04.10.2014 Views

ASHRAE Journal: Designing Chilled Beams for Thermal ... - TROX

ASHRAE Journal: Designing Chilled Beams for Thermal ... - TROX

ASHRAE Journal: Designing Chilled Beams for Thermal ... - TROX

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

This article was published in <strong>ASHRAE</strong> <strong>Journal</strong>, Vol. 51, October 2009. Copyright 2009 American Society of Heating, Refrigerating and Air-<br />

Conditioning Engineers, Inc. Reprinted by permission at www.troxusa.com. This article may not be copied and/or distributed electronically or<br />

in paper <strong>for</strong>m without permission of <strong>ASHRAE</strong>. For more in<strong>for</strong>mation about <strong>ASHRAE</strong> <strong>Journal</strong>, visit www.ashrae.org.<br />

DESIGNING<br />

<strong>Chilled</strong> <strong>Beams</strong><br />

FOR<br />

<strong>Thermal</strong> Com<strong>for</strong>t<br />

By Ken Loudermilk, P.E., Member <strong>ASHRAE</strong><br />

Active chilled beams have been used in Europe since the mid-1990s but<br />

only recently have become a popular alternative to all-air HVAC systems<br />

<strong>for</strong> nonresidential buildings in North America. Although active chilled beams<br />

are an in-room space conditioning device, they are also the room air diffusion<br />

device, so sizing and locating the beams is vital to providing acceptable levels<br />

of occupant thermal com<strong>for</strong>t as established by <strong>ASHRAE</strong>’s thermal com<strong>for</strong>t<br />

standard (55-2004). 1<br />

Designers also should devote adequate<br />

consideration to the specification<br />

and maintenance of space humidity<br />

levels where chilled beams are to be<br />

used. <strong>Designing</strong> <strong>for</strong> space humidity<br />

levels that are unnecessarily low can<br />

result in primary airflow rates that are<br />

higher than necessary, and neglecting<br />

space latent loads can lead to excessive<br />

space humidity levels and potential<br />

condensation issues.<br />

Principles of Operation<br />

Figure 1 illustrates an active chilled<br />

beam. Primary air that has been cooled<br />

and dehumidified (1) is ducted from<br />

the central air-handling unit to a distribution<br />

plenum within the beam from<br />

which it is injected (2) through a series<br />

of nozzles. The velocity of the primary<br />

air jets entrain room air (3) through<br />

the beam’s integral heat transfer coil<br />

where it is reconditioned (4), then subsequently<br />

mixed with the primary air<br />

be<strong>for</strong>e this mixture is discharged to the<br />

space (5). The volume of induced room<br />

air is typically two to five times that of<br />

the primary air, depending on the size<br />

and design of the induction nozzles<br />

used, thus the discharge air mixture is<br />

three to six times the primary airflow<br />

rate. The ratio of the induced airflow<br />

rate to the primary (ducted) airflow rate<br />

is referred to as the beam’s induction<br />

ratio (IR).<br />

About the Author<br />

Ken Loudermilk, P.E., is the vice president of<br />

technology development <strong>for</strong> <strong>TROX</strong> USA, Cumming,<br />

Ga. He is vice chair of <strong>ASHRAE</strong> Technical<br />

Committee 5.3, Room Air Distribution, and chairs<br />

the TC 5.3 subcommittee on chilled beams.<br />

5 8 A S H R A E J o u r n a l a s h r a e . o r g O c t o b e r 2 0 0 9


The sensible cooling coil within the beam is supplied with<br />

chilled water whose supply temperature is maintained at, or<br />

above, the space dew-point temperature to prevent condensation.<br />

The sensible heat removed by the coil typically constitutes<br />

50% to 75% of the required space sensible heat removal. As a<br />

result, the primary airflow rate required to accomplish the space<br />

sensible cooling can be reduced accordingly.<br />

Although primary (ducted) airflow rates associated with<br />

chilled beams are considerably lower than those in all-air systems,<br />

their discharge airflow rate to the room is always greater.<br />

Since the chilled water supplied to the beam is maintained<br />

above the space dew point, the beam’s off-coil temperature<br />

will be higher than the primary air temperatures used in all-air<br />

systems. The resultant temperature of the beam’s discharge<br />

mixture is typically 3°F to 6°F (2°C to 3.3°C) warmer than<br />

that of all-air systems. There<strong>for</strong>e, a proportionally higher<br />

