Chapter 7<br />

Construction BMPs<br />

5.2 Slope-Length and Runoff<br />

Considerations<br />

Cut-and-fill slopes should be designed<br />

and constructed to minimize erosion.<br />

This requires consideration of <strong>the</strong> length<br />

and steepness of <strong>the</strong> slope, <strong>the</strong> soil type,<br />

upslope drainage area, groundwater<br />

conditions and o<strong>the</strong>r applicable factors.<br />

Slopes found to be eroding excessively<br />

will require additional slope stabilization<br />

until <strong>the</strong> problem is corrected. The<br />

following guidelines should assist site<br />

planners and plan reviewers in<br />

developing an adequate design:<br />

• Rough soil surfaces enhance<br />

infiltration and/or leng<strong>the</strong>n <strong>the</strong> travel<br />

path or runoff, reducing runoff<br />

velocity. See <strong>the</strong> Surface Roughening BMP Fact Sheet.<br />

Photograph 7-2. Diverting <strong>the</strong> upland slope drainage area may have<br />

avoided <strong>the</strong> rilling shown in this picture.<br />

• Temporary diversion dikes should be constructed at <strong>the</strong> top of long or steep slopes. Diversion dikes<br />

or terraces reduce slope length within <strong>the</strong> disturbed area. See <strong>the</strong> Earth Dikes and <strong>Drainage</strong> Swales<br />

BMP Fact Sheet.<br />

• Temporary diversion dikes should be provided whenever:<br />

where:<br />

S 2 L > 2.5 for undisturbed tributary areas; Equation 7-1<br />

S 2 L > 1.0 for disturbed tributary areas; Equation 7-2<br />

S 2 L > 0.25 for paved tributary areas; Equation 7-3<br />

S = slope of <strong>the</strong> upstream tributary area (feet/foot)<br />

L = length of <strong>the</strong> upstream slope (feet)<br />

As an example, runoff from a developed area runs on to an area that will be disturbed. A<br />

diversion dike would be required if, for example, <strong>the</strong> length of <strong>the</strong> flow path was greater than 625<br />

feet and <strong>the</strong> slope of <strong>the</strong> flow path was 2%.<br />

• Concentrated stormwater (e.g., pipe outflow, channel, swale) should not be allowed to flow down cut<br />

or fill slopes unless contained within an adequately-sized temporary channel diversion, a permanent<br />

channel, or temporary slope drain. See <strong>the</strong> Temporary Slope Drain and Diversion Ditches/Channels<br />

BMP Fact Sheets.<br />

• Wherever a slope face crosses a water seepage plane that endangers <strong>the</strong> stability of <strong>the</strong> slope,<br />

adequate drainage should be provided.<br />

7-20 <strong>Urban</strong> <strong>Drainage</strong> and Flood Control District November 2010<br />