Table ED-10— Unit Wiring With <strong>Electric</strong> <strong>Heat</strong> (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and<br />
151/181/ 241 Reheat Option(Downflow Only)<br />
Standard Indoor Motor Oversize Indoor Motor<br />
To Use <strong>Heat</strong>er <strong>Heat</strong>er Control Max Fuse Size or Max Fuse Size or<br />
Tons With Model No. KW Rating Stages MCA Max Circuit MCA Max Circuit<br />
Breaker 2 Breaker 1,2<br />
208/230 Volts Three Phase<br />
AYDHTRK318A 13.5/18.0 1 61/68 70/70 68/76 80/80<br />
12½ TCD151C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150<br />
AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200<br />
15<br />
AYDHTRK318A 13.5/18.0 1 74/74 100/100 80/80 90/90<br />
TCD181C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150<br />
AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200<br />
TCD181C3 *AYDHTRK318A 13.5/18.0 1 71/71 90/90 77/77 100/100<br />
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150<br />
17½ TCD211C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200<br />
AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250<br />
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150<br />
20 TCD241C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200<br />
AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250<br />
AYDHTRL336A 27.0/36.0 2 125/139 150/150 — —<br />
25 TCD301C3 AYDHTRL354A 40.5/54.0 2 171/193 175/200 — —<br />
AYDHTRK372A 54.0/72.0 2 218/247 225/250 — —<br />
460 Volts Three Phase<br />
AYDHTRL418A 18.0 1 34 35 37 40<br />
12½ TCD151C4 AYDHTRK436A 36.0 2 61 70 64 70<br />
AYDHTRK454A 54.0 2 88 90 91 100<br />
15<br />
TCD181C4<br />
AYDHTRL418A 18.0 1 37 50 39 50<br />
AYDHTRK427A 3 27.0 2 47 50 — —<br />
AYDHTRK436A 36.0 2 61 70 64 70<br />
AYDHTRK454A 54.0 2 88 90 91 100<br />
TCD181C4 *AYDHTRL418A 18.0 1 36 45 39 50<br />
AYDHTRL427A 3 27.0 2 51 60 — —<br />
AYDHTRL436A 36.0 2 64 70 68 70<br />
17½ TCD211C4 AYDHTRL454A 54.0 2 91 100 95 100<br />
AYDHTRK472A 72.0 2 118 125 123 125<br />
AYDHTRL427A 3 27.0 2 51 60 — —<br />
AYDHTRL436A 36.0 2 64 70 68 70<br />
20 TCD241C4 AYDHTRL454A 54.0 2 91 100 95 100<br />
AYDHTRK472A 72.0 2 118 125 123 125<br />
AYDHTRL427A 3 27.0 2 57 70 — —<br />
AYDHTRL436A 36.0 2 68 70 — —<br />
25 TCD301C4 AYDHTRL454A 54.0 2 95 100 — —<br />
AYDHTRK472A 72.0 2 123 125 — —<br />
Notes:<br />
1. HACR type circuit breaker per NEC.<br />
2. Values do not include power exhaust accessory.<br />
3. Do not use <strong>with</strong> oversized motor.<br />
* Applies only to Dehumidification (Hot Gas Reheat) Models<br />
60 RT-PRC002-EN