<strong>Electric</strong>al<br />

Data<br />

(Standard Efficiency)<br />

Table ED-1 — Unit Wiring — Standard Efficiency<br />

Standard Indoor Fan Motor Oversize Indoor Fan Motor<br />

Unit Minimum Maximum Fuse Minimum Maximum Fuse<br />

Unit Operating Circuit Size or Maximum Circuit Size or Maximum<br />

Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1<br />

TC*150D3 187-253 63 80 69 80<br />

12½ TC*150D4 414-506 33 40 36 40<br />

TC*150DW 518-633 26 30 28 35<br />

TC*150DK 342-418 43 50 – –<br />

TC*180B3 187-253 78 90 84 100<br />

15 TC*180B4 414-506 39 50 42 50<br />

TC*180BW 517-633 31 40 33 40<br />

TC*180BK 342-418 50 60 – –<br />

TC*210C3 187-253 88 100 96 125<br />

17½ TC*210C4 414-506 44 50 47 60<br />

TC*210CW 517-633 35 45 38 45<br />

TC*210CK 342-418 57 70 – –<br />

TC*240B3 187-253 100 125 107 125<br />

20 TC*240B4 414-506 50 60 54 60<br />

TC*240BW 517-633 40 45 43 50<br />

TC*240BK 342-418 65 80 – –<br />

TC*300B3 187-253 118 150 – –<br />

25 TC*300B4 414-506 58 70 – –<br />

TC*300BW 517-633 46 50 – –<br />

TC*300BK 342-418 70 80 – –<br />

Notes:<br />

1. HACR breaker per NEC.<br />

2. Values do not include power exhaust accessory.<br />

*Indicates both downflow and horizontal units.<br />

50 RT-PRC002-EN