(20% to 30%) discharge airflow rate to the space must be<br />

provided. This higher discharge flow rate often contributes to<br />

greater draft risks, which may compromise occupant thermal<br />

com<strong>for</strong>t levels.<br />

V L ’ T L<br />

1<br />

Beam A<br />

V O ’ T O<br />

Q S<br />

Q A Q A<br />

2<br />

4<br />

5<br />

3<br />

A<br />

Beam B<br />

V C<br />

V O ’ T O<br />

Q S<br />

H1<br />

V H1 ’ T H1<br />

<strong>Designing</strong> <strong>for</strong> Occupant <strong>Thermal</strong> Com<strong>for</strong>t<br />

Standard 55-2004 2 defines the occupied zone as the portion of<br />

a space where occupants normally reside. It is further quantified<br />

as the volume of the room that is (1) no closer than 3.3 ft (1 m)<br />

from any outside walls or windows nor within 1 ft (0.3 m) of<br />

any internal wall and (2) is vertically bounded by the floor and<br />

the head level of the predominant space occupants. Although<br />

the head level is often accepted to be 67 in. (1.7 m) <strong>for</strong> standing<br />

occupants, the standard allows the designer to define that<br />

height according to the space occupancy.<br />

For example, if a space is predominantly occupied by seated<br />

persons, the occupied zone height could be considered as 42 in.<br />

(1.1 m). Chapter 20 of the 2007 <strong>ASHRAE</strong> Handbook— HVAC<br />

Applications 3 predicts the percentage of occupants who might<br />

express thermal dissatisfaction <strong>for</strong> various combinations of<br />

local air speed and temperatures. Figure 2 (from that chapter)<br />

can be used to predict the percentage of occupants that will<br />

object to various air speeds and temperatures at the neck and<br />

ankle regions. As active chilled beams are normally mounted<br />

overhead, the neck region is usually the most critical. Com<strong>for</strong>t<br />

cooling applications should strive to minimize dissatisfaction<br />

levels, and in all cases limit the percentage of occupants objecting<br />

to these local conditions to 20% or less.<br />

Room Air Distribution<br />

Active chilled beams distribute air within the room in a<br />

manner consistent with that of linear slot diffusers. As such,<br />

relationships between airstream terminal velocities and thermal<br />

decay of the supply airstream that apply to linear slot diffusers<br />

also apply to active chilled beams. Upon discharge to the open<br />

space, velocity and temperature differentials between the supply<br />

air mixture and the room begin to diminish due to room air<br />

entrainment. Linear slot diffusers exhibit relatively long throw<br />

characteristics and their velocity and temperature differentials<br />

1 m<br />

(0.3 ft)<br />

Occupied Zone<br />

(Height Determined By Designer)<br />

Figure 1: Application of active chilled beams.<br />

diminish at a rate that is proportional to the distance the air has<br />

traveled within the space.<br />

Manufacturers publish throw values that allow designers to<br />

estimate the travel distance of the airstream be<strong>for</strong>e it reaches a<br />

given terminal velocity. Most manufacturers present such data<br />

using isothermal air <strong>for</strong> terminal velocities of 150, 100 and 50<br />

