D—Service Test for Fire Hose<br />
and dust cannot be removed thoroughly by<br />
brushing, or if the hose has come in contact<br />
with harmful chemicals, it should be washed. If<br />
detergent is used, use a mild solution and<br />
rinse thoroughly with clean water.<br />
Wet hose should be drained and completely<br />
dried before being placed in service or<br />
storage. Hose should not be dried on hot<br />
pavements or under intense sunlight. Wet<br />
hose, even the lightweight all-synthetic,<br />
should be thoroughly dried. Cotton-synthetic<br />
hose has been treated for mildew protection<br />
but will mildew under prolonged wet<br />
conditions. In addition, linen hose must be<br />
thoroughly dried immediately after testing to<br />
avoid mildew.<br />
Allow the jacket to dry completely by hanging a<br />
50-foot length of hose from the middle. Hang a<br />
100-foot length of hose from the middle and<br />
allow to drain for a minimum of 4 hours. After 4<br />
hours, double the hose and continue to dry for<br />
2 to 3 days or longer as required. The<br />
couplings should be off the ground at all times.<br />
Salvaging bad hose<br />
All hose failing the visual exam and the<br />
pressure test should be tagged, repaired, or<br />
disposed of as per your agencies guidelines.<br />
In the field, tie a knot in failed hose to avoid<br />
reuse. If a 100-foot length of hose fails, it<br />
should be shortened to 50 feet. If a 50-foot<br />
length of hose fails, it should be shortened to<br />
no less than 45 feet. Good couplings should be<br />
salvaged from discarded hose.<br />
Hose that has been repaired or recoupled<br />
should be retested at a test pressure of at least<br />
50 percent greater than the service test<br />
pressure.<br />
Place a readily visible, distinguishing mark<br />
noting the location of the hose defect, before<br />
sending it in. Good couplings should be<br />
salvaged from any hose not repairable. For<br />
defective couplings, the couplings should be<br />
cut from the hose and the hose sent in for recoupling.<br />
When a length of hose is recoupled,<br />
the tailpiece gasket should be replaced. For<br />
additional information, consult the “Fire<br />
<strong>Equipment</strong> Storage and Refurbishing<br />
Standards,” <strong>National</strong> <strong>Wildfire</strong> <strong>Coordinating</strong><br />
Group, NFES Number 2249, November 1994.<br />