conditional<br />

control is [OF]. To enable conditional<br />

control press the + or - key.The display<br />

will change to [On].<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

The default setting for Torque Switch<br />

Bypass is [OF], the torque switches are<br />

not bypassed during the unseating<br />

movement.<br />

To bypass the torque switches during<br />

the unseating movement press the + or<br />

- key.<br />

The display will change to [On].<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

The torque switches will be bypassed<br />

from closed limit to 5% open when<br />

opening and from open limit to 95%<br />

when closing. Bypassing the torque<br />

switches makes torque in excess of<br />

rated and up to actuator stall available<br />

for unseating a ‘‘sticky’’ valve. Outside<br />

these positions the torque setting will<br />

revert to the values set for [tC], see<br />

page 25 and [tO] page 26.<br />

Conditional Control Off<br />

Torque Switch Bypass Off