04.10.2014 Views

ASHRAE Journal: Designing Chilled Beams for Thermal ... - TROX

ASHRAE Journal: Designing Chilled Beams for Thermal ... - TROX

ASHRAE Journal: Designing Chilled Beams for Thermal ... - TROX

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>for</strong> a space whose latent gains total 400 Btu/h (117 W) can be<br />

calculated <strong>for</strong> various design humidity ratios:<br />

If W R OOM = 65 grains (50% RH) → Q PRIMARY = 84 cfm<br />

If W R OOM = 68 grains (52% RH) → Q PRIMARY = 59 cfm<br />

If W R OOM = 69 grains (53% RH) → Q PRIMARY = 53 cfm<br />

In this case, designing <strong>for</strong> 75°F (24°C) and 50% relative<br />

humidity would result in a primary airflow rate that is 58%<br />

higher than that required to maintain 53% RH in the space. As<br />

the 53% RH is within Standard 55-2004 recommendations and<br />

results in a space dew-point temperature of 57°F (14°C), it is<br />

probably a reasonable design goal.<br />

<strong>Chilled</strong> beams are often used with central HVAC equipment<br />

that includes heat recovery and enthalpy wheels. Lower space<br />

dew-point temperatures can be achieved when the dew-point<br />

temperature is further suppressed by these processes. In cases<br />

where room dew-point temperatures below 55°F (13°C) are<br />

desired, using such equipment is recommended.<br />

Summary<br />

Active chilled beams can be selected to remove large amounts<br />

of sensible heat while substantially reducing primary airflow<br />

requirements. However, this must be done with consideration<br />

Advertisement <strong>for</strong>merly in this space.<br />

of the occupant thermal com<strong>for</strong>t and space dehumidification.<br />

Because producing high levels of thermal com<strong>for</strong>t is the primary<br />

objective of any com<strong>for</strong>t cooling application, beams should be<br />

selected, sized and located with that in mind.<br />

While primary airflow reduction opportunities are an inherent<br />

characteristic of chilled beams, the reduction of such should<br />

be limited to that required to provide adequate space humidity<br />

control. All-air systems almost always deliver a sufficient<br />

amount of dry air to satisfy the space sensible load, there<strong>for</strong>e,<br />

engineers often do not consider space latent loads in their selection.<br />

Individual space latent loads should be considered when<br />

designing chilled beam systems.<br />

In conclusion, the following design guidelines should be observed<br />

when selecting, sizing and locating active chilled beams:<br />

• <strong>Chilled</strong> beams should not be used in low ceiling<br />

height applications where the distance between the<br />

ceiling and the top of the occupied zone is less than<br />

3 ft (0.9 m).<br />

• When applied in lobbies, atriums or other areas with<br />

high and/or uncontrollable infiltration rates, provide<br />

adequate condensation prevention strategies.<br />

• To maintain high levels of thermal com<strong>for</strong>t (velocities<br />

within the occupied zone no greater than 50 fpm<br />

or [0.25 m/s]), active chilled beams were mounted<br />

at least 3.5 ft (1.1 m) above the designated occupied<br />

zone should be sized and located such that their throw<br />

to a terminal velocity of 100 fpm (0.5 m/s) does not<br />

exceed half the distance between them and another<br />

beam with an opposing blow. Active beams mounted<br />

6 ft (2 m)or more above the designated occupied zone<br />

may be located such that their throw to a terminal<br />

velocity of 150 fpm (0.75 m/s) is as much as half the<br />

distance between the beam and an adjacent beam with<br />

an opposing discharge.<br />

• Smaller nozzles result in higher induction ratios and<br />

higher sensible cooling capacities per cfm (m 3 /h) of<br />

primary air. However, the use of smaller nozzles generally<br />

results in higher noise levels and inlet pressure<br />

requirements <strong>for</strong> a given primary airflow rate that<br />

increases the number of beams required.<br />

• <strong>Designing</strong> <strong>for</strong> space humidity levels lower than that<br />

actually required may result in significantly higher<br />

primary airflow rates.<br />

References<br />

1. ANSI/<strong>ASHRAE</strong> Standard 55-2004, <strong>Thermal</strong> Environmental<br />

Conditions <strong>for</strong> Human Occupancy.<br />

2. Standard 55-2004, p. 3.<br />

3. 2009 <strong>ASHRAE</strong> Handbook—Fundamentals, p. 20.13.<br />

4. Koestal, A. 1954. “Computing temperature and velocities in<br />

vertical jets of hot or cold air.” ASHVE Transactions 60:385.<br />

5. 2007 <strong>ASHRAE</strong> Handbook—HVAC Applications, p. 56.4.<br />

6. ANSI/<strong>ASHRAE</strong> Standard 62.1-2004, Ventilation <strong>for</strong> Acceptable<br />

Indoor Air Quality, Table 6-1.<br />

7. Standard 55-2004, p. 5.2.1.1.<br />

8. 2009 <strong>ASHRAE</strong> Handbook—Fundamentals, p. 9.12.<br />

6 4 A S H R A E J o u r n a l O c t o b e r 2 0 0 9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!