Telecom
Telecom
Telecom
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
W orld Class Power Solutions<br />
<strong>Telecom</strong><br />
Modular DC Power Supply Systems BLT<br />
with remote monitoring system MCU<br />
DC-DC Converters, Inverters
With the increasing demands on power<br />
supplies for today´s telecommunications<br />
industry Benning have developed a<br />
wide range of power modules.<br />
Benning power<br />
supply systems<br />
have a modular<br />
structure and<br />
can be adapted<br />
all customer<br />
requirements.<br />
Flexible, modular Structure<br />
Float<br />
Boost<br />
Battery Test<br />
Battery Test Negative<br />
Rectifier Failure<br />
Mains Failure<br />
DC Voltage < 2,1 V/C<br />
Batt. Discha. U < 1,8 V/C<br />
Battery Failure<br />
LVD tripped<br />
Battery Fuse tripped<br />
Load Fuse tripped<br />
Reserve<br />
LED Test/Reset<br />
DC-Power-Supply<br />
Systems are available with wall-mounted<br />
cabinets and floor-standing cabinets.<br />
Using combination cabinets it is<br />
possible to build in batteries with the<br />
plug-in power supplies.<br />
U<<br />
+ ++<br />
BLT-Power Supply-Systems<br />
The following switched mode plug-in<br />
rectifiers and BLT-systems meet the<br />
requirements for compact and reliable<br />
power supplies and have the following<br />
principal features:<br />
The modular structure of the BLTsystems<br />
allows adaptation to almost<br />
all requirements. All BLT-systems are<br />
Plug-in Rectifiers<br />
delivered with the monitoring system<br />
MCU 500/1000 or MCU 2000+.<br />
La Defense, Paris; – BENNING , power where it’s needed,<br />
• efficiency ≥ 90 %<br />
• power factor ≥ 0,93 / 0,98<br />
• radio interference suppression to<br />
EN 55022 level B<br />
• noise voltage<br />
≤ 1 mV or 2 mV CCITT<br />
• excellent transient response<br />
• temperature-controlled voltage<br />
characteristic<br />
Rectifier range PDT 400,<br />
PDT 650, PDT 800, PDT 1800<br />
This range is used for smaller power<br />
systems. The mechanical layout allows<br />
the arrangement of 6 plug-in rectifiers<br />
(PDT 400 + PDT 650) side by side in<br />
one 19“ rack. (Only without MCU<br />
interface available.) The units PDT 800<br />
and PDT 1800 are with or without MCU<br />
interface available, 4 plug-in rectifiers<br />
can be fitted in one 19“ rack.<br />
PDT 800<br />
24 V - 15 A<br />
48 V - 15 A<br />
60 V - 12 A<br />
PDT 400<br />
48 V - 7,5 A PDT 650<br />
48 V - 12 A<br />
60 V - 10 A<br />
PDT 1800<br />
24 V - 50 A<br />
48 V - 33 A<br />
60 V - 27 A
Range PDD 3000<br />
The forced-ventilated design is rated<br />
for an output power of 3000 W. The<br />
mechanical layout of this unit allows<br />
the arrangement of 3 rectifiers each<br />
on one level of a 19“ rack. (with or<br />
without MCU interface)<br />
PDT 3000<br />
24 V - 75 A<br />
48 V - 50 A<br />
60 V - 40 A<br />
BLT 150<br />
Range PDE 7200 / 15000<br />
Power supplies up to several thousands<br />
Amps can be constructed with this<br />
range. The plug-in rectifiers have a<br />
19“ mechanical layout and are built<br />
into corresponding cabinets. The temperature<br />
controlled forced ventilation<br />
allows a very compact design.<br />
(with MCU interface)<br />
PDE 7200<br />
24 V - 200 A<br />
48 V - 125 A<br />
