Performance<br />

Data<br />

(15 Ton)<br />

High Efficiency<br />

Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Standard or TXV Refrigeration System<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3 HP Standard Motor & 3 HP Standard Motor & Field<br />

Field Supplied Extra Supplied Low Static Drive (1)<br />

L ow Static Drive (2)<br />

3000* — — 337 0.32 387 0.42 432 0.53 472 0.65 511 0.77 547 0.90 580 1.03 611 1.16 640 1.29<br />

3900* 341 0.45 384 0.55 423 0.66 462 0.78 500 0.91 536 1.05 569 1.19 600 1.35 630 1.51 660 1.67<br />

4800 399 0.76 437 0.89 471 1.01 503 1.14 535 1.29 566 1.44 598 1.60 629 1.77 658 1.94 684 2.11<br />

5400 445 1.04 474 1.19 506 1.33 536 1.47 564 1.62 592 1.78 621 1.95 648 2.12 676 2.30 704 2.49<br />

6000 479 1.38 513 1.55 543 1.72 571 1.87 597 2.03 623 2.19 648 2.36 673 2.55 699 2.74 723 2.93<br />

6600 519 1.79 552 1.98 580 2.17 606 2.35 632 2.52 656 2.69 679 2.87 702 3.05 725 3.25 748 3.46<br />

7200 560 2.28 591 2.49 618 2.70 643 2.91 667 3.09 690 3.27 712 3.46 734 3.65 755 3.85 776 4.06<br />

3 HP Standard Motor & Drive 5 HP Oversized Motor & Drive<br />

Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3 HP Standard Motor & Drive 3 HP Standard Motor & High<br />

Static Drive Accessory<br />

3000* 667 1.43 693 1.57 717 1.71 740 1.86 763 2.01 784 2.16 805 2.31 825 2.47 845 2.63 864 2.80<br />

3900* 688 1.84 715 2.00 741 2.17 766 2.34 790 2.51 812 2.68 834 2.85 855 3.03 875 3.21 895 3.39<br />

4800 710 2.29 735 2.48 760 2.68 785 2.88 809 3.09 832 3.29 854 3.49 876 3.69 898 3.90 919 4.10<br />

5400 730 2.68 755 2.88 778 3.07 800 3.28 823 3.49 845 3.71 867 3.94 889 4.17 910 4.40 931 4.62<br />

6000 749 3.13 774 3.34 798 3.56 821 3.77 842 3.99 863 4.20 884 4.43 904 4.66 924 4.90 944 5.15<br />

6600 771 3.67 794 3.88 816 4.09 839 4.32 862 4.56 884 4.80 904 5.03 924 5.27 943 5.51 961 5.75<br />

7200 797 4.29 818 4.51 839 4.74 860 4.96 881 5.20 902 5.45 923 5.70 — — — — — —<br />

5 HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.<br />

For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.<br />

For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.<br />

*Unit applications below 4000 CFM<br />

• <strong>Electric</strong> heaters restricted on applications below 4000 CFM.<br />

• Dehumidification (Hot Gas Reheat) or TXV <strong>with</strong> Frostat and Crankcase<br />

<strong>Heat</strong>ers<br />

are required on applications below 4000 CFM.<br />

Fan motor heat (MBH) = 3.15 x Fan BHP<br />

Data includes pressure drop due to wet coils and filters.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-35 to determine add’l static pressure drop due to other options/ccessories.<br />

Note:<br />

1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field<br />

Supplied Belt may be necessary.<br />

Factory supplied motors, in commercial equipment, are<br />

definite purpose motors, specifically designed and tested to<br />

operate reliably and continuously at all cataloged conditions.<br />

Using the full horsepower range of our fan motors as shown<br />

in our tabular data will not result in nuisance tripping or<br />

premature motor failure. Our product’s warranty will not be<br />

affected.<br />

*Indicates both downflow and horizontal units.<br />

RT-PRC002-EN<br />