<strong>Electric</strong>al<br />

Data<br />

(High Efficiency)<br />

Table ED-9 — Unit Wiring With <strong>Electric</strong> <strong>Heat</strong> (Single Point Connection) — High Efficiency, Standard Refrigeration System<br />

(Horizontal Only)<br />

Standard Indoor Motor Oversize Indoor Motor<br />

To Use <strong>Heat</strong>er <strong>Heat</strong>er Control Max Fuse Size or Max Fuse Size or<br />

Tons With Model No. KW Rating Stages MCA Max Circuit MCA Max Circuit<br />

Breaker 1 Breaker 2<br />

208/230 Volts Three Phase<br />

AYHHTRN318A 13.5/18.0 1 64/68 80/80 70/76 90/90<br />

12½ TCH151C3 AYHHTRP336A 27.0/36.0 2 108/122 110/125 115/130 125/150<br />

AYHHTRP354A 40.5/54.0 2 154/176 175/200 162/184 175/200<br />

AYHHTRM318A 13.5/18.0 1 74/74 100/100 80/80 100/100<br />

15 TCH181C3 AYHHTRM336A 27.0/36.0 2 108/122 110/125 115/130 125/150<br />

AYHHTRM354A 40.5/54.0 2 154/176 175/200 162/184 175/200<br />

AYHHTRN336A 27.0/36.0 2 115/130 125/150 125/139 125/150<br />

17½ TCH211C3 AYHHTRN354A 40.5/54.0 2 162/184 175/200 171/193 175/200<br />

AYHHTRN372A 54.0/72.0 2 209/238 225/250 218/247 225/250<br />

AYHHTRN336A 27.0/36.0 2 115/130 125/150 125/139 125/150<br />

20 TCH241C3 AYHHTRN354A 40.5/54.0 2 162/184 175/200 171/193 175/200<br />

AYHHTRN372A 54.0/72.0 2 209/238 225/250 218/247 225/250<br />

AYHHTRN336A 27.0/36.0 2 125/139 150/150 — —<br />

25 TCH301C3 AYHHTRN354A 40.5/54.0 2 171/193 175/200 — —<br />

AYHHTRN372A 54.0/72.0 2 218/247 225/250 — —<br />

460 Volts Three Phase<br />

AYHHTRN418A 18.0 1 34 40 37 40<br />

12½ TCH151C4 AYHHTRP436A 36.0 2 61 70 64 70<br />

AYHHTRP454A 54.0 2 88 90 91 100<br />

AYHHTRM418A 18.0 1 36 50 38 50<br />

15 TCH181C4 AYHHTRM436A 36.0 2 61 70 64 70<br />

AYHHTRM454A 54.0 2 88 90 91 100<br />

AYHHTRN436A 36.0 2 64 70 68 70<br />

17½ TCH211C4 AYHHTRN454A 54.0 2 91 100 95 100<br />

AYHHTRN472A 72.0 2 118 125 123 125<br />

AYHHTRN436A 36.0 2 64 70 68 70<br />

20 TCH241C4 AYHHTRN454A 54.0 2 91 100 95 100<br />

AYHHTRN472A 72.0 2 118 125 123 125<br />

AYHHTRN436A 36.0 2 68 70 — —<br />

25 TCH301C4 AYHHTRN454A 54.0 2 95 100 — —<br />

AYHHTRN472A 72.0 2 123 125 — —<br />

575 Volts Three Phase<br />

AYHHTRNW18A 18.0 1 27 30 30 35<br />

12½ TCH151CW AYHHTRPW36A 36.0 2 49 50 51 60<br />

AYHHTRPW54A 54.0 2 70 70 73 80<br />

AYHHTRMW18A 18.0 1 29 40 31 40<br />

15 TCH181CW AYHHTRMW36A 36.0 2 49 50 31 40<br />

AYHHTRMW54A 54.0 2 70 70 73 80<br />

AYHHTRMW36A 36.0 2 51 60 55 60<br />

17½ TCH211CW AYHHTRNW54A 54.0 2 73 80 77 80<br />

AYHHTRNW72A 72.0 2 95 100 98 100<br />

AYHHTRMW36A 36.0 2 51 60 55 60<br />

20 TCH241CW AYHHTRNW54A 54.0 2 73 80 77 80<br />

AYHHTRNW72A 72.0 2 95 100 98 100<br />

AYHHTRMW36A 36.0 2 55 60 — —<br />

25 TCH301CW AYHHTRNW54A 54.0 2 77 80 — —<br />

AYHHTRNW72A 72.0 2 98 100 — —<br />

Notes:<br />

1. HACR type circuit breaker per NEC.<br />

2. Values do not include power exhaust accessory.<br />

RT-PRC002-EN<br />