fpm (0.75, 0.5 and 0.25 m/s). These data can be used to map<br />

the airstream and predict the local velocity at the point where it<br />

enters the occupied zone. As the room-to-supply-air-differential<br />

decays at a similar rate, its temperature also can be predicted<br />

at the entry point based on the initial temperature difference<br />

(ΔT O ) between the beam discharge temperature and that of the<br />

room into which it is introduced. Manufacturers supply selection<br />

software that can be used predict the value of local velocities<br />

and temperatures at critical locations such as that where the<br />

airstream enters the occupied zone.<br />

Figure 1 illustrates a space being served by two active beams<br />

with two-way discharge patterns delivering identical primary<br />

(Q P ) and discharge (Q S ) airflow rates. The discharge airflow<br />

rate is a function of the induction ratio of the nozzles chosen<br />

and is calculated by multiplying the primary airflow rate by the<br />

induction ratio. Assume a beam produces an induction ratio of<br />

2.5 and is sized to deliver 100 cfm (170 m 3 /h) of 55°F (13°C)<br />

primary air to a 75°F (24°C) room. Also, assume that chilled<br />

water enters the beam at 57°F (14°C) and leaves at 61°F (16°C).<br />

The discharge airflow rate to the space will be 3.5 times the<br />

O c t o b e r 2 0 0 9 A S H R A E J o u r n a l 5 9


primary airflow rate or 350 cfm (595 m 3 /h). The temperature<br />

(T OC ) of the air leaving the beam’s integral cooling coil can<br />

be conservatively estimated as 1°F (0.6°C) warmer than its<br />

mean chilled water temperature, which is the average of the<br />

entering and leaving chilled water temperatures. In fact, the<br />

leaving air temperature would typically be at least 2°F to 4°F<br />

(1°C to 2°C) higher than the coil mean water temperature. The<br />

beam manufacturer has this in<strong>for</strong>mation as well as the beam’s<br />

IR. Upon identifying the primary air temperature (T PA ), the<br />

temperature (T Z ) leaving the beam as well as the initial room<br />

to supply air temperature difference (ΔT Z ) can be estimated<br />

using Equations 1 and 2.<br />

T Z = [T PA + (T OC × IR)] / (IR+1) (1)<br />

or, <strong>for</strong> this example,<br />

ΔT Z = T ROOM – T Z (2)<br />

T Z = [55°F + (60°F × 2.5)] / (2.5 + 1) = 58.6°F and<br />

ΔT Z = 75°F – 58.6°F = 16.4°F<br />

The initial velocity (V O ) of a supply airstream leaving the<br />

discharge slot can be calculated by dividing the supply airflow<br />

rate leaving each slot (<strong>for</strong> two-way beams this is 0.5 x Q S ) by the<br />

effective area of that slot. If the effective area is not available,<br />

V O can be conservatively estimated as 450 fpm (2.3 m/s) <strong>for</strong> the<br />

purposes of this calculation. The local temperature difference<br />

(ΔT X ) between the room and the supply airstream at any point<br />

along its travel can be estimated by Equation 3. 4<br />

ΔT X = 0.8 × ΔT Z × (V X / V O ) (3)<br />

For a beam with an initial discharge velocity (V O ) of 450 fpm<br />

(2.3 m/s) and an initial supply to room temperature differential<br />

(ΔT Z ) of 16.4°F (9.1°C), the local temperature differential (ΔT X )<br />

at the point coincident with a 50 fpm (0.25 m/s) terminal velocity<br />

is about 1.4°F (0.9°C). Referring to Figure 2, this predicts<br />

that less than 20% of the occupants would be dissatisfied with<br />

these local velocity/temperature conditions.<br />

As the region near the outside walls is not defined as part<br />

of the occupied zone, local velocities and temperatures do not<br />

generally affect occupant thermal com<strong>for</strong>t. Care should still be<br />

taken that they are not so high that they can affect processes<br />

(e.g., fume hoods) along the outer wall and that they are sufficient<br />

to provide adequate heating where applicable. Chapter 56<br />

of the 2007 <strong>ASHRAE</strong> Handbook—HVAC Applications 5 recommends<br />

