<strong>Electric</strong>al<br />

Data<br />

(High Efficiency)<br />

Table ED-10— Unit Wiring With <strong>Electric</strong> <strong>Heat</strong> (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and<br />

151/181/ 241 Reheat Option(Downflow Only)<br />

Standard Indoor Motor Oversize Indoor Motor<br />

To Use <strong>Heat</strong>er <strong>Heat</strong>er Control Max Fuse Size or Max Fuse Size or<br />

Tons With Model No. KW Rating Stages MCA Max Circuit MCA Max Circuit<br />

Breaker 2 Breaker 1,2<br />

208/230 Volts Three Phase<br />

AYDHTRK318A 13.5/18.0 1 61/68 70/70 68/76 80/80<br />

12½ TCD151C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150<br />

AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200<br />

15<br />

AYDHTRK318A 13.5/18.0 1 74/74 100/100 80/80 90/90<br />

TCD181C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150<br />

AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200<br />

TCD181C3 *AYDHTRK318A 13.5/18.0 1 71/71 90/90 77/77 100/100<br />

AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150<br />

17½ TCD211C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200<br />

AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250<br />

AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150<br />

20 TCD241C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200<br />

AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250<br />

AYDHTRL336A 27.0/36.0 2 125/139 150/150 — —<br />

25 TCD301C3 AYDHTRL354A 40.5/54.0 2 171/193 175/200 — —<br />

AYDHTRK372A 54.0/72.0 2 218/247 225/250 — —<br />

460 Volts Three Phase<br />

AYDHTRL418A 18.0 1 34 35 37 40<br />

12½ TCD151C4 AYDHTRK436A 36.0 2 61 70 64 70<br />

AYDHTRK454A 54.0 2 88 90 91 100<br />

15<br />

TCD181C4<br />

AYDHTRL418A 18.0 1 37 50 39 50<br />

AYDHTRK427A 3 27.0 2 47 50 — —<br />

AYDHTRK436A 36.0 2 61 70 64 70<br />

AYDHTRK454A 54.0 2 88 90 91 100<br />

TCD181C4 *AYDHTRL418A 18.0 1 36 45 39 50<br />

AYDHTRL427A 3 27.0 2 51 60 — —<br />

AYDHTRL436A 36.0 2 64 70 68 70<br />

17½ TCD211C4 AYDHTRL454A 54.0 2 91 100 95 100<br />

AYDHTRK472A 72.0 2 118 125 123 125<br />

AYDHTRL427A 3 27.0 2 51 60 — —<br />

AYDHTRL436A 36.0 2 64 70 68 70<br />

20 TCD241C4 AYDHTRL454A 54.0 2 91 100 95 100<br />

AYDHTRK472A 72.0 2 118 125 123 125<br />

AYDHTRL427A 3 27.0 2 57 70 — —<br />

AYDHTRL436A 36.0 2 68 70 — —<br />

25 TCD301C4 AYDHTRL454A 54.0 2 95 100 — —<br />

AYDHTRK472A 72.0 2 123 125 — —<br />

Notes:<br />

1. HACR type circuit breaker per NEC.<br />

2. Values do not include power exhaust accessory.<br />

3. Do not use <strong>with</strong> oversized motor.<br />

* Applies only to Dehumidification (Hot Gas Reheat) Models<br />

60 RT-PRC002-EN