UDFCD <strong>BMP</strong> MONITORING SITES<br />
Open Bed S<strong>and</strong> Filter<br />
Impermeable<br />
Membrane <strong>and</strong><br />
Geotextile Liners<br />
When expansive or NRCS Type D soils are present, or<br />
when st<strong>and</strong>ard percolation tests show percolation<br />
drawdown rates exceeding 60 minutes per inch, or<br />
potential for groundwater contamination exists, install a<br />
16 mil thick impermeable liner on the bottom <strong>and</strong><br />
sides of the basin. If vertical walls are permeable or of<br />
stacked blocks, extend the impermeable liner behind the<br />
walls.<br />
If soils are not expansive (i.e., NRCS Type A, B or C),<br />
use a woven geotextile material that meets the<br />
following ASTM requirements:<br />
o D-4751 – AOS U.S. Std. Sieve #50 to #70<br />
o D-4633 – Trapezoidal tear strength >= 100x60 lbs<br />
o COE specified open area >= 4%.<br />
Products meeting requirements: US Fabric US 2070 <strong>and</strong><br />
US 670, Mirafi Filterweave 500 <strong>and</strong> 700, Carthage Mills<br />
Carthage 6%.<br />
Wrap all liners to top of the s<strong>and</strong> filter basin <strong>and</strong> attach<br />
firmly with staples to the soil vertical wall using staples or<br />
concrete anchors. Provide sufficient slack so that the<br />
liners are not stretched when rock <strong>and</strong> s<strong>and</strong>/peat mix is<br />
placed. If tears are seen or discovered, repair them as<br />
recommended by manufacturer with no less than 18<br />
inches of overlap on all sides of the tear.<br />
Outlet Works<br />
When underdrains are needed, the outlet<br />
works consists of 4” perforated HDPE<br />
pipe to convey water to the overflow outlet<br />
structure. Space perforated pipe on 20 foot<br />
centers or less. At the outlet of the HDPE<br />
pipe into the box, install an orifice sized to<br />
empty the WQCV above the s<strong>and</strong> in no less<br />
than 24 hours.<br />
Provided an overflow outlet pipe out of the<br />
overflow structure to convey flows away from<br />
the filter basin when the runoff volume exceeds<br />
the WQCV at rates required by local<br />
jurisdiction to control the flood detention,<br />
typically the 10- <strong>and</strong> the 100-year storm.