Performance Data (20 Ton) High Efficiency Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Standard or TXV Refrigeration System External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field Supplied 5 HP Standard Motor & Field Extra Low Static Drive (3) Supplied Low Static Drive (1) 4000* — — — — 428 0.69 467 0.82 504 0.95 538 1.08 572 1.23 603 1.38 632 1.55 660 1.71 5200* 426 0.94 463 1.09 494 1.22 524 1.35 555 1.51 585 1.67 614 1.83 642 2.00 670 2.17 696 2.35 6400 506 1.64 540 1.84 570 2.03 595 2.19 620 2.34 644 2.51 669 2.69 693 2.89 717 3.09 741 3.29 7200 560 2.28 592 2.50 620 2.72 646 2.92 668 3.10 690 3.27 711 3.45 733 3.65 755 3.86 777 4.08 8000 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03 8800 671 4.04 698 4.29 724 4.55 747 4.83 769 5.10 790 5.34 808 5.56 826 5.77 844 5.98 861 6.20 9600 728 5.19 753 5.46 776 5.74 799 6.04 820 6.34 840 6.63 859 6.90 876 7.14 893 7.37 909 7.59 5 HP Standard Motor & Drive (2) 7.5 HP Oversized Motor & Drive Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory 4000* 688 1.87 714 2.03 739 2.20 764 2.36 787 2.53 810 2.70 831 2.87 852 3.05 873 3.23 892 3.41 5200* 722 2.54 747 2.73 771 2.93 795 3.14 817 3.35 839 3.56 861 3.77 882 3.98 902 4.19 923 4.41 6400 765 3.49 788 3.70 810 3.91 832 4.12 854 4.34 875 4.57 896 4.80 916 5.04 936 5.29 955 5.54 7200 799 4.31 820 4.53 841 4.76 862 4.99 883 5.22 902 5.46 922 5.69 942 5.94 961 6.19 980 6.44 8000 837 5.26 857 5.51 876 5.76 896 6.01 915 6.26 934 6.52 953 6.77 971 7.03 989 7.29 — — 8800 879 6.43 897 6.67 915 6.93 933 7.19 951 7.46 969 7.74 986 8.01 — — — — — — 9600 925 7.83 941 8.07 958 8.32 974 8.58 — — — — — — — — — — — — 7.5 HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. *Unit applications below 6400 CFM • Electric heaters restricted on applications below 6400 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary. 2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary. 3. Field Supplied Fan Sheave B5V200 and Motor Sheave IVP34 required. Field Supplied Belt may be necessary. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. *Indicates both downflow and horizontal units. 42 RT-PRC002-EN
Performance Data (20 Ton) High Efficiency Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Dehumidification (Hot Gas Reheat) Option External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Field 5 HP Standard Motor & Drive & Field Supplied 5 HP Standard Supplied Fan Sheave (1) Low Static Fan Sheave Motor & Drive 4000* — — — — 441 0.77 477 0.90 511 1.03 543 1.17 573 1.32 603 1.47 631 1.63 658 1.78 4800* 414 0.84 452 0.99 487 1.13 519 1.27 550 1.43 579 1.59 607 1.74 635 1.91 660 2.08 686 2.26 5600* 469 1.25 504 1.45 536 1.61 566 1.78 594 1.95 620 2.12 647 2.30 672 2.49 696 2.67 720 2.87 6400 525 1.80 558 2.03 588 2.24 615 2.42 641 2.61 666 2.80 689 3.00 713 3.20 736 3.41 758 3.62 7200 583 2.50 613 2.75 641 3.02 666 3.23 690 3.44 714 3.65 736 3.86 758 4.08 778 4.30 799 4.53 8000 641 3.37 669 3.64 695 3.93 719 4.21 742 4.45 763 4.67 785 4.91 805 5.14 825 5.38 844 5.62 8800 699 4.42 725 4.72 750 5.03 773 5.35 794 5.65 815 5.91 835 6.15 854 6.41 873 6.66 892 6.93 9600 758 5.67 782 6.00 805 6.32 827 6.68 848 7.04 867 7.35 886 7.63 904 7.90 923 8.18 941 8.46 7.5 HP Oversized Motor & Drive (3) 5 HP Standard Motor & High StaticDrive Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Continued External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive 4000* 684 1.94 708 2.10 731 2.27 753 2.43 775 2.60 795 2.77 814 2.94 834 3.12 852 3.29 870 3.47 4800* 711 2.44 735 2.63 758 2.81 780 3.00 802 