60 V - 100 A<br />
PDE 15000<br />
48 V - 225 A<br />
60 V - 200 A<br />
BLT-Line 2500, threephase
DC-DC converters<br />
The following DC-DC converters can<br />
be used in combination with the plugin<br />
rectifiers in the same plug-in rack.<br />
The designs available are galvanically<br />
separated and cover the ranges 24 V,<br />
48 V and 60 V.<br />
PCT 300 W<br />
24 / 48 V - 6 A<br />
La Defense, Paris; – BENNING , powers information technologies<br />
PDC 960, 1300, 1400<br />
24 / 48 V - 20 A<br />
48 / 24 V - 40 A<br />
60 / 24 V - 54 A<br />
60 / 48 V - 25 A<br />
Technical data<br />
Type table<br />
PCT 300 PDC 960 - 1400<br />
Input voltage V see type table<br />
Permissible deviation % + 20, - 10 I + 20, - 15<br />
Nominal output voltage V see type table<br />
Stability U output<br />
Static % ± 1<br />
Dynamic (load 10-100-10) % + 4, - 5<br />
Output current A see type table<br />
Voltage ripple Vpp < 1 %<br />
Noise voltage mV 1 or 2 frequency weighted with filter<br />
A in accordance with CCITT 0.41<br />
Response time ms < 5<br />
Efficiency % 80<br />
Radio interference EN 55022 class B I EN 55022 class A<br />
Ambient temperature °C 0 to + 40<br />
Protection IP 20<br />
Protection class 1 - EN 60950<br />
Max. installation height m 2000 above sea level<br />
Moisture class F in according with DIN 40040<br />
Indications<br />
DC voltage high<br />
red LED, automatic cut-off,<br />
to reset switch-off mains<br />
Operation<br />
green LED<br />
Input – I yellow LED<br />
I at DC voltage >TBD<br />
Alarm red LED I red LED (unit failure)<br />
temperature monitoring I approx. > 30 sec. delayed<br />
Current indication (output) – I bargraph<br />
Connections:<br />
Input<br />
plug<br />
Output<br />
plug<br />
Cooling<br />
convection<br />
Dimensions mm H 291 x B 71 x T 300 I H 266 x B 145 x T 440<br />
Weight kg approx. 4 I approx. 11<br />
Input voltage Output voltage Output current Type<br />
24 V 48 V 6 A G 24 G 48/ 6 PCT<br />
24 V 48 V 20 A G 24 G 48/20 PCD<br />
48 V 24 V 40 A G 48 G 24/40 PCD<br />
60 V 24 V 54 A G 60 G 24/54 PCD<br />
60 V 48 V 25 A G 60 G 48/25 PCD
Technical data, Plug-in Rectifiers<br />
Type<br />
max. quantity per 19“ level<br />
output power [W]<br />
PDT<br />
6<br />
400<br />
PDT<br />
6<br />
650<br />
PDT<br />
4<br />
800<br />
PDT<br />
4<br />
1800<br />
PDD<br />
3<br />
3000<br />
PDE<br />
1<br />
7200<br />
PDE<br />
1<br />
15000<br />
Input voltage range<br />
Input current<br />
Frequency<br />
Power factor<br />
Output current<br />
at 24 V<br />
at 48 V<br />
at 60 V<br />
Output voltages<br />
Boost voltage<br />
Float voltage<br />
Direct supply<br />
Battery check<br />
[V]<br />
[A]<br />
[Hz]<br />
[A]<br />
[A]<br />
[A]<br />
[V/c]<br />
[V/c]<br />
[V/c]<br />
[V/c]<br />
singlephase 196–264 I threephase 340–460<br />
2,1 I 3,4 I 4,2 I 8,5 I 14 I 13,7 I 22<br />
47–63<br />
0,98 I 0,93<br />
– I – I 15 I 50 I 75 I 200 I –<br />
7,5 I 12 I 15 I 33 I 50 I 125 I 225<br />
– I 10 I 12 I 27 I 40 I 100 I 200<br />
externally adjustable<br />
2,4<br />
2,23<br />
2,05<br />
1,8<br />
Stability U output<br />
Static [%]<br />
Dynamic load 10-100-10 [%]<br />
(di/dt>200µs)<br />
Response time<br />
[ms]<br />
Efficiency<br />
Characteristic<br />
Noise voltage<br />
[mV]<br />
Radio interference<br />
