Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane
Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane
Performance Data Table PD-39— Hot Gas Reheat Temperature Rise 1,2,3 Leaving Evaporator Dry Bulb [F] 1 Tons SCFM 35 40 45 50 55 60 65 2500 23.4 23.8 25.0 26.9 29.5 32.9 37.0 3000 21.4 21.6 22.5 24.0 26.0 28.7 31.9 3500 19.5 19.7 20.4 21.5 23.1 25.2 27.7 12½ 4000 17.8 18.1 18.6 19.6 20.9 22.5 24.5 4500 16.3 16.7 17.3 18.1 19.2 20.5 22.1 5000 14.9 15.5 16.2 17.1 18.0 19.2 20.4 5500 13.5 14.4 15.3 16.2 17.2 18.1 19.1 6000 12.1 13.4 14.6 15.7 16.7 17.6 18.3 Tons SCFM 35 40 45 50 55 60 65 3000 34.4 36.7 38.9 41.2 43.5 45.8 48.1 3600 29.3 31.2 33.1 35.0 36.9 38.8 40.8 4200 25.4 27.0 28.6 30.2 31.9 33.5 35.1 15 4800 22.3 23.7 25.1 26.5 27.9 29.3 30.7 5400 19.9 21.2 22.4 23.7 24.9 26.2 27.4 6000 18.0 19.1 20.3 21.4 22.5 23.7 24.8 6600 16.4 17.5 18.6 19.6 20.7 21.7 22.8 7200 15.1 16.1 17.1 18.1 19.1 20.1 21.1 Tons SCFM 35 40 45 50 55 60 65 4000 22.0 22.5 23.6 25.4 27.7 30.6 34.0 4800 19.1 19.8 20.9 22.3 24.0 26.1 28.5 5600 16.6 17.4 18.4 19.5 20.9 22.4 24.0 20 6400 14.7 15.5 16.3 17.2 18.2 19.3 20.6 7200 13.5 14.1 14.7 15.4 16.2 17.0 17.9 8000 12.9 13.2 13.7 14.2 14.8 15.5 16.2 8800 12.5 12.9 13.3 13.7 14.2 14.8 15.4 9600 12.4 12.8 13.1 13.5 13.9 14.5 15.0 Notes: 1. Temperature does not account for indoor fan heat. 2. 70 deg OD Ambient Temperature. 3. For units with the Dehumidification (Hot Gas Reheat) option. 48 RT-PRC002-EN
Controls Field Installed Control Options Zone Sensors Zone sensors are the building occupant’s comfort control devices. They replace the conventional electro-mechanical thermostats. The following zone sensor options are available for Voyager units with the ReliaTel control: Manual Changeover Heat, Cool or Off System Switch. Fan Auto or Off Switch. One temperature setpoint lever. Manual/Automatic Changeover Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch. Two temperature setpoint levers. Optional Status Indication LED lights, System On, Heat, Cool, or Service. Remote Sensor Sensor(s) available for all zone sensors to provide remote sensing capabilities. Dual Thermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. RT-PRC002-EN Digital Display Zone Sensor The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC). This sensor should be utilized with ReliaTel controls. Programmable Night Setback Auto or manual changeover with sevenday programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and two (2) Override programs per day. Integrated Comfort TM System Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane Integrated Comfort system. CO Sensing The CO 2 2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventilation requirements. The CO 2 sensor kit is available as a field installed accessory. Economizer Controls The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two optional controls, Enthalpy and Differential Enthalpy Control. Enthalpy Control Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable set point. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability. Differential Enthalpy Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source. This control option offers the highest level of comfort control, plus energy efficiency, available. Remote Potentiometer Minimum position setting of economizer can be remotely adjusted with this accessory. Differential Pressure Switches This factory or field-installed option allows individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation. Trane Communication Interface (TCI) This factory or field-installed microprocessor interface allows the unit to communicate to Trane’s Integrated Comfort system. 49
- Page 1 and 2: Packaged Cooling with Electric Heat