3.19 823 3.38 843 3.58 864 3.78 882 3.97 901 4.17 5600* 743 3.06 765 3.26 787 3.46 809 3.67 830 3.88 850 4.09 871 4.31 890 4.53 910 4.75 929 4.98 6400 779 3.82 800 4.04 821 4.26 841 4.48 861 4.70 881 4.93 899 5.16 919 5.41 938 5.66 956 5.90 7200 819 4.76 840 5.00 859 5.23 879 5.47 898 5.72 916 5.96 933 6.19 952 6.46 968 6.70 987 6.97 8000 863 5.87 881 6.12 900 6.38 918 6.64 936 6.90 954 7.16 971 7.42 988 7.69 — — — — 8800 909 7.19 927 7.46 944 7.73 961 8.01 978 8.29 994 8.56 — — — — — — — — 9600 — — — — — — — — — — — — — — — — — — — — 7.5 HP Oversized Motor & Drive For Standard Evaporator Fan Speed (RPM), reference Table PD-31. For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32. For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 6400 CFM • Electric heaters restricted on applications below 6400 CFM. • Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM. Fan motor heat (MBH) = 3.15 x Fan BHP Data includes pressure drop due to wet coils and filters. No accessories or options are included in pressure drop data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories. Notes: 1. Field Supplied Motor Sheave IVP34 Required. Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary. 3. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected. RT-PRC002-EN 43
- Page 1 and 2: Packaged Cooling with Electric Heat
- Page 3 and 4: Contents Introduction Features and
- Page 5 and 6: Features and Benefits Easy to Insta
- Page 7 and 8: Features and Benefits Reference or
- Page 9 and 10: Application Considerations Applicat
- Page 11 and 12: Selection Procedure Dehumidificatio
- Page 13 and 14: General Data (12½, 15 Ton) Standar
- Page 15 and 16: General Data (12½, 15 Ton) High Ef
- Page 17 and 18: Performance Data (12½, 15 Ton) Sta
- Page 19 and 20: Performance Data (25 Ton) Standard
- Page 21 and 22: Performance Data (12½ Ton) High Ef
- Page 23 and 24: Performance Data (15 Ton) High Effi
- Page 25 and 26: Performance Data (17½ Ton) High Ef
- Page 27 and 28: Performance Data (20 Ton) High Effi
- Page 29 and 30: Performance Data (25 Ton) High Effi
- Page 31 and 32: Performance Data (12½ Ton) Standar
- Page 33 and 34: Performance Data (17½Ton) Standard
- Page 35 and 36: Performance Data (25 Ton) Standard
- Page 37 and 38: Performance Data (12½ Ton) High Ef
- Page 39 and 40: Performance Data (15 Ton) High Effi
- Page 41: Performance Data (17½ Ton) High Ef
- Page 45 and 46: Performance Data (12½-25 Ton) Tabl
- Page 47 and 48: Performance Data (12½-25 Ton) Tabl
- Page 49 and 50: Controls Field Installed Control Op
- Page 51 and 52: Electrical Data (Standard Efficienc
- Page 53 and 54: Electrical Data (Standard Efficienc
- Page 55 and 56: Electrical Data (Standard Efficienc
- Page 57 and 58: Electrical Data (High Efficiency) T
- Page 59 and 60: Electrical Data (High Efficiency) T
- Page 61 and 62: Electrical Data (High Efficiency) T
- Page 63 and 64: Electrical Data Table ED-14 — Ele
- Page 65 and 66: Jobsite Connections ZONE SENSORS DI
- Page 67 and 68: Typical Wiring (12½-25 Ton) Typica
- Page 69 and 70: Typical Wiring (12½-25 Ton) RT-PRC
- Page 71 and 72: Dimensional Data (12½ Ton) High Ef
- Page 73 and 74: Dimensional Data (15-25 Ton) High E
- Page 75 and 76: Dimensional Data Factory Installed
- Page 77 and 78: Dimensional Data (12½-25 Ton) Tabl
- Page 79 and 80: Weights Table W-2 — Maximum Unit
- Page 81 and 82: Mechanical Specifications General T
- Page 83 and 84: Mechanical Specifications Factory o
- Page 85 and 86: RT-PRC002-EN 85
- Page 87 and 88: RT-PRC002-EN 87
Performance<br />
Data<br />
(20 Ton)<br />