Protection class<br />
Safety<br />
Protection<br />
Cooling<br />
Ambient temperature<br />
[°C]<br />
Installation height<br />
[m]<br />
Moisture class<br />
Current measurement<br />
Voltage measurement<br />
Indications:/front panel<br />
Mains<br />
DC voltage high<br />
Operation<br />
Alarm<br />
Fan failure<br />
Common alarm/change-over contact<br />
Connections:<br />
Main input<br />
Output<br />
Alarms<br />
Dimensions<br />
Height (front panel)<br />
[mm]<br />
Width<br />
[mm]<br />
Depth<br />
[mm]<br />
Weight<br />
[kg]<br />
±1<br />
±5<br />
< 5<br />
90 I 91 I 94<br />
IU<br />
1 for 24 V units, 2 for 48/60 V units<br />
EN 55022 class B<br />
1-EN 60950<br />
EN 60950<br />
IP 20<br />
convection<br />
I fan behind the front panel, temperature controlled<br />
0 – 40<br />
up to 2000 m above sea level<br />
F DIN 40040<br />
– I test sockets*<br />
– I – I test sockets*<br />
yellow LED<br />
red LED<br />
green LED<br />
red LED<br />
I<br />
red LED<br />
fault<br />
plug I terminals 4 mm 2<br />
plug I M8 I M12<br />
plug I plugterminal<br />
267 I 267 I 267 I 267 I 267 I 177 I 267<br />
71 I 71 I 107 I 107 I 146 I 485 I 485<br />
250 I 250 I 250 I 350 I 440 I 400 I 400<br />
3,0 I 3,6 I 5,5 I 9,5 I 12,5 I 26,5 I 40,0<br />
* digital display: standard in PDE 7200 and PDE 15000<br />
in PDT 800, PDT 1800 and PDD 3000 only in version with MCU interface
General<br />
The inverters can be connected in<br />
parallel so systems with N+1<br />
redundancy can be constructed.<br />
Inverter range TEBEVERT<br />
Parallel connection can be<br />
used for increasing the<br />
power, and thus system<br />
extension on site is possible<br />
for increasing power<br />
demand.<br />
Systems with up to 5 inverters<br />
connected in parallel are<br />
possible.<br />
The use of modern semiconductors<br />
with high switching frequencies<br />
provides compact construction,<br />
low weight and a very high efficiency.<br />
TEBEVERT<br />
Inverter<br />
5000 VA<br />
In order to increase the availability of<br />
the system a mechanical by-pass can<br />
be provided. In case of inverter failure<br />
it automatically switches over to the<br />
public mains (fig. 1) with a low changeover<br />
time.<br />
The EUE (static by-pass) is another<br />
component for increasing the system<br />
safety. Using the EUE the loads are<br />
directly switched to the mains in case<br />
of overload or faults in the<br />
inverter (fig. 2 + 3). This switch-over<br />
is made almost without interruption.<br />
All monitoring and control units are<br />
designed to be intrinsically safe<br />
so that an uninterrupted supply of the<br />
connected load is ensured.<br />
Operation mode<br />
Airport Frankfurt/Main, Benning - Power to Communikation<br />
These products have a very good<br />
dynamic range. At load peaks of<br />
0 %-100 % - 0 %, fluctuations and<br />
voltage surges are corrected within a<br />
very short time.<br />
The plug-in inverters are available<br />
with the output power 1000 VA, 1500 VA<br />
(only 24 V), 2500 VA and 5000 VA.<br />
The cabinets can be installed side by<br />
side with rectifier cabinets of similar<br />
design.<br />
Battery<br />
+<br />
Fig.1: Inverter with mechanical bypass<br />
(SUE), voltage gap approx. 100 ms<br />
Battery<br />
