9.2 Indication Contacts<br />

S1, S2, S3 and S4<br />

r1<br />

Contact S1 - Function<br />

32<br />

Indication contacts S1 [r1], S2 [r2], S3<br />

[r3] and S4 [r4] may each be set to trip<br />

for any one of the following functions:<br />

Code Function<br />

[CL] closed end position<br />

[OP] open end position<br />

[Po] intermediate position<br />

[tC] torque trip close<br />

[tO] torque trip open<br />

[tt] torque trip any position<br />

[tl] torque trip mid travel<br />

[dC] actuator closing<br />

[dO] actuator opening<br />

[d?] actuator rotating<br />

[St] motor stalled<br />

[bA] battery low<br />

[HA] hand operation<br />

[bL] blinker<br />

[LS] local stop<br />

[Ol] open interlock<br />

[Cl] close interlock<br />

[lL] interlock active<br />

[ES] ESD signal<br />

[LP] lost phase **<br />

[Lo] local selected<br />

[rE] remote selected<br />

[AA] actuator alarm *<br />

[24] 24V power failure ***<br />

[rr] motor running<br />

[UA] Valve alarm*<br />

[Ht] thermostat tripped<br />

[CA] Control alarm*<br />

[rP] relay parity<br />

The S contact form can be set normally<br />

open [no] or normally closed [nc].<br />

The procedures for setting up contacts<br />

S2, S3 and S4 are the same as those<br />

shown for S1.<br />

Unless specified with order, the<br />

default settings for indication<br />

contacts are as follows:<br />

S1 – [CL] closed end position [no]<br />

S2 – [OP] open end position [no]<br />

S3 – [CL] closed end position [nc]<br />

S4 – [OP] open end position [nc]<br />

* Contact alarm indication will operate<br />

under the same conditions as the<br />

display alarm indication icons (refer to<br />

page 5 for information).<br />

** [LP] Function not available for<br />

phases 1 & 2, only for phase 3. For<br />

phase loss detection on phase 1 & 2<br />

please use monitor relay<br />

*** [24] Function not available if the 3<br />

phase supply is lost.<br />

Using the + or - key display the desired<br />

function.<br />

PRESS THE KEY.<br />

The displayed function will flash<br />

indicating that it has been set.<br />

Contact S1 Configured to Trip<br />

at Valve Closed Limit<br />

PRESS THE ❖ KEY.