High Efficiency<br />
Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Standard or TXV Refrigeration System<br />
External Static Pressure (Inches of Water)<br />
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
5 HP Standard Motor & Field Supplied 5 HP Standard Motor & Field<br />
Extra Low Static Drive (3) Supplied Low Static Drive (1)<br />
4000* — — — — 428 0.69 467 0.82 504 0.95 538 1.08 572 1.23 603 1.38 632 1.55 660 1.71<br />
5200* 426 0.94 463 1.09 494 1.22 524 1.35 555 1.51 585 1.67 614 1.83 642 2.00 670 2.17 696 2.35<br />
6400 506 1.64 540 1.84 570 2.03 595 2.19 620 2.34 644 2.51 669 2.69 693 2.89 717 3.09 741 3.29<br />
7200 560 2.28 592 2.50 620 2.72 646 2.92 668 3.10 690 3.27 711 3.45 733 3.65 755 3.86 777 4.08<br />
8000 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03<br />
8800 671 4.04 698 4.29 724 4.55 747 4.83 769 5.10 790 5.34 808 5.56 826 5.77 844 5.98 861 6.20<br />
9600 728 5.19 753 5.46 776 5.74 799 6.04 820 6.34 840 6.63 859 6.90 876 7.14 893 7.37 909 7.59<br />
5 HP Standard Motor & Drive (2) 7.5 HP Oversized Motor & Drive<br />
Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued<br />
External Static Pressure (Inches of Water)<br />
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
5 HP Standard Motor & Drive 5 HP Standard Motor<br />
& High Static Drive Accessory<br />
4000* 688 1.87 714 2.03 739 2.20 764 2.36 787 2.53 810 2.70 831 2.87 852 3.05 873 3.23 892 3.41<br />
5200* 722 2.54 747 2.73 771 2.93 795 3.14 817 3.35 839 3.56 861 3.77 882 3.98 902 4.19 923 4.41<br />
6400 765 3.49 788 3.70 810 3.91 832 4.12 854 4.34 875 4.57 896 4.80 916 5.04 936 5.29 955 5.54<br />
7200 799 4.31 820 4.53 841 4.76 862 4.99 883 5.22 902 5.46 922 5.69 942 5.94 961 6.19 980 6.44<br />
8000 837 5.26 857 5.51 876 5.76 896 6.01 915 6.26 934 6.52 953 6.77 971 7.03 989 7.29 — —<br />
8800 879 6.43 897 6.67 915 6.93 933 7.19 951 7.46 969 7.74 986 8.01 — — — — — —<br />
9600 925 7.83 941 8.07 958 8.32 974 8.58 — — — — — — — — — — — —<br />
7.5 HP Oversized Motor & Drive<br />
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.<br />
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.<br />
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.<br />
*Unit applications below 6400 CFM<br />
• <strong>Electric</strong> heaters restricted on applications below 6400 CFM.<br />
• Dehumidification (Hot Gas Reheat) or TXV <strong>with</strong> Frostat and Crankcase <strong>Heat</strong>ers<br />
are required on applications below 6400 CFM.<br />
Fan motor heat (MBH) = 3.15 x Fan BHP<br />
Data includes pressure drop due to wet coils and filters.<br />
No accessories or options are included in pressure drop data.<br />
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.<br />
Notes:<br />
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.<br />
2. 7.5 HP Standard Motor <strong>with</strong> Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt<br />
may be necessary.<br />
3. Field Supplied Fan Sheave B5V200 and Motor Sheave IVP34 required. Field Supplied Belt may<br />
be necessary.<br />
Factory supplied motors, in commercial equipment, are<br />
definite purpose motors, specifically designed and tested to<br />
operate reliably and continuously at all cataloged conditions.<br />
Using the full horsepower range of our fan motors as shown<br />
in our tabular data will not result in nuisance tripping or<br />
premature motor failure. Our product’s warranty will not be<br />
affected.<br />
*Indicates both downflow and horizontal units.<br />
42 RT-PRC002-EN