A4<br />

ESD Override<br />

Interlocks<br />

A5<br />

ESD Override<br />

Local Stop<br />

A6<br />

Maintained<br />

Local Control<br />

A7<br />

2-wire Remote<br />

Control<br />

35<br />

The default setting for ESD Override<br />

Interlocks is [OF]. ESD action will not<br />

override an active interlock applied to<br />

the actuator.<br />

If an applied ESD signal is required to<br />

override active interlocks causing the<br />

ESD action as set for A1, press the + or<br />

- key. The display will change to [On].<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

ESD Override Interlock – Off<br />

The default setting for ESD Override<br />

Local Stop is [OF]. ESD will not override<br />

local stop when selected.<br />

If an applied ESD signal is required to<br />

override local stop causing the ESD<br />

action as set for A1, press the + or -<br />

key. The display will change to [On].<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

ESD Override Local Stop – Off<br />

The default setting for Local Actuator<br />

Pushbutton control is self-maintained<br />

[On].<br />

If non-maintained actuator pushbutton<br />

control is required (jogging, inching,<br />

push to run), press the + or - key. The<br />

display will change to [OF].<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Self-Maintained Local Control<br />

The default setting for 2-wire Remote<br />

Control is Stayput [SP]. If a open and<br />

closed remote control signal are applied<br />

simultaneously the actuator will stayput<br />

(stop if running). Refer to actuator<br />

wiring diagram or publication E<strong>12</strong>0E.<br />

Use the + or - key to select the<br />

required priority:<br />

[OP] Open<br />

[SP] Stay put<br />

[CL] Close<br />

PRESS THE<br />

KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

2-wire Control – Stayput Priority