+<br />
Fig. 2: Inverter with static by-pass (EUE)<br />
for the uninterrupted supply of the<br />
loads<br />
Dimensions<br />
diagram<br />
SUE<br />
Inverter<br />
EUE<br />
Inverter<br />
* 1 1000 VA 48V/60V<br />
* 2 2500 VA 48V/60V<br />
* 2 1500 VA 24V<br />
* 3 5000 VA 48V/60V<br />
*3<br />
177 *2<br />
133,4 *1<br />
Load<br />
Load<br />
272 *1<br />
390 *2 / 450 *3<br />
Arresting hooks can be dismantled<br />
Battery<br />
Fig. 3 Inverters connected in parallel with<br />
static by-pass (EUE) for increasing the<br />
system safety<br />
39<br />
483<br />
On<br />
Off<br />
+<br />
Ein<br />
Aus<br />
EUE<br />
Inverter 1<br />
Inverter 2<br />
Inverter 5<br />
TEBEVERT<br />
Load<br />
Output present<br />
Mains synchronization /<br />
Present<br />
Overload<br />
Parallel operation<br />
Fault
Technical data TEBEVERT<br />
Static by-pass EUE<br />
Input DC voltage V see type table<br />
Permissible deviation % + 20, -15<br />
Ripple of the input voltage % max. 5 rms<br />
Reverse smoothing mV 2<br />
Nominal power VA see type table<br />
Output voltage V 230<br />
Static deviation % ± 5<br />
Frequency Hz 50<br />
Frequency stability % ± 0,1 (crystal controlled)<br />
Mains control of frequency % ± 3<br />
Power factor range<br />
0,7 ind. to 0,8 cap.<br />
Voltage form<br />
sine-wave<br />
Distortion factor % < 3 (at linear load)<br />
Overload capacity<br />
2xI nom for 1 sec.,<br />
cut-off after 40 sec.<br />
Crest factor load 2,5 : 1<br />
Radio interference EN 55022<br />
Efficiency % 80–85<br />
Ambient temperature °C +5 to +40<br />
Installation height m up to 1000 above sea level<br />
Moisture class<br />
F<br />
Cooling<br />
temperature-controlled<br />
forced ventilation<br />
Protection class 1 - EN 60950<br />
Protection<br />
IP 20 (without terminals)<br />
Painting (front panel) RAL 7032<br />
Indications<br />
Output current<br />
Output voltage present<br />
Fault<br />
Overload<br />
Mains synchronization<br />
Parallel operation<br />
Pot.-free contact<br />
bargraph<br />
LED<br />
LED<br />
LED<br />
LED<br />
LED<br />
fault (delay approx. 10 sec.)<br />
Loads of systems with EUE are<br />
permanently supplied via the inverter.<br />
The voltage gap, arising in the event of<br />
failure in the inverter or overload, is<br />
< 1,5 ms, so even sensitive electronic<br />
loads can be supplied without any<br />
problems. The overload behaviour is<br />
approx. 5 x I rated for 100 ms, therefore<br />
loads with high inrush currents can<br />
also be connected.<br />
Dimensions EUE (Static By-Pass)<br />
246,5<br />
483<br />
466<br />
3 U = 133,4<br />
Connections<br />
AC side<br />
DC side<br />
Alarm<br />
Remote control<br />
Earthing bolt<br />
EUE/parallel operation<br />
Options<br />
Dimensions<br />
plugs / terminals<br />
plugs / terminals<br />
plugs<br />
M6<br />
connector<br />
SUE operation<br />
EUE operation<br />
parallel operation<br />
see type table<br />
444<br />
Type table Tebevert<br />
Type<br />
Input<br />
voltage<br />
Input current at<br />
cos ϕ 0,8 a. Nominal<br />
input voltage<br />
Output<br />
power<br />
Dimensions<br />
H x W x D [mm]<br />
G 24 E 230/ 6,5/2rfg-PWE 24 V 57A 1500VA 177,0 x 483 x 390 18,5<br />
G 48 E 230/ 4,4/2rfg-PWE 48 V 20A 1000VA 133,4 x 483 x 256 10,5<br />
