28.09.2014 Views

Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane

Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane

Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Electric</strong>al<br />

Data<br />

(Standard Efficiency)<br />

Table ED-4— <strong>Electric</strong>al Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency<br />

Compressor Motors<br />

Condenser Fan Motors<br />

Unit Amps 1 Amps 1<br />

Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA<br />

TC*150D3 2 208-230 3 6.00 3450 20.4 156 2 1 .50 3.2 8.8<br />

TC*150D4 2 460 3 6.00 3450 10.8 75 2 1 .50 1.6 3.8<br />

12½ TC*150DW 2 575 3 6.00 3450 8.3 54 2 1 .50 1.3 3.2<br />

TC*150DK 2 380 3 6.0 3450 13.1 70 2 1 .50 1.9 5.2<br />

TC*180B3 2 208-230 3 9.30/5.10 3450 31.9/20.7 253/128 2 1 .50 3.2 8.8<br />

15 TC*180B4 2 460 3 9.30/5.10 3450 16.3/10.0 113/63 2 1 .50 1.6 3.8<br />

TC*180BW 2 575 3 9.30/5.10 3450 13.1/7.4 85/49 2 1 .50 1.3 3.2<br />

TC*180BK 2 380 3 9.3/5.1 3450 19.7/12.1 125/64 2 1 .50 1.9 5.2<br />

TC*210C3 2 208-230 3 9.3/6.0 3450 31.5/20.8 253/156 2 1 1.00 5.5 18.3<br />

17½ TC*210C4 2 460 3 9.3/6.0 3450 15.9/10.0 113/75 2 1 1.00 2.9 9.3<br />

TC*210CW 2 575 3 9.3/6.0 3450 12.8/8.2 85/54 2 1 1.00 2.0 5.7<br />

TC*210CK 2 380 3 9.3/6.0 3450 19.2/12.1 125/70 2 1 1.00 3.5 8.5<br />

TC*240B3 2 208-230 3 9.30 3450 31.7 253 2 1 1.00 5.5 18.3<br />

20 TC*240B4 2 460 3 9.30 3450 16.2 113 2 1 1.00 2.9 9.3<br />

TC*240BW 2 575 3 9.30 3450 13.0 85 2 1 1.00 2.0 5.7<br />

TC*240BK 2 380 3 9.3 3450 19.6 125 2 1 1.00 3.5 8.5<br />

TC*300B3 2 208-230 3 10.00 3450 36.6 278 2 1 1.00 5.5 18.3<br />

25 TC*300B4 2 460 3 10.00 3450 17.9 124 2 1 1.00 2.9 9.3<br />

TC*300BW 2 575 3 10.00 3450 14.9 92 2 1 1.00 2.0 5.7<br />

TC*300BK 2 380 3 10.0 3450 21.7 137 2 1 1.00 3.5 8.5<br />

Notes:<br />

1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.<br />

2. HP for each compressor.<br />

*Indicates both downflow and horizontal units.<br />

RT-PRC002-EN<br />

55

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!