that outlets used <strong>for</strong> perimeter heating be selected and<br />

located such that their isothermal throw to 150 fpm (0.75 m/s)<br />

extends at least halfway down the outside surface or to a level<br />

5 ft (1.5 m) above the floor, whichever is greater.<br />

The area of greatest draft risk usually occurs directly below<br />

the point where two opposing airstreams collide. Figure 1 illustrates<br />

such a point and defines the collision velocity as V C .<br />

If the velocity (V C ) of the colliding airstreams is of sufficient<br />

velocity (greater than 100 fpm or 0.5 m/s), some of the velocity<br />

and temperature differential of the airstreams is dissipated by the<br />

collision and the velocity (V H1 ) at the point where the airstream<br />

Figure 2: Percentage of occupants objecting to drafts in air. 3<br />

enters the occupied zone is reduced accordingly. Figure 3 can<br />

be used to estimate the velocity at the entry point <strong>for</strong> various<br />

collision velocities and vertical distances (H1) between the<br />

point of collision and the top of the occupied zone. This figure<br />

illustrates that the velocity (V H1 ) entering the occupied zone<br />

directly below the point of collision of two airstreams will be<br />

less than half the collision velocity (V C ) if distance H1 (the<br />

distance between the ceiling and the top of the designated occupied<br />

zone) is greater than or equal to 3.5 ft (1.1 m).<br />

In cases where the collision velocity (V C ) is 100 fpm (0.5 m/s)<br />

V H1 would be less than or equal to 50 fpm provided H1 is greater<br />

than 3.5 ft (1.1 m). In cases where H1 is greater than 3.5 ft (1.1<br />

m), active chilled beams should be sized and located so that<br />

their throw to a terminal velocity of 100 fpm (0.5 m/s) does not<br />

exceed half the distance to another beam with an opposing blow.<br />

In cases where the collision velocity (V C ) is 150 fpm (0.75<br />

m/s), V H1 is less than or equal to 50 fpm provided H1 is greater<br />

than 6 ft (1.8 m). Active beams <strong>for</strong> which H1 is greater than<br />

6 0 A S H R A E J o u r n a l a s h r a e . o r g O c t o b e r 2 0 0 9


or equal to 6 ft (1.8 m) can be sized such that their throw to a<br />

terminal velocity of 150 fpm (0.75 m/s) does not exceed half<br />

the distance to a beam with an opposing discharge.<br />

Figure 3 can be used to determine the maximum collision<br />

velocity that limits velocities within the occupied zone to 50<br />

fpm (0.25 m/s) or less <strong>for</strong> any given distance H1 using the following<br />

equation:<br />

V C = 50 / (V H1 / V C ) (4)<br />

where V H1 / V C is the value from Figure 3 that corresponds to<br />

the distance H1.<br />

For example, if H1 is equal to 4 ft,<br />

V C = 50 / 0.43 = 116 fpm<br />

Room Humidity Design Considerations<br />

The sensible cooling contribution with chilled beams af<strong>for</strong>ds<br />

the designer an opportunity to significantly reduce the<br />

primary airflow rate compared to all air systems. As 50% to<br />

75% of the sensible heat gains are typically removed by the<br />

chilled water coil, proportional reductions in the primary<br />

airflow rates within the system may be achievable. However,<br />

this should be done with caution as the beam must also deliver<br />

sufficient ventilation air and maintain acceptable space<br />

humidity levels. The primary airflow rate to the room must<br />

be the greater of that required to (1) ventilate the space in<br />

con<strong>for</strong>mance to <strong>ASHRAE</strong> Standard 62.1-2007 6 (or other<br />