G 48 E 230/10,9/2rfg-PWE 48 V 50A 2500VA 177,0 x 483 x 390 18,5<br />
G 48 E 230/21,7/2rfg-PWE 48 V 92A 5000VA 177,0 x 483 x 450 28,0<br />
G 60 E 230/ 4,4/2rfg-PWE 60 V 16A 1000VA 133,4 x 483 x 256 10,5<br />
G 60 E 230/10,9/2rfg-PWE 60 V 40A 2500VA 177,0 x 483 x 390 18,5<br />
G 60 E 230/21,7/2rfg-PWE 60 V 74A 5000VA 177,0 x 483 x 450 28,0<br />
Weight [kg]<br />
Type table EUE<br />
Type<br />
Nominal power<br />
[VA]<br />
Dimensions<br />
H x W x D [mm]<br />
EUE E 230/ 32,60/2 - 24E 7500 133,4 x 483 x 300<br />
EUE E 230/ 21,74/2 - 48E (60E) 5000 133,4 x 483 x 300<br />
EUE E 230/ 54,35/2 - 48E (60E) 12500 133,4 x 483 x 300<br />
EUE E 230/ 108,7/2 - 48E (60E) 25000 133,4 x 483 x 300
General<br />
With the increasing demand for power systems in<br />
the telecommunication sector, and the need for<br />
more efficient use of operating and maintenance<br />
staff, Benning have produced a range of system<br />
monitoring. The Benning MCU 500, MCU 1000 and<br />
MCU 2000+ offer the user a solution depending<br />
on the customer requirements.<br />
BLT 150 and BLT 400 power systems are fitted<br />
with MCU 500 (Optional MCU 1000) monitoring<br />
system.<br />
By means of local indication (13 off LED´s) and<br />
numerical display, the system status can be<br />
quickly assessed.<br />
The MCU 1000 additionally offers direct communication,<br />
via a RS 485 interface, with the rectifier<br />
modules.<br />
As an optional extra the MCU 1000 may be fitted<br />
with a relay box having 8 volt free contact.<br />
Remote Monitoring System MCU 500, 1000 und 2000+<br />
Float<br />
Boost<br />
Battery test<br />
Battery test negative<br />
Rectifier failure<br />
Mains failure<br />
Fault U < 2,1 V/C<br />
Battery disch. U < 1,9 V/C<br />
LVD tripped<br />
Battery fuse tripped<br />
Load fuse tripped<br />
Battery fault<br />
(reserve)<br />
LED test/reset<br />
MCU 500<br />
DC-Power-Supply<br />
Contacts<br />
(1)<br />
The BLT 2500/5000 has the MCU 2000+ monitoring<br />
fitted as standard.<br />
Both MCU 1000 and MCU 2000+ monitoring<br />
systems have the facility to control and monitor<br />
the power system via the public telephone<br />
network.<br />
As an option, the MCU 1000 and MCU 2000+ signals<br />
can be transmitted via modem to a central<br />
control station.<br />
Float<br />
Boost<br />
Battery test<br />
Battery test negative<br />
Rectifier failure<br />
Mains failure<br />
Fault U < 2,1 V/C<br />
Battery disch. U < 1,9 V/C<br />
LVD tripped<br />
Battery fuse tripped<br />
Load fuse tripped<br />
Battery fault<br />
(reserve)<br />
LED test/reset<br />
DC-Power-Supply<br />
Contacts<br />
(1)<br />
RS 485<br />
(2)<br />
Using a PC and dedicated monitoring software,<br />
information can be sent and received by the<br />
customer based in the control station.<br />
MCU 1000<br />
Rectifier with (2)<br />
or without (1)<br />
interface<br />
The MCU 2000+ provides a large range of supervisory<br />
functions, and enables easy monitoring<br />
and controlling of the power supply system.<br />
Airport München, Benning - Power to Communikation<br />
Communication with the rectifiers is via an RS<br />
485 interface. Options include 8 additional volt<br />
free alarm contacts, 24 external digital inputs and<br />
15 measurement channels.<br />
Float<br />
Boost<br />