- Page 3 and 4: Contents Introduction Features and
- Page 5 and 6: Features and Benefits Easy to Insta
- Page 7 and 8: Features and Benefits Reference or
- Page 9 and 10: Application Considerations Applicat
- Page 11 and 12: Selection Procedure Dehumidificatio
- Page 13 and 14: General Data (12½, 15 Ton) Standar
- Page 15 and 16: General Data (12½, 15 Ton) High Ef
- Page 17 and 18: Performance Data (12½, 15 Ton) Sta
- Page 19 and 20: Performance Data (25 Ton) Standard
- Page 21 and 22: Performance Data (12½ Ton) High Ef
- Page 23 and 24: Performance Data (15 Ton) High Effi
- Page 25 and 26: Performance Data (17½ Ton) High Ef
- Page 27 and 28: Performance Data (20 Ton) High Effi
- Page 29 and 30: Performance Data (25 Ton) High Effi
- Page 31 and 32: Performance Data (12½ Ton) Standar
- Page 33 and 34: Performance Data (17½Ton) Standard
- Page 35 and 36: Performance Data (25 Ton) Standard
- Page 37 and 38: Performance Data (12½ Ton) High Ef
- Page 39 and 40: Performance Data (15 Ton) High Effi
- Page 41 and 42: Performance Data (17½ Ton) High Ef
- Page 43 and 44: Performance Data (20 Ton) High Effi
- Page 45 and 46: Performance Data (12½-25 Ton) Tabl
- Page 47: Performance Data (12½-25 Ton) Tabl
- Page 51 and 52: Electrical Data (Standard Efficienc
- Page 53 and 54: Electrical Data (Standard Efficienc
- Page 55 and 56: Electrical Data (Standard Efficienc
- Page 57 and 58: Electrical Data (High Efficiency) T
- Page 59 and 60: Electrical Data (High Efficiency) T
- Page 61 and 62: Electrical Data (High Efficiency) T
- Page 63 and 64: Electrical Data Table ED-14 — Ele
- Page 65 and 66: Jobsite Connections ZONE SENSORS DI
- Page 67 and 68: Typical Wiring (12½-25 Ton) Typica
- Page 69 and 70: Typical Wiring (12½-25 Ton) RT-PRC
- Page 71 and 72: Dimensional Data (12½ Ton) High Ef
- Page 73 and 74: Dimensional Data (15-25 Ton) High E
- Page 75 and 76: Dimensional Data Factory Installed
- Page 77 and 78: Dimensional Data (12½-25 Ton) Tabl
- Page 79 and 80: Weights Table W-2 — Maximum Unit
- Page 81 and 82: Mechanical Specifications General T
- Page 83 and 84: Mechanical Specifications Factory o
- Page 85 and 86: RT-PRC002-EN 85
- Page 87 and 88: RT-PRC002-EN 87
Performance<br />
Data<br />
Table PD-39— Hot Gas Reheat Temperature Rise 1,2,3<br />
Leaving Evaporator Dry Bulb [F] 1<br />
Tons SCFM 35 40 45 50 55 60 65<br />
2500 23.4 23.8 25.0 26.9 29.5 32.9 37.0<br />
3000 21.4 21.6 22.5 24.0 26.0 28.7 31.9<br />
3500 19.5 19.7 20.4 21.5 23.1 25.2 27.7<br />
12½ 4000 17.8 18.1 18.6 19.6 20.9 22.5 24.5<br />
4500 16.3 16.7 17.3 18.1 19.2 20.5 22.1<br />
5000 14.9 15.5 16.2 17.1 18.0 19.2 20.4<br />
5500 13.5 14.4 15.3 16.2 17.2 18.1 19.1<br />
6000 12.1 13.4 14.6 15.7 16.7 17.6 18.3<br />
Tons SCFM 35 40 45 50 55 60 65<br />
3000 34.4 36.7 38.9 41.2 43.5 45.8 48.1<br />
3600 29.3 31.2 33.1 35.0 36.9 38.8 40.8<br />
4200 25.4 27.0 28.6 30.2 31.9 33.5 35.1<br />
15 4800 22.3 23.7 25.1 26.5 27.9 29.3 30.7<br />
5400 19.9 21.2 22.4 23.7 24.9 26.2 27.4<br />
6000 18.0 19.1 20.3 21.4 22.5 23.7 24.8<br />
6600 16.4 17.5 18.6 19.6 20.7 21.7 22.8<br />
7200 15.1 16.1 17.1 18.1 19.1 20.1 21.1<br />
Tons SCFM 35 40 45 50 55 60 65<br />
4000 22.0 22.5 23.6 25.4 27.7 30.6 34.0<br />
4800 19.1 19.8 20.9 22.3 24.0 26.1 28.5<br />
5600 16.6 17.4 18.4 19.5 20.9 22.4 24.0<br />
20 6400 14.7 15.5 16.3 17.2 18.2 19.3 20.6<br />
7200 13.5 14.1 14.7 15.4 16.2 17.0 17.9<br />
8000 12.9 13.2 13.7 14.2 14.8 15.5 16.2<br />
8800 12.5 12.9 13.3 13.7 14.2 14.8 15.4<br />
9600 12.4 12.8 13.1 13.5 13.9 14.5 15.0<br />
Notes:<br />
1. Temperature does not account for indoor fan heat.<br />
2. 70 deg OD Ambient Temperature.<br />
3. For units <strong>with</strong> the Dehumidification (Hot Gas Reheat) option.<br />
48 RT-PRC002-EN