applicable ventilation codes); (2) offset space latent gains<br />

to control the room humidity level within <strong>ASHRAE</strong> Standard<br />

55-2004 recommendations; and (3) provide sufficient<br />

sensible cooling to complement the sensible heat removed<br />

by the chilled water coil.<br />

In most common interior space applications, the primary<br />

airflow rate required to offset space latent gains will exceed<br />

both the ventilation airflow rate and the airflow rate required<br />

to complement the coil’s sensible cooling. The space airflow<br />

rate will be determined by the latent gains and the design<br />

room humidity ratio (W ROOM ). In perimeter spaces, the<br />

primary airflow rate to the beams will be driven by the sensible<br />

load (laboratories may be exceptions due to their high<br />

mandated ventilation rates). The use of beams whose water<br />

side cooling capacity contributes to more than about 65%<br />

of the total space load may be impractical due to architectural<br />

constraints that limit the installed beam quantities and<br />

lengths in these spaces. The goal of the design should be to<br />

reduce the primary airflow rate to as close to the required<br />

ventilation rate as possible.<br />

<strong>Designing</strong> chilled beam systems to maintain room air humidity<br />

levels lower than necessary can result in considerably<br />

higher primary air requirements. Figure 4 is presented in<br />

Standard 55-2004 7 and prescribes acceptable ranges of room<br />

temperatures and humidity ratios. Assuming a clothing level<br />

of 1.0 clo (0.15 m 2 · k/W), this diagram defines the thermal<br />

com<strong>for</strong>t window <strong>for</strong> a dry-bulb temperature of 75°F (24°C)<br />

to include room dew-point temperatures as high as 62°F<br />

Distance H1 (ft)<br />

7.0<br />

6.5<br />

6.0<br />

5.5<br />

5.0<br />

4.5<br />

4.0<br />

3.5<br />

3.0<br />

2.5<br />

0.3 0.4 0.5 0.6 0.7<br />

V H1 /V C<br />

Figure 3: Velocities entering the occupied zone.<br />

Figure 4: <strong>ASHRAE</strong> Summer and Winter Com<strong>for</strong>t Zones. Acceptable<br />

ranges of operative temperature and humidity with air speed ≤ 40<br />

fpm (≤0.20 m/s) <strong>for</strong> people wearing 1.0 and 0.5 clo (0.15 m 2 · k/W<br />

and 0.08 m 2 · k/W) clothing during primarily sedentary activity<br />

(≤1.1 met [≤63.9 W/m 2 ]). 8<br />

(16.7°C). Where chilled beams are applied, the room dewpoint<br />

temperature must not exceed the chilled water supply<br />

temperature, so design <strong>for</strong> dew points above about 57°F (14°C)<br />

is not recommended.<br />

Most conventional HVAC systems condition delivered air to<br />

about a 52°F (11°C) dew-point temperature, which coincides<br />

with a humidity ratio (W PRIMARY ) of 58 grains (3.8 g). The<br />

airflow rate (Q PRIMARY ) to offset the space latent heat gains<br />

(q LATENT ) can be determined by Equation 5.<br />

Q PRIMARY = q LATENT / [0.68 × (W ROOM – W PRIMARY )] (5)<br />

Using this equation and assuming the humidity ratio of the<br />

primary air is 58 grains (3.8 g), the primary airflow requirement<br />

6 2 A S H R A E J o u r n a l a s h r a e . o r g O c t o b e r 2 0 0 9


<strong>for</strong> a space whose latent gains total 400 Btu/h (117 W) can be<br />

calculated <strong>for</strong> various design humidity ratios:<br />

If W R OOM = 65 grains (50% RH) → Q PRIMARY = 84 cfm<br />

If W R OOM = 68 grains (52% RH) → Q PRIMARY = 59 cfm<br />

If W R OOM = 69 grains (53% RH) → Q PRIMARY = 53 cfm<br />

In this case, designing <strong>for</strong> 75°F (24°C) and 50% relative<br />

humidity would result in a primary airflow rate that is 58%<br />

higher than that required to maintain 53% RH in the space. As<br />

the 53% RH is within Standard 55-2004 recommendations and<br />

results in a space dew-point temperature of 57°F (14°C), it is<br />

probably a reasonable design goal.<br />

<strong>Chilled</strong> beams are often used with central HVAC equipment<br />

that includes heat recovery and enthalpy wheels. Lower space<br />

dew-point temperatures can be achieved when the dew-point<br />

temperature is further suppressed by these processes. In cases<br />

where room dew-point temperatures below 55°F (13°C) are<br />

desired, using such equipment is recommended.<br />

Summary<br />

Active chilled beams can be selected to remove large amounts<br />

of sensible heat while substantially reducing primary airflow<br />

requirements. However, this must be done with consideration<br />

Advertisement <strong>for</strong>merly in this space.<br />

of the occupant thermal com<strong>for</strong>t and space dehumidification.<br />