Battery test<br />
Battery test negative<br />
Rectifier failure<br />
Mains failure<br />
Fault U < 2,1 V/C<br />
Battery disch. U < 1,9 V/C<br />
LVD tripped<br />
Battery fuse tripped<br />
Load fuse tripped<br />
Battery fault<br />
(reserve)<br />
LED test/reset<br />
DC-Power-Supply<br />
RS 485<br />
(2)<br />
MCU 2000 +
I 2 C-Bus<br />
Base Unit<br />
• 8 external digital inputs<br />
• 3 pot. free contacts<br />
• 3 measurement-value channel for<br />
voltage, current or temperature<br />
RS 232<br />
I 2 C-Bus<br />
Base Unit<br />
• 8 external digital inputs<br />
• 3 pot. free contacts<br />
• 3 measurement-value channel for<br />
voltage, current or temperature<br />
RS 232<br />
Option:<br />
• Relay Box with 8 pot. free contacts<br />
RS 232<br />
Telephone line<br />
Base Unit<br />
• 8 external digital inputs<br />
• 3 pot. free contacts<br />
• 3 measurement-value channel for<br />
voltage, current or temperature<br />
RS 232<br />
I 2 C-Bus<br />
Option:<br />
• Relay Box with 8 pot. free contacts<br />
• 24 external digital inputs<br />
• 15 measurement-value channel for<br />
voltage, current or temperature<br />
RS 232
General<br />
”BLT” Power Systems are designed<br />
with the latest switch mode technology<br />
and are suitable for all <strong>Telecom</strong> applications.<br />
Modular DC Power Supply Systems BLT 150, BLT 400<br />
with MCU 500/1000<br />
The BLT 150 systems are able to feed<br />
smaller DC loads (approx. 15 A up to<br />
150 A), while the BLT 400 systems are<br />
used for middle range (approx. 100 A<br />
up to 400 A) and the BLT 2500/5000<br />
for the large range (approx. 500 A up<br />
to 5400 A).<br />
The special features are good efficiency,<br />
high power factor as well as a good<br />
dynamic behaviour.<br />
BLT 150<br />
Kongresszentrum Berlin, Benning - Power to Communikation<br />
DC System BLT 150 BLT 150<br />
Rectifier range<br />
No. of rectifiers<br />
Monitoring system<br />
Input<br />
Voltage<br />
Current (with 3 x 400 V)<br />
Frequency<br />
Power factor<br />
Output<br />
Voltage<br />
Current (max.)<br />
Characteristic<br />
Ripple voltage<br />
General data<br />
Efficiency<br />
Operating temperature<br />
Protection<br />
Dimensions<br />
PDT 400<br />
n = 6<br />
MCU 500<br />
Option MCU 1000<br />
3 x 400 V (± 15 %)<br />
4,2 A<br />
50 Hz (± 5 %)<br />
0,98<br />
48 VDC / 60 VDC<br />
45 A / 30 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
90 %<br />
0 ÷ 40 °C<br />
IP 20<br />
670 x 534 x 400<br />
PDT 650<br />
n = 6<br />
MCU 500<br />
Option MCU 1000<br />
3 x 400 V (± 15 %)<br />
6,8 A<br />
50 Hz (± 5 %)<br />
0,98<br />
48 VDC / 60 VDC<br />
72 A / 60 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
90 %<br />
0 ÷ 40 °C<br />
IP 20<br />
758 x 534 x 470
BLT 400<br />
BLT 150 BLT 400 BLT 400<br />
PDT 1800<br />
n = 4<br />
MCU 500<br />
Option MCU 1000<br />
3 x 400 V (± 15 %)<br />
17 A<br />
50 Hz (± 5 %)<br />
0,98<br />
24 VDC / 48 VDC / 60 VDC<br />
200 A / 132 A / 104 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
91 %<br />
0 ÷ 40 °C<br />
IP 20<br />
758 x 534 x 470<br />
PDT 1800<br />
n = 8<br />
MCU 500<br />
Option MCU 1000<br />
3 x 400 V (± 15 %)<br />
25,5 A<br />
50 Hz (± 5 %)<br />
0,98<br />
24 VDC / 48 VDC / 60 VDC<br />
