<strong>Electric</strong>al<br />

Data<br />

(High Efficiency)<br />

Table ED-5 — Unit Wiring - High Efficiency - Standard Refrigeration System<br />

Standard Indoor Fan Motor Oversize Indoor Fan Motor<br />

Unit Minimum Maximum Fuse Minimum Maximum Fuse<br />

Unit Operating Circuit Size or Maximum Circuit Size or Maximum<br />

Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1<br />

TC*151C3 187-253 64 80 70 90<br />

12½ TC*151C4 414-506 31 40 34 40<br />

TC*151CW 517-633 25 30 28 35<br />

TC*181C3 187-253 74 90 80 100<br />

15 TC*181C4 414-506 36 50 38 50<br />

TC*181CW 517-633 29 40 31 40<br />

TC*211C3 187-253 91 110 98 125<br />

17½ TC*211C4 414-506 44 60 48 60<br />

TC*211CW 517-633 35 45 38 50<br />

TC*241C3 187-253 99 125 107 125<br />

20 TC*241C4 414-506 50 60 54 60<br />

TC*241CW 517-633 40 50 43 50<br />

TC*301C3 187-253 120 150 N/A N/A<br />

25 TC*301C4 414-506 58 70 N/A N/A<br />

TC*301CW 517-633 47 60 N/A N/A<br />

Notes:<br />

1. HACR breaker per NEC.<br />

2. Values do not include power exhaust accessory.<br />

Table ED-6— Unit Wiring - High Efficiency - TXV/Face-Split Evaporator Coil Option (Downflow Only)<br />

Standard Indoor Fan Motor Oversize Indoor Fan Motor<br />

Unit Minimum Maximum Fuse Minimum Maximum Fuse<br />

Unit Operating Circuit Size or Maximum Circuit Size or Maximum<br />

Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1<br />

TCD151C3 187-253 59 70 65 80<br />

12½ TCD151C4 414-506 30 35 32 40<br />

TCD151CW 517-633 24 30 26 30<br />

TCD181C3 187-253 74 90 80 90<br />

15 TCD181C4 414-506 37 50 39 50<br />

TCD181CW 517-633 30 40 32 40<br />

TCD211C3 187-253 91 125 99 125<br />

17½ TCD211C4 414-506 45 60 49 60<br />

TCD211CW 517-633 36 45 39 50<br />

TCD241C3 187-253 99 125 107 125<br />

20 TCD241C4 414-506 51 60 54 70<br />

TCD241CW 517-633 40 50 43 50<br />

TCD301C3 187-253 117 150 N/A N/A<br />

25 TCD301C4 414-506 57 70 N/A N/A<br />

TCD301CW 517-633 46 50 N/A N/A<br />

Notes:<br />

1. HACR breaker per NEC.<br />

2. Values do not include power exhaust accessory.<br />