Because producing high levels of thermal com<strong>for</strong>t is the primary<br />

objective of any com<strong>for</strong>t cooling application, beams should be<br />

selected, sized and located with that in mind.<br />

While primary airflow reduction opportunities are an inherent<br />

characteristic of chilled beams, the reduction of such should<br />

be limited to that required to provide adequate space humidity<br />

control. All-air systems almost always deliver a sufficient<br />

amount of dry air to satisfy the space sensible load, there<strong>for</strong>e,<br />

engineers often do not consider space latent loads in their selection.<br />

Individual space latent loads should be considered when<br />

designing chilled beam systems.<br />

In conclusion, the following design guidelines should be observed<br />

when selecting, sizing and locating active chilled beams:<br />

• <strong>Chilled</strong> beams should not be used in low ceiling<br />

height applications where the distance between the<br />

ceiling and the top of the occupied zone is less than<br />

3 ft (0.9 m).<br />

• When applied in lobbies, atriums or other areas with<br />

high and/or uncontrollable infiltration rates, provide<br />

adequate condensation prevention strategies.<br />

• To maintain high levels of thermal com<strong>for</strong>t (velocities<br />

within the occupied zone no greater than 50 fpm<br />

or [0.25 m/s]), active chilled beams were mounted<br />

at least 3.5 ft (1.1 m) above the designated occupied<br />

zone should be sized and located such that their throw<br />

to a terminal velocity of 100 fpm (0.5 m/s) does not<br />

exceed half the distance between them and another<br />

beam with an opposing blow. Active beams mounted<br />

6 ft (2 m)or more above the designated occupied zone<br />

may be located such that their throw to a terminal<br />

velocity of 150 fpm (0.75 m/s) is as much as half the<br />

distance between the beam and an adjacent beam with<br />

an opposing discharge.<br />

• Smaller nozzles result in higher induction ratios and<br />

higher sensible cooling capacities per cfm (m 3 /h) of<br />

primary air. However, the use of smaller nozzles generally<br />

results in higher noise levels and inlet pressure<br />

requirements <strong>for</strong> a given primary airflow rate that<br />

increases the number of beams required.<br />

• <strong>Designing</strong> <strong>for</strong> space humidity levels lower than that<br />

actually required may result in significantly higher<br />

primary airflow rates.<br />

References<br />

1. ANSI/<strong>ASHRAE</strong> Standard 55-2004, <strong>Thermal</strong> Environmental<br />

Conditions <strong>for</strong> Human Occupancy.<br />

2. Standard 55-2004, p. 3.<br />

3. 2009 <strong>ASHRAE</strong> Handbook—Fundamentals, p. 20.13.<br />

4. Koestal, A. 1954. “Computing temperature and velocities in<br />

vertical jets of hot or cold air.” ASHVE Transactions 60:385.<br />

5. 2007 <strong>ASHRAE</strong> Handbook—HVAC Applications, p. 56.4.<br />

6. ANSI/<strong>ASHRAE</strong> Standard 62.1-2004, Ventilation <strong>for</strong> Acceptable<br />

Indoor Air Quality, Table 6-1.<br />

7. Standard 55-2004, p. 5.2.1.1.<br />

8. 2009 <strong>ASHRAE</strong> Handbook—Fundamentals, p. 9.12.<br />

6 4 A S H R A E J o u r n a l O c t o b e r 2 0 0 9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!