<strong>Electric</strong>al<br />
Data<br />
(Standard Efficiency)<br />
Table ED-1 — Unit Wiring — Standard Efficiency<br />
Standard Indoor Fan Motor Oversize Indoor Fan Motor<br />
Unit Minimum Maximum Fuse Minimum Maximum Fuse<br />
Unit Operating Circuit Size or Maximum Circuit Size or Maximum<br />
Tons Model No. Voltage Range Ampacity 2 Circuit Breaker 1 Ampacity 2 Circuit Breaker 1<br />
TC*150D3 187-253 63 80 69 80<br />
12½ TC*150D4 414-506 33 40 36 40<br />
TC*150DW 518-633 26 30 28 35<br />
TC*150DK 342-418 43 50 – –<br />
TC*180B3 187-253 78 90 84 100<br />
15 TC*180B4 414-506 39 50 42 50<br />
TC*180BW 517-633 31 40 33 40<br />
TC*180BK 342-418 50 60 – –<br />
TC*210C3 187-253 88 100 96 125<br />
17½ TC*210C4 414-506 44 50 47 60<br />
TC*210CW 517-633 35 45 38 45<br />
TC*210CK 342-418 57 70 – –<br />
TC*240B3 187-253 100 125 107 125<br />
20 TC*240B4 414-506 50 60 54 60<br />
TC*240BW 517-633 40 45 43 50<br />
TC*240BK 342-418 65 80 – –<br />
TC*300B3 187-253 118 150 – –<br />
25 TC*300B4 414-506 58 70 – –<br />
TC*300BW 517-633 46 50 – –<br />
TC*300BK 342-418 70 80 – –<br />
Notes:<br />
1. HACR breaker per NEC.<br />
2. Values do not include power exhaust accessory.<br />
*Indicates both downflow and horizontal units.<br />