24.10.2014 Views

Commuter Rail AC Electrification Load-Flow Simulation Report - RTD

Commuter Rail AC Electrification Load-Flow Simulation Report - RTD

Commuter Rail AC Electrification Load-Flow Simulation Report - RTD

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Commuter</strong> <strong>Rail</strong> <strong>AC</strong> <strong>Electrification</strong> <strong>Load</strong>-<strong>Flow</strong> <strong>Simulation</strong> <strong>Report</strong> Revision 1<br />

8.0 ELECTRICAL SYSTEM SIMULATION RESULTS<br />

8.1 GENERAL<br />

The morning and evening rush-hour operation is assumed to be the same, i.e., the same train<br />

consists at the same headways, as presented in Table 1 above, will operated in both periods of<br />

time. Therefore, the results of the study apply to both rush-hours.<br />

8.2 STUDIES PEFORMED<br />

The following two sets of studies were performed:<br />

• Set 1 – Two traction power transformers in Sandown substation and two traction power<br />

transformers in Argo substation<br />

o All systems in service<br />

o Argo substation out of service<br />

o Sandown substation out of service<br />

• Set 2 - Two traction power transformers in Sandown substation and one traction power<br />

transformer in Argo substation<br />

o All systems in service<br />

o Sandown substation out of service<br />

It was not necessary to run the Argo substation out of service case in the study Set 2, as the<br />

results would be the same as in the study Set 1.<br />

8.3 SYSTEM VOLTAGES<br />

The minimum train (pantograph to running rail) voltage for each commuter rail line during all<br />

equipment in-service and for contingency operation of each substation out-of-service are shown<br />

in the following Table.<br />

Table 10 -<br />

System Voltages<br />

System Condition<br />

2 Transformers in Sandown,<br />

2 Transformers in Argo<br />

East<br />

Corridor<br />

Gold<br />

Line<br />

Minimum Voltage (kV)<br />

North<br />

Metro<br />

Corridor<br />

2 Transformers in Sandown,<br />

1 Transformer in Argo<br />

East<br />

Corridor<br />

Gold<br />

Line<br />

North<br />

Metro<br />

Corridor<br />

All Equipment-In-Service 24.5 24.8 24.5 24.4 24.4 24.1<br />

Argo Substation Outage 24.1 24.0 23.9 24.1 24.0 23.9<br />

Sandown Substation Outage 24.0 24.3 24.0 23.9 24.1 23.9<br />

Voltage profiles along each corridor are presented in Appendices C, D, E, F and G.<br />

8.4 CONDUCTOR CURRENTS<br />

Normally, conductor temperatures vs. time are derived on transient basis using the one-second<br />

output from the computer load-flow simulations. However, since the RMS currents were well<br />

02/27/2009 FRSC Page 23 of 250

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!