400 A / 264 A / 208 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
91 %<br />
0 ÷ 40 °C<br />
IP 20<br />
2000 x 600 x 600<br />
PDD 3000<br />
n = 6<br />
MCU 500<br />
Option MCU 1000<br />
3 x 400 V (± 15 %)<br />
28 A<br />
50 Hz (± 5 %)<br />
0,98<br />
24 VDC / 48 VDC / 60 VDC<br />
450 A / 300 A / 240 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
91 %<br />
0 ÷ 40 °C<br />
IP 20<br />
2000 x 600 x 600<br />
Kongresszentrum Berlin, Benning - Power to Communikation
Modular DC Power Supply Systems BLT 2500/5000<br />
with MCU 2000 +<br />
BLT 2500<br />
BLT 2500<br />
La Defense, Paris; – BENNING , power where it’s needed,<br />
DC System BLT 2500 BLT 2500<br />
Rectifier range<br />
No. of rectifiers<br />
Monitoring system<br />
Input<br />
Voltage<br />
Current (with 3 x 400 V)<br />
Frequency<br />
Power factor<br />
Output<br />
Voltage<br />
Current (max.)<br />
Characteristic<br />
Ripple voltage<br />
General data<br />
Efficiency<br />
Operating temperature<br />
Protection<br />
Dimensions<br />
PDE 7200<br />
n = 5<br />
MCU 2000 +<br />
3 x 400 V (± 15 %)<br />
68,5 A<br />
50 Hz (± 5 %)<br />
0,93<br />
48 VDC / 60 VDC<br />
625 A / 500 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
93 %<br />
0 ÷ 40 °C<br />
IP 20<br />
2000 x 1800 x 600<br />
PDE 7200<br />
n = 10<br />
MCU 2000 +<br />
3 x 400 V (± 15 %)<br />
137 A<br />
50 Hz (± 5 %)<br />
0,93<br />
48 VDC / 60 VDC<br />
1250 A / 1000 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
93 %<br />
0 ÷ 40 °C<br />
IP 20<br />
2000 x 2400 x 600
BLT 2500<br />
BLT 5000<br />
BLT 2500 BLT 2500 BLT 2500/5000<br />
PDE 15000<br />
n = 6<br />
MCU 2000 +<br />
3 x 400 V (± 15 %)<br />
132 A<br />
50 Hz (± 5 %)<br />
0,94<br />
48 VDC / 60 VDC<br />
1350 A / 1200 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
94 %<br />
0 ÷ 40 °C<br />
IP 20<br />
2000 x 2400 x 600<br />
PDE 15000<br />
n = 12<br />
MCU 2000 +<br />
3 x 400 V (± 15 %)<br />
264 A<br />
50 Hz (± 5 %)<br />
0,94<br />
48 VDC / 60 VDC<br />
2700 A / 2400 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
94 %<br />
0 ÷ 40 °C<br />
IP 20<br />
2000 x 3000 x 600<br />
PDE 15000<br />
n = 24<br />
MCU 2000 +<br />
3 x 400 V (± 15 %)<br />
528 A<br />
50 Hz (± 5 %)<br />
0,94<br />
48 VDC / 60 VDC<br />
5400 A / 4800 A<br />
IU in accordance with DIN 41773<br />
< 2 mV in accordance with CCITT 0.41<br />
94 %<br />
0 ÷ 40 °C<br />
IP 20<br />
2000 x 6000 x 600<br />
La Defense, Paris; – BENNING , power where it’s needed,
BENNING World Class Power Solutions<br />
www.benning.de<br />
BENNING worldwide<br />
Austria<br />
Benning GmbH Elektrotechnik und Elektronik<br />
Eduard-Klinger-Str. 9<br />
A-3423 St. Andrä-Wördern<br />
Tel. 0 22 42 / 3 24 16-0<br />
Fax 0 22 42 / 3 24 23<br />
E-Mail: info@benning.at<br />
Ireland<br />
Theo Benning GmbH<br />
North Industrial Estate<br />
Whitemill North<br />
IRE-Wexford / Rep. Ireland<br />
Tel. 0 53/4179 5<br />
Fax 0 53 /41841<br />
E-Mail: benning@benning.ie<br />
South East Asia<br />
Benning Power Electronics Pte Ltd<br />
1, Kaki Bukit View<br />
# 05-03/04 Techview<br />
SGP-Singapore 415941<br />
Tel. (65) 6844 3133<br />
Fax (65) 6844 3279<br />
E-Mail: benning@singnet.com.sg<br />
Belgium<br />
Benning Belgium<br />
Power Electronics<br />
Z. 2 Essenestraat 16<br />
B-1740 Ternat<br />
Tel. 02 / 58 287 84 (85)<br />
Fax 02 / 58 287 69<br />
E-Mail: info@benning.be<br />
Italy<br />
Benning Conversione di Energia S.r.l.<br />
Via E. Mattei, 7<br />
I-40138 Bologna<br />
Tel. 0 51/5319 55<br />
Fax 0 51 / 530923<br />
E-Mail: benning.energia@libero.it<br />
Sweden<br />
Eldaco AB<br />
Box 990, Hovslagarev. 3B<br />
S-19129 Sollentuna<br />
Tel. 08 / 6239500<br />
Fax 08/969772<br />
E-Mail: power@eldaco.se<br />
Czech Republic<br />
Benning CR s.r.o.<br />
Zahradní ul. 894<br />
CZ-293 06 Kosmonosy<br />
(Mladá Boleslav)<br />
Tel. 3 26721003<br />
Fax 3 26 72 25 33<br />
E-Mail: benning@benning.cz<br />
Netherlands<br />
Benning NL<br />
Power Electronics<br />
Peppelkade 42<br />
NL-3992 AK Houten<br />
Tel. 0 30/6346010<br />
Fax 0 30 / 6 34 60 20<br />
E-Mail: info@benning.nl<br />
Switzerland<br />
Benning Power Electronics GmbH<br />
Industriestrasse 6<br />
CH-8305 Dietlikon<br />
Tel. 01/ 8057575<br />
Fax 01/8057580<br />
E-Mail: info@benning.ch<br />
France<br />
Benning Conversion d’énergie<br />
43, avenue Winston Churchill<br />
B.P. 418<br />
F-27404 Louviers Cedex<br />
Tél. 0 / 2.32.25.23.94<br />
Fax 0/2.32.25.08.64<br />
E-Mail: info@benning.fr<br />
Poland<br />
Benning Power Electronics Sp.z.o.o.<br />
Korczunkowa 30<br />
PL-05-503 Glosków<br />
Tel. 0 22 / 7 57 84 53 / 7 57 36 68-70<br />
Fax 0 22 /75784 52<br />
E-Mail: biuro@benning.biz<br />
Spain<br />
Benning Conversión de Energía S.A.<br />
C/Pico de Santa Catalina 2<br />
Pol. Ind. Los Linares<br />
E-28970 Humanes, Madrid<br />
Tel. 91/ 6048110<br />
Fax 91/6048402<br />
E-Mail: benningcde@retemail.es<br />
ISO 14001<br />
Germany<br />
Theo Benning<br />
Elektrotechnik und Elektronik GmbH & Co.KG<br />
Münsterstr. 135-137<br />
D-46397 Bocholt<br />
Tel. 0 28 71/ 93-0<br />
Fax 0 28 71/93297<br />
E-Mail: info@benning.de<br />
Great-Britain<br />
Benning Power Electronics (UK) Ltd.<br />
Oakley House<br />
Hogwood Lane<br />
Finchampstead<br />
GB-Berkshire<br />
RG 40 4QW<br />
Tel. 0118 9731506<br />
Fax 0118 9731508<br />
E-Mail: info@benninguk.com<br />
Hungary<br />
Benning Kft.<br />
Power Electronics<br />
Rákóczi út 262<br />
H-2541 Lábatlan<br />
Tel. 033 / 50 7600<br />
Fax 033 / 50 7601<br />
E-Mail: benning@vnet.hu<br />
P. R. of China<br />
Benning V. GmbH<br />
Shanghai Repr. Office<br />
1233 Si Ping Rd., Rm. 006<br />
PRC-200 092 Shanghai<br />
Tel. 021 5557 0609<br />
Fax 021 6504 1878<br />
E-Mail: benning@public8.sta.net.cn<br />
Russian Federation<br />
OOO Benning Power Electronics<br />
Schtscholkovskoje Chaussee, 5<br />
RF-105122 Moscow<br />
Tel. 0 95/9676850<br />
Fax 0 95 / 9 67 68 51<br />
E-Mail: benning@mtu-net.ru<br />
Slovakia<br />
Benning Slovensko, s.r.o.<br />
Kukuričná 17<br />
SK-83103 Bratislava<br />
Tel. 02 / 44459942<br />
Fax 02 / 44455005<br />
E-Mail: benning@internet.sk<br />
Ukraine<br />
Benning<br />
ul. Solomenskaja, 3B<br />
UA-252110 Kiew<br />
Tel. 044 / 246 10 25<br />
Fax 044 / 248 92 36<br />
E-Mail: benning@benning.com.ua<br />
U.S.A.<br />
Lucas-Benning<br />
Power Electronics, Inc.<br />
11120 Grader Street<br />
USA-Dallas, TX 75238<br />
Tel. 214 5531444<br />
Fax 214 5531355<br />
E-Mail: sales@lucasbenning.com<br />
784165.03 10/2003 paus Design & Medien, Bocholt Subject to alterations. Printed